37. Minimum setbacks for high rise buildings.

Table -14: Minimum exterior open spaces around the buildings for all type of high rise buildings unless otherwise specified
Table -14: Minimum exterior open spaces around the buildings for all type of high rise buildings unless otherwise specified
Sl.
Sl.
Height of the Building Upto (m)
Height of the Building Upto (m)
Exterior open spaces to be left out on all
sides in m.
Exterior open spaces to be left out on all
sides in m.
Front setback
Front setback
Side and Rear setback
Side and Rear setback
1
More than 16.4 and upto 19.25m
6.5
4.5
2
More than 19.25m and upto 23.10m
7.5
4.5
3
More than 23.10m and upto 30m
8.0
5.0
4
In case of buildings of more than 30m height, for
every increase in height of 3.35m. or fraction thereof or
addition of one floor, 1m. in the front set back and 0.75 m. in
the sides and rear setbacks shall be added.
Note:- (1) In no case the minimum setbacks shall be less than those specified in sub-section 42.1 of these Bye Law for high rise buildings in the mentioned category.
(2) In case of multi storied buildings the exterior open space around a building shall be of hard surface capable of taking load of fire, engine weighting up to 45 tones.
Coverage of Building
Maximum ground coverage