31. Electrical apparatus and installations

(i) all electrical meters, distribution boards, switches, fuses, plugs and sockets shall be of flame proof construction complying with the requirements of IS : 2148 : 1968 and the frames shall be effectively earthed;
(ii) all electrical fixed lamps shall be enclosed in a well glass flame proof fitting conforming to IS : 2206 (Part I) : 1962.
[31-A. Classification of hazardous area for flammable gases
(a) a division "0" area, if inflammable gases of vapours are expected to be continuously present in the area;
(b) a division "1" area, if inflammable gases or vapours are likely to be present in the area under normal operating conditions; or
(c) a division "2" area, if inflammable gases or vapours are likely to be present in the area only under abnormal operating conditions or failure or rupture of an equipment.
31-B. Extent of hazardous area
(i) Entire space within the dispenser enclosure cabinet and forty-six centimetres horizontally from the exterior of enclosure cabinet and up to an elevation of one hundred and twenty-two centimetres above dispenser base and the entire pit or open space beneath the dispenser shall be division "1";
(ii) Up to forty-six centimetres vertically, above the surrounding ground level and horizontally beyond forty-six centimetres up to six metres on all sides of the dispenser enclosure cabinet shall be division "2".]