(a) diameter of the vessel, in case of vessels with water capacity not exceeding forty thousand litres,
(b) fifteen metres, if the water capacity of the vessels exceeds forty thousand litres.]
[22. Location of pressure vessel
TABLE 1
MINIMUM SAFETY
DISTANCES FOR CORROSIVE, TOXIC OR PERMANENT FLAMMABLE GASES
Sl. Nos Water capacity of vessel(in litres) Minimum distance From building or group of buildings or line of adjoining property Minimum distance between pressure vessels (1) (2) (3) (4) (i) (ii) (iii) (iv) (v) Not above 2000 Above 2000 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 5 metres 10 metres 15 metres 20 metres 30 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres
Sl.
Nos
Water capacity of vessel(in litres)
Minimum distance
From building or group of buildings or line of
adjoining property
Minimum distance
between pressure
vessels
(1)
(2)
(3)
(4)
(i)
(ii)
(iii)
(iv)
(v)
Not above 2000
Above 2000 but not above 10,000
Above 10,000 but not above 20,000
Above 20,000 but not above 40,000
Above 40,000
5 metres
10 metres
15 metres
20 metres
30 metres
1 metre
1 metre
1.5 metres
2 metres
2 metres
TABLE 2
Minimum safety distances for non-corrosive, non-flammable or non-toxic gases
Sl. Nos Water capacity of vessel(in litres) Minimum distance from building or group of buildings or line of adjoining property Minimum distance between pressure vessels (1) (2) (3) (4) (i) (ii) (iii) (iv) (v) Not above 2000 Above 2000 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 3 metres 5 metres 7.5 metres 10 metres 15 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres
Sl.
Nos
Water capacity of vessel(in litres)
Minimum distance from
building or group of
buildings or line of
adjoining property
Minimum distance
between pressure
vessels
(1)
(2)
(3)
(4)
(i)
(ii)
(iii)
(iv)
(v)
Not above 2000
Above 2000 but not above 10,000
Above 10,000 but not above 20,000
Above 20,000 but not above 40,000
Above 40,000
3 metres
5 metres
7.5 metres
10 metres
15 metres
1 metre
1 metre
1.5 metres
2 metres
2 metres
TABLE 3
Minimum safety distances for liquefied
flammable gases
Sl. No. Water capacity of vessel (in litres) Minimum distance from building or group of buildings or line of adjoining property Minimum distance between vessels Above ground level Underground or Aboveground vessels covered with earth(mound) Above ground level Underground or aboveground vessels covered with earth(mound) (1) (2) (3) (4) (5) (6) (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) Not above 2000 Above 2000 but not above 75,00 Above 75,00 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 but not above 3,50,000 Above 3,50,000 but not above 4,50,000 Above 4,50,000 but not above 7,50,000 Above 7,50,000 but not above 38,00,000 Above 38,00,000 5 metres 10 metres 10 metres 15 metres 20 metres 30 metres 40 metres 60 metres 90 metres 120 metres 3 metres 3 metres 5 metres 7.5 metres 10 metres 15 metres 15 metres 15 metres 15 metres 15 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres 2 metres or ¼ th of the sum of the sum of diameter of adjacent vessel or ½ the diameter of the two adjacent vessels, whichever is greater 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre
Sl.
No.
Water capacity of vessel
Minimum distance from building or group of buildings or line of
Minimum distance between
Above
ground
level
Underground or Aboveground vessels covered
with
Above
ground
level
Underground or aboveground
vessels covered
with earth(mound)
(1)
(2)
(3)
(4)
(5)
(6)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)
(x)
Not above 2000
Above 2000 but not above 75,00
Above 75,00 but not above 10,000
Above 10,000 but not above 20,000
Above 20,000 but not above 40,000
Above 40,000 but not above 3,50,000
Above 3,50,000 but not above 4,50,000
Above 4,50,000 but not above 7,50,000
Above 7,50,000 but not above 38,00,000
Above 38,00,000
5 metres
10 metres
10 metres
15 metres
20 metres
30 metres
40 metres
60 metres
90 metres
120 metres
3 metres
3 metres
5 metres
7.5 metres
10 metres
15 metres
15 metres
15 metres
15 metres
15 metres
1 metre
1 metre
1.5 metres
2 metres
2 metres
2 metres or ¼ th
of the sum of
the sum of
diameter of
adjacent vessel
or ½ the
diameter of the
two adjacent
vessels,
whichever is
greater
1 metre
1 metre
1 metre
1 metre
1 metre
1 metre
1 metre
1 metre
1 metre
1 metre
TABLE 4
Minimum Safety distances (in meters) between
facilities associated with storage of liquefied flammable gas in petroleum
refinery, gas processing plants, storage terminals and bottling plants.
(A) For Total Storage not Above 100
Tonnes
(A) For Total Storage not Above 100
Tonnes
From/To Storage Vessel Property line/ buildings not associated with storage and operation Sheds for filling storage, evacuation of cylinders Tank Truck loading/ unloading gantry Tank Wagon gantry Pump/ compres sor Shed Fire Water Pump room (1) (2) (3) (4) (5) (6) (7) (8) Storage vessel Table -3 Table - 3 30 30 50 15 60 Property line/ buildings not associated with storage and operation Table -3 ----- 30 30 50 30 -- Sheds for filling storage, evacuation of cylinders 30 30 15 30 50 15 60 Tank Truck loading/ unloading gantry 30 30 30 30 50 30 60 Tank Wagon gantry 50 50 50 50 50 30 60 Pump/compressor Shed 15 30 15 30 30 --- 60 Fire Water Pump room 60 --- 60 60 60 60 ---
From/To
Storage
Vessel
Property line/ buildings not
associated
with storage
and operation
Sheds for
filling
storage,
evacuation
of
cylinders
Tank Truck
loading/
unloading
gantry
Tank
Wagon
gantry
Pump/
compres
sor
Shed
Fire
Water
Pump
room
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Storage vessel
Table -3
Table - 3
30
30
50
15
60
Property line/
buildings not
associated with
storage and
operation
Table -3
-----
30
30
50
30
--
Sheds for filling
storage,
evacuation of
cylinders
30
30
15
30
50
15
60
Tank Truck
loading/
unloading gantry
30
30
30
30
50
30
60
Tank Wagon
gantry
50
50
50
50
50
30
60
Pump/compressor
Shed
15
30
15
30
30
---
60
Fire Water Pump
room
60
---
60
60
60
60
---
(B) For Total Storage not Above 100
Tonnes
(B) For Total Storage not Above 100
Tonnes
From/To Storage Vessel Property line/ buildings not associated with storage and operation Sheds for filling storage, evacuation of cylinders Tank truck unloading/ loading gantry Fire Water Pump room (1) (2) (3) (4) (5) (6) Storage Vessel Table-3 Table 3 Table - 3 15 30 Property line/buildings not associated with storage & operation Table-3 ----- 15 15 -- Sheds for filling storage, evacuation of cylinders Table - 3 15 15 15 30 Tank truck unloading/loading gantry 15 15 15 15 30 Fire Water Pump room 30 -- 30 30 --
From/To
Storage
Vessel
Property line/
buildings not
associated
with storage
and operation
Sheds for filling
storage,
evacuation of
cylinders
Tank truck
unloading/
loading gantry
Fire
Water
Pump
room
(1)
(2)
(3)
(4)
(5)
(6)
Storage Vessel
Table-3
Table 3
Table - 3
15
30
Property line/buildings not
associated with storage &
operation
Table-3
-----
15
15
--
Sheds for filling storage,
evacuation of cylinders
Table - 3
15
15
15
30
Tank truck
unloading/loading gantry
15
15
15
15
30
Fire Water Pump room
30
--
30
30
--
TABLE 5
Minimum Safety distances (in metres) between
facilities associated with storage and dispensing of liquefied petroleum gas in
liquefied Petroleum gas dispensing station as automotive fuel to motor vehicles .
To/ From Liquefied Petroleu mLPG Storage Vessels Fill point of LPG Storage vessel and Centre of LPG Tank-Truck unloading hard stand Liquefied petroleum gas Dispenser Property line Petroleum Class A or B service Station licensed in Form XII of Petroleum Rules 1976 Fill point of petroleum tanks Vent pipe Of petrolem tanks Petroleum Class A/B dispensig pump Liquefied petroleum gas storage vessels Table-3 9 (aboveground/ mounded vessels exceeding 7500 litres capacity) 6 (aboveground/ mounded vessels not exceeding 7500 litres capacity ) 3 (underground vessel) 15 (aboveground vessels exceeding 20,000 litres capacity) 9 (aboveground vessels not exceeding 20,000 litres capacity or underground/ mounded vessels) Table-3 9 9 9 Fill point of LPG Storage vessel and Centre of LPG Tank- Truck unloading hard stand 9 (abovegr ound/ mounded vessels exceedin g 7500 litres capacity) 6 (abovegr ound/ mounded vessels not exceeding 7500 litres capacity) 3 (underground vessel) - 6 9 6 6 6 Liquefied Petroleum Gas Dispenser 9 ( aboveground vessels not exceeding 20,000 litres capacity or underground/mounded vessels ) 15 ( aboveground vessels exceeding 20,000 litres capacity ) 6 - 6 6 6 6 Property line T able 3 9 6 - 3 4 6
To/ From
Liquefied
Petroleu
mLPG
Storage
Vessels
Fill point of LPG
Storage
vessel and Centre
of LPG
Tank-Truck
unloading hard
stand
Liquefied petroleum gas Dispenser
Property
line
Petroleum Class A or B service Station licensed in Form XII of Petroleum Rules 1976
Fill point of petroleum
tanks
Vent pipe
Of petrolem
tanks
Petroleum
Class
A/B
dispensig
pump
Liquefied petroleum gas storage vessels
Table-3
9 (aboveground/
mounded
vessels exceeding
7500
litres capacity)
6 (aboveground/
mounded
vessels not
exceeding
7500 litres
capacity ) 3 (underground
vessel) 15 (aboveground vessels exceeding 20,000 litres capacity)
9 (aboveground
vessels not
exceeding
20,000 litres
capacity or
underground/
mounded
vessels)
Table-3
9
9
9
Fill point
of LPG
Storage
vessel and
Centre of
LPG
Tank-
Truck
unloading
hard stand
9
(abovegr
ound/
mounded
vessels
exceedin
g 7500
litres
capacity)
6
(abovegr
ound/
mounded
vessels not exceeding 7500 litres capacity) 3 (underground vessel)
-
6
9
6
6
6
Liquefied Petroleum Gas Dispenser
9 ( aboveground vessels not exceeding 20,000 litres capacity or underground/mounded vessels ) 15 ( aboveground vessels exceeding 20,000 litres capacity )
6
-
6
6
6
6
Property line
T able 3
9
6
-
3
4
6
[TABLE 6
Minimum safety distances for non-flammable non
toxic cryogenic liquids
Water capacity of vessel in litres Between Two vesse Between vessel and any building or adjoining property line or pedestrians passage Between vessel and flammable structure, naked flame, pipeline, containing flammable fluids, electric installation or places of public assembly or drain Not exceeding 10,000 Exceeding 10,000 1 metre 1 metre 3 metres 3 metres 5 metres 7.5 metres
Water capacity of
vessel in litres
Between
Two
vesse
Between vessel and
any building or
adjoining property line
or pedestrians
passage
Between vessel and
flammable structure,
naked flame, pipeline,
containing flammable
fluids, electric
installation or places
of public assembly or
drain
Not exceeding 10,000
Exceeding 10,000
1 metre
1 metre
3 metres
3 metres
5 metres
7.5 metres
TABLE 7
Minimum safety distances for liquid
carbon-dioxide
Water capacity of vessel in litres Between Two vessel Between vessel and any building or adjoining property line or pedestrians passage or places of public assembly Not exceeding 50,000 1 metre 2 metres Exceeding 50,000 2 metre 4 metres
Water capacity of
vessel in litres
Between
Two
vessel
Between vessel and
any building or
adjoining property line
or pedestrians
passage or places of
public assembly
Not exceeding 50,000
1 metre
2 metres
Exceeding 50,000
2 metre
4 metres
(a) thirty metres for corrosive, toxic or flammable gases;
(b) fifteen metres for non-corrosive, non-toxic or non-flammable gases;
Section 21 • The Static And Mobile Pressure Vessels (Unfired) Rules, 1981
21. General
the-static-and-mobile-pressure-vessels-unfired-rules-1981-sec-21.json
•
Section 21
{
"act_title": "The Static And Mobile Pressure Vessels (Unfired) Rules, 1981",
"act_slug": "the-static-and-mobile-pressure-vessels-unfired-rules-1981",
"section_label": "Section",
"section": {
"number": "21",
"title": "21. General",
"chapter": null,
"content": "(a) diameter of the vessel, in case of vessels with water capacity not exceeding forty thousand litres,\n(b) fifteen metres, if the water capacity of the vessels exceeds forty thousand litres.]\n[22. Location of pressure vessel\nTABLE 1\nMINIMUM SAFETY\nDISTANCES FOR CORROSIVE, TOXIC OR PERMANENT FLAMMABLE GASES\nSl. Nos Water capacity of vessel(in litres) Minimum distance From building or group of buildings or line of adjoining property Minimum distance between pressure vessels (1) (2) (3) (4) (i) (ii) (iii) (iv) (v) Not above 2000 Above 2000 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 5 metres 10 metres 15 metres 20 metres 30 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres\nSl.\nNos\nWater capacity of vessel(in litres)\nMinimum distance\nFrom building or group of buildings or line of\nadjoining property\nMinimum distance\nbetween pressure\nvessels\n(1)\n(2)\n(3)\n(4)\n(i)\n(ii)\n(iii)\n(iv)\n(v)\nNot above 2000\nAbove 2000 but not above 10,000\nAbove 10,000 but not above 20,000\nAbove 20,000 but not above 40,000\nAbove 40,000\n5 metres\n10 metres\n15 metres\n20 metres\n30 metres\n1 metre\n1 metre\n1.5 metres\n2 metres\n2 metres\nTABLE 2\nMinimum safety distances for non-corrosive, non-flammable or non-toxic gases\nSl. Nos Water capacity of vessel(in litres) Minimum distance from building or group of buildings or line of adjoining property Minimum distance between pressure vessels (1) (2) (3) (4) (i) (ii) (iii) (iv) (v) Not above 2000 Above 2000 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 3 metres 5 metres 7.5 metres 10 metres 15 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres\nSl.\nNos\nWater capacity of vessel(in litres)\nMinimum distance from\nbuilding or group of\nbuildings or line of\nadjoining property\nMinimum distance\nbetween pressure\nvessels\n(1)\n(2)\n(3)\n(4)\n(i)\n(ii)\n(iii)\n(iv)\n(v)\nNot above 2000\nAbove 2000 but not above 10,000\nAbove 10,000 but not above 20,000\nAbove 20,000 but not above 40,000\nAbove 40,000\n3 metres\n5 metres\n7.5 metres\n10 metres\n15 metres\n1 metre\n1 metre\n1.5 metres\n2 metres\n2 metres\nTABLE 3\nMinimum safety distances for liquefied\nflammable gases\nSl. No. Water capacity of vessel (in litres) Minimum distance from building or group of buildings or line of adjoining property Minimum distance between vessels Above ground level Underground or Aboveground vessels covered with earth(mound) Above ground level Underground or aboveground vessels covered with earth(mound) (1) (2) (3) (4) (5) (6) (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) Not above 2000 Above 2000 but not above 75,00 Above 75,00 but not above 10,000 Above 10,000 but not above 20,000 Above 20,000 but not above 40,000 Above 40,000 but not above 3,50,000 Above 3,50,000 but not above 4,50,000 Above 4,50,000 but not above 7,50,000 Above 7,50,000 but not above 38,00,000 Above 38,00,000 5 metres 10 metres 10 metres 15 metres 20 metres 30 metres 40 metres 60 metres 90 metres 120 metres 3 metres 3 metres 5 metres 7.5 metres 10 metres 15 metres 15 metres 15 metres 15 metres 15 metres 1 metre 1 metre 1.5 metres 2 metres 2 metres 2 metres or ¼ th of the sum of the sum of diameter of adjacent vessel or ½ the diameter of the two adjacent vessels, whichever is greater 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre 1 metre\nSl.\nNo.\nWater capacity of vessel\nMinimum distance from building or group of buildings or line of\nMinimum distance between\nAbove\nground\nlevel\nUnderground or Aboveground vessels covered\nwith\nAbove\nground\nlevel\nUnderground or aboveground\nvessels covered\nwith earth(mound)\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\n(i)\n(ii)\n(iii)\n(iv)\n(v)\n(vi)\n(vii)\n(viii)\n(ix)\n(x)\nNot above 2000\nAbove 2000 but not above 75,00\nAbove 75,00 but not above 10,000\nAbove 10,000 but not above 20,000\nAbove 20,000 but not above 40,000\nAbove 40,000 but not above 3,50,000\nAbove 3,50,000 but not above 4,50,000\nAbove 4,50,000 but not above 7,50,000\nAbove 7,50,000 but not above 38,00,000\nAbove 38,00,000\n5 metres\n10 metres\n10 metres\n15 metres\n20 metres\n30 metres\n40 metres\n60 metres\n90 metres\n120 metres\n3 metres\n3 metres\n5 metres\n7.5 metres\n10 metres\n15 metres\n15 metres\n15 metres\n15 metres\n15 metres\n1 metre\n1 metre\n1.5 metres\n2 metres\n2 metres\n2 metres or ¼ th\nof the sum of\nthe sum of\ndiameter of\nadjacent vessel\nor ½ the\ndiameter of the\ntwo adjacent\nvessels,\nwhichever is\ngreater\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\n1 metre\nTABLE 4\nMinimum Safety distances (in meters) between\nfacilities associated with storage of liquefied flammable gas in petroleum\nrefinery, gas processing plants, storage terminals and bottling plants.\n(A) For Total Storage not Above 100\nTonnes\n(A) For Total Storage not Above 100\nTonnes\nFrom/To Storage Vessel Property line/ buildings not associated with storage and operation Sheds for filling storage, evacuation of cylinders Tank Truck loading/ unloading gantry Tank Wagon gantry Pump/ compres sor Shed Fire Water Pump room (1) (2) (3) (4) (5) (6) (7) (8) Storage vessel Table -3 Table - 3 30 30 50 15 60 Property line/ buildings not associated with storage and operation Table -3 ----- 30 30 50 30 -- Sheds for filling storage, evacuation of cylinders 30 30 15 30 50 15 60 Tank Truck loading/ unloading gantry 30 30 30 30 50 30 60 Tank Wagon gantry 50 50 50 50 50 30 60 Pump/compressor Shed 15 30 15 30 30 --- 60 Fire Water Pump room 60 --- 60 60 60 60 ---\nFrom/To\nStorage\nVessel\nProperty line/ buildings not\nassociated\nwith storage\nand operation\nSheds for\nfilling\nstorage,\nevacuation\nof\ncylinders\nTank Truck\nloading/\nunloading\ngantry\nTank\nWagon\ngantry\nPump/\ncompres\nsor\nShed\nFire\nWater\nPump\nroom\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\n(7)\n(8)\nStorage vessel\nTable -3\nTable - 3\n30\n30\n50\n15\n60\nProperty line/\nbuildings not\nassociated with\nstorage and\noperation\nTable -3\n-----\n30\n30\n50\n30\n--\nSheds for filling\nstorage,\nevacuation of\ncylinders\n30\n30\n15\n30\n50\n15\n60\nTank Truck\nloading/\nunloading gantry\n30\n30\n30\n30\n50\n30\n60\nTank Wagon\ngantry\n50\n50\n50\n50\n50\n30\n60\nPump/compressor\nShed\n15\n30\n15\n30\n30\n---\n60\nFire Water Pump\nroom\n60\n---\n60\n60\n60\n60\n---\n(B) For Total Storage not Above 100\nTonnes\n(B) For Total Storage not Above 100\nTonnes\nFrom/To Storage Vessel Property line/ buildings not associated with storage and operation Sheds for filling storage, evacuation of cylinders Tank truck unloading/ loading gantry Fire Water Pump room (1) (2) (3) (4) (5) (6) Storage Vessel Table-3 Table 3 Table - 3 15 30 Property line/buildings not associated with storage & operation Table-3 ----- 15 15 -- Sheds for filling storage, evacuation of cylinders Table - 3 15 15 15 30 Tank truck unloading/loading gantry 15 15 15 15 30 Fire Water Pump room 30 -- 30 30 --\nFrom/To\nStorage\nVessel\nProperty line/\nbuildings not\nassociated\nwith storage\nand operation\nSheds for filling\nstorage,\nevacuation of\ncylinders\nTank truck\nunloading/\nloading gantry\nFire\nWater\nPump\nroom\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\nStorage Vessel\nTable-3\nTable 3\nTable - 3\n15\n30\nProperty line/buildings not\nassociated with storage &\noperation\nTable-3\n-----\n15\n15\n--\nSheds for filling storage,\nevacuation of cylinders\nTable - 3\n15\n15\n15\n30\nTank truck\nunloading/loading gantry\n15\n15\n15\n15\n30\nFire Water Pump room\n30\n--\n30\n30\n--\nTABLE 5\nMinimum Safety distances (in metres) between\nfacilities associated with storage and dispensing of liquefied petroleum gas in\nliquefied Petroleum gas dispensing station as automotive fuel to motor vehicles .\nTo/ From Liquefied Petroleu mLPG Storage Vessels Fill point of LPG Storage vessel and Centre of LPG Tank-Truck unloading hard stand Liquefied petroleum gas Dispenser Property line Petroleum Class A or B service Station licensed in Form XII of Petroleum Rules 1976 Fill point of petroleum tanks Vent pipe Of petrolem tanks Petroleum Class A/B dispensig pump Liquefied petroleum gas storage vessels Table-3 9 (aboveground/ mounded vessels exceeding 7500 litres capacity) 6 (aboveground/ mounded vessels not exceeding 7500 litres capacity ) 3 (underground vessel) 15 (aboveground vessels exceeding 20,000 litres capacity) 9 (aboveground vessels not exceeding 20,000 litres capacity or underground/ mounded vessels) Table-3 9 9 9 Fill point of LPG Storage vessel and Centre of LPG Tank- Truck unloading hard stand 9 (abovegr ound/ mounded vessels exceedin g 7500 litres capacity) 6 (abovegr ound/ mounded vessels not exceeding 7500 litres capacity) 3 (underground vessel) - 6 9 6 6 6 Liquefied Petroleum Gas Dispenser 9 ( aboveground vessels not exceeding 20,000 litres capacity or underground/mounded vessels ) 15 ( aboveground vessels exceeding 20,000 litres capacity ) 6 - 6 6 6 6 Property line T able 3 9 6 - 3 4 6\nTo/ From\nLiquefied\nPetroleu\nmLPG\nStorage\nVessels\nFill point of LPG\nStorage\nvessel and Centre\nof LPG\nTank-Truck\nunloading hard\nstand\nLiquefied petroleum gas Dispenser\nProperty\nline\nPetroleum Class A or B service Station licensed in Form XII of Petroleum Rules 1976\nFill point of petroleum\ntanks\nVent pipe\nOf petrolem\ntanks\nPetroleum\nClass\nA/B\ndispensig\npump\nLiquefied petroleum gas storage vessels\nTable-3\n9 (aboveground/\nmounded\nvessels exceeding\n7500\nlitres capacity)\n6 (aboveground/\nmounded\nvessels not\nexceeding\n7500 litres\ncapacity ) 3 (underground\nvessel) 15 (aboveground vessels exceeding 20,000 litres capacity)\n9 (aboveground\nvessels not\nexceeding\n20,000 litres\ncapacity or\nunderground/\nmounded\nvessels)\nTable-3\n9\n9\n9\nFill point\nof LPG\nStorage\nvessel and\nCentre of\nLPG\nTank-\nTruck\nunloading\nhard stand\n9\n(abovegr\nound/\nmounded\nvessels\nexceedin\ng 7500\nlitres\ncapacity)\n6\n(abovegr\nound/\nmounded\nvessels not exceeding 7500 litres capacity) 3 (underground vessel)\n-\n6\n9\n6\n6\n6\nLiquefied Petroleum Gas Dispenser\n9 ( aboveground vessels not exceeding 20,000 litres capacity or underground/mounded vessels ) 15 ( aboveground vessels exceeding 20,000 litres capacity )\n6\n-\n6\n6\n6\n6\nProperty line\nT able 3\n9\n6\n-\n3\n4\n6\n[TABLE 6\nMinimum safety distances for non-flammable non\ntoxic cryogenic liquids\nWater capacity of vessel in litres Between Two vesse Between vessel and any building or adjoining property line or pedestrians passage Between vessel and flammable structure, naked flame, pipeline, containing flammable fluids, electric installation or places of public assembly or drain Not exceeding 10,000 Exceeding 10,000 1 metre 1 metre 3 metres 3 metres 5 metres 7.5 metres\nWater capacity of\nvessel in litres\nBetween\nTwo\nvesse\nBetween vessel and\nany building or\nadjoining property line\nor pedestrians\npassage\nBetween vessel and\nflammable structure,\nnaked flame, pipeline,\ncontaining flammable\nfluids, electric\ninstallation or places\nof public assembly or\ndrain\nNot exceeding 10,000\nExceeding 10,000\n1 metre\n1 metre\n3 metres\n3 metres\n5 metres\n7.5 metres\nTABLE 7\nMinimum safety distances for liquid\ncarbon-dioxide\nWater capacity of vessel in litres Between Two vessel Between vessel and any building or adjoining property line or pedestrians passage or places of public assembly Not exceeding 50,000 1 metre 2 metres Exceeding 50,000 2 metre 4 metres\nWater capacity of\nvessel in litres\nBetween\nTwo\nvessel\nBetween vessel and\nany building or\nadjoining property line\nor pedestrians\npassage or places of\npublic assembly\nNot exceeding 50,000\n1 metre\n2 metres\nExceeding 50,000\n2 metre\n4 metres\n(a) thirty metres for corrosive, toxic or flammable gases;\n(b) fifteen metres for non-corrosive, non-toxic or non-flammable gases;",
"footnote": "",
"is_definition": false,
"sort_order": 20
},
"prev_section": "20",
"next_section": "23"
}