← Back to The Oil Mines Regulations, 2017

71. Gas compressor shed or house.

(a) pressure relief valves on inlet and all stages to prevent pressure build up above the predetermined set point;
(b) high discharge temperature shut down mechanism and high cooling water temperature switch fitted on cooling water return line to shut the compressor in the event of a fault;
(c) high inlet, inter stage and discharge pressures shut down mechanisms;
(d) low lube oil pressure shut down mechanism;
(e) low cooling water flow switch fitted to the cooling water return line to shut the compressor in the event of fault; and
(f) a remote isolation switch, wherever applicable, for emergency shutdown with manual reset at control panel.