    "act_title": "The Oil Mines Regulations, 2017",
    "act_slug": "the-oil-mines-regulations-2017",
    "section_label": "Section",
    "section": {
        "number": "71",
        "title": "71. Gas compressor shed or house.",
        "chapter": null,
        "content": "(a) pressure relief valves on inlet and all stages to prevent pressure build up above the predetermined set point;\n(b) high discharge temperature shut down mechanism and high cooling water temperature switch fitted on cooling water return line to shut the compressor in the event of a fault;\n(c) high inlet, inter stage and discharge pressures shut down mechanisms;\n(d) low lube oil pressure shut down mechanism;\n(e) low cooling water flow switch fitted to the cooling water return line to shut the compressor in the event of fault; and\n(f) a remote isolation switch, wherever applicable, for emergency shutdown with manual reset at control panel.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 70
    },
    "prev_section": "70",
    "next_section": "72"
}