(a) well control fluid and equipment are available and installed and used as required;
(b) well is full of well fluid of adequate specific gravity to overbalance the bottom hole pressure;
(c) during tripping operation, closely watch to notice any sign of kick in the well and annulus is kept full;
(d) full opening safety valve with connection for circulation and operating key are readily available and kept in open position on the derrick floor;
(e) blow out preventer and related equipment like choke and kill manifold, control panel and accumulator are available, maintained and tested regularly;
(f) blow out preventer equipment is function-tested and pressure-tested when installed and also at the appropriate time during operations to determine that the blow out preventer functions properly;
(g) instructions of the blow out preventer operating manual of the manufacturer are complied with;
(h) all connections, valves, fittings, piping, and other equipment have a minimum working pressure equal to the rated working pressure of the blow out preventer;
(i) bolts, nuts and fittings of correct size are used and tightened to the recommended torque; and all connections are pressure-tested before resuming operation;
(j) all manually operated valves are equipped with hand wheels, and always kept ready for use; and
(k) pit drills are carried out regularly.
Section 52 • The Oil Mines Regulations, 2017
52. Well control equipment and operation.
the-oil-mines-regulations-2017-sec-52.json
•
Section 52
{
"act_title": "The Oil Mines Regulations, 2017",
"act_slug": "the-oil-mines-regulations-2017",
"section_label": "Section",
"section": {
"number": "52",
"title": "52. Well control equipment and operation.",
"chapter": null,
"content": "(a) well control fluid and equipment are available and installed and used as required;\n(b) well is full of well fluid of adequate specific gravity to overbalance the bottom hole pressure;\n(c) during tripping operation, closely watch to notice any sign of kick in the well and annulus is kept full;\n(d) full opening safety valve with connection for circulation and operating key are readily available and kept in open position on the derrick floor;\n(e) blow out preventer and related equipment like choke and kill manifold, control panel and accumulator are available, maintained and tested regularly;\n(f) blow out preventer equipment is function-tested and pressure-tested when installed and also at the appropriate time during operations to determine that the blow out preventer functions properly;\n(g) instructions of the blow out preventer operating manual of the manufacturer are complied with;\n(h) all connections, valves, fittings, piping, and other equipment have a minimum working pressure equal to the rated working pressure of the blow out preventer;\n(i) bolts, nuts and fittings of correct size are used and tightened to the recommended torque; and all connections are pressure-tested before resuming operation;\n(j) all manually operated valves are equipped with hand wheels, and always kept ready for use; and\n(k) pit drills are carried out regularly.",
"footnote": "",
"is_definition": false,
"sort_order": 51
},
"prev_section": "51",
"next_section": "53"
}