(a) for any flat roof, open balcony, verandah roof and lean-to-roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres from the highest point, and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and
(b) for pitched roof-
(i) when the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and
(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres.
Section 79 • The Indian Electricity Rules, 1956
79. Clearances from buildings of low and medium voltage lines and service lines
the-indian-electricity-rules-1956-sec-79.json
•
Section 79
{
"act_title": "The Indian Electricity Rules, 1956",
"act_slug": "the-indian-electricity-rules-1956",
"section_label": "Section",
"section": {
"number": "79",
"title": "79. Clearances from buildings of low and medium voltage lines and service lines",
"chapter": null,
"content": "(a) for any flat roof, open balcony, verandah roof and lean-to-roof-\n(i) when the line passes above the building a vertical clearance of 2.5 metres from the highest point, and\n(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and\n(b) for pitched roof-\n(i) when the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and\n(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres.",