    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "79",
        "title": "79. Clearances from buildings of low and medium voltage lines and service lines",
        "chapter": null,
        "content": "(a) for any flat roof, open balcony, verandah roof and lean-to-roof-\n(i) when the line passes above the building a vertical clearance of 2.5 metres from the highest point, and\n(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres from the nearest point, and\n(b) for pitched roof-\n(i) when the line passes above the building a vertical clearance of 2.5 metres immediately under the lines, and\n(ii) when the line passes adjacent to the building a horizontal clearance of 1.2 metres.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 78
    },
    "prev_section": "78",
    "next_section": "80"
}