29. Clearance zone for buildings near High Tension Electrical Line.

Table 33: Clearance Zone for buildings near
High Tension Electrical Line
Table 33: Clearance Zone for buildings near
High Tension Electrical Line
Type of supply line
Type of supply line
Type of supply line Horizontal clearance (in meters)
(including both sides and from the centre line of the tower)
Type of supply line Horizontal clearance (in meters)
(including both sides and from the centre line of the tower)
High voltage lines up to 11 KV
11.5
High voltage lines above 11 KV and up to 33KV
15.0
High voltage lines above 33 KV and up to 66KV
18.0
High voltage lines above 66 KV and up to 132KV
27.0
High voltage lines above 132 KV and up to 220KV
35.0
High voltage lines above 220 KV and up to 440KV
52.0