    "act_title": "Punjab Urban Planning and Development Building Rules, 2018",
    "act_slug": "punjab-urban-planning-and-development-building-rules-2018",
    "section_label": "Section",
    "section": {
        "number": "29",
        "title": "29. Clearance zone for buildings near High Tension Electrical Line.",
        "chapter": null,
        "content": "Table 33: Clearance Zone for buildings near\n\t\t\t\tHigh Tension Electrical Line\nTable 33: Clearance Zone for buildings near\n\t\t\t\tHigh Tension Electrical Line\nType of supply line\nType of supply line\nType of supply line Horizontal clearance (in meters)\n\t\t\t\t(including both sides and from the centre line of the tower)\nType of supply line Horizontal clearance (in meters)\n\t\t\t\t(including both sides and from the centre line of the tower)\nHigh voltage lines up to 11 KV\n11.5\nHigh voltage lines above 11 KV and up to 33KV\n15.0\nHigh voltage lines above 33 KV and up to 66KV\n18.0\nHigh voltage lines above 66 KV and up to 132KV\n27.0\nHigh voltage lines above 132 KV and up to 220KV\n35.0\nHigh voltage lines above 220 KV and up to 440KV\n52.0",
        "footnote": "",
        "is_definition": false,
        "sort_order": 24
    },
    "prev_section": "28",
    "next_section": "30"
}