12. Galleys, Provision rooms, cold storage, refrigerating equipment.

(b) The galley shall be situated as near as may be to the mess rooms provided for the seafarer and any necessary equipment shall be provided to enable food to be served in the mess rooms under all weather conditions.
(c) There shall be no direct opening between the galley and any sleeping room.
(d) Every galley shall be provided with exhaust fans which will draw off fumes from the cooking appliances therein and discharge the fumes into the open air.
(e) The floor of the galley shall be provided with gutters and with scuppers which shall be led overboard or to an enclosed tank served by mechanically operated suction pump. The position and number of the gutter and scuppers shall be such as will ensure the efficient drainage of the floor.
(f) The cooking appliances in the galley shall be arranged in a manner which shall facilitate the cleaning of the galley.
(g) All cupboards and dressers in the galley shall be made of material which is impervious to dirt and moisture and can easily be kept clean. All metal parts of the cupboards and dressers shall be rustproof. The bottoms of all cupboards and dressers in the galley shall either be flush with the deck or shall be so fitted as to enable the deck space beneath them to be readily accessible for cleaning.
(h) Every galley shall be provided with such equipment as will enable food in sufficient quantity to be properly and readily prepared for the persons whom the galley is intended to serve, and the cooking utensils to be hygienically cleaned.
(i) Every galley shall be provided with one or more cooking appliances with an oven or cooking range of adequate capacity.
(b) Every dry provision store room shall be enclosed by bulkheads constructed of steel or other suitable material.
(c) Access to every dry provision store room shall be obtained from a passageway, galley, pantry or another store room, or from a position on an open deck with, in so far as is reasonable and practicable in the circumstances, shall be a protected position.
(d) Every dry provision store room shall be so situated, constructed and ventilated as to avoid deterioration of the stores through heat, draught, condensation or infestation by insects or vermin.
(b) Access to every cold store room shall be obtained from a passageway, galley or pantry or from another store room.
Second Schedule
[ See rule 2(1) (k)]
Trunked Mechanical Ventilation System
Category
Space
Fresh air changes per hour
Volume of fresh air for each person likely to use
the room at any one time (m 3 /min)
(1)
(2)
(3)
(4)
A
Spaces other than those in category
(C) in deck houses above the upper or shelter deck :-
(1) outside rooms (other than rooms
adjoining machinery casing)
(2) inside rooms and rooms adjoining machinery casing
10
15
1.42
1.42
B
Spaces other than those in category
(C) in side-to-side superstructures above the upper or shelter
deck:
(1) outside rooms (other than rooms
adjoining machinery casing
(2) inside rooms and rooms adjoining machinery casing
12
15
1.42
1.42
C
Mess rooms, smoking rooms and
recreation rooms (in each case above the upper or shelter decks):
(1) not adjoining machinery casing
(2) adjoining machinery casing
15
18
0.71*
0.71*
D
Passageways adjoining machinery casings
4
E
Rooms in between decks (including
shelter between decks) of ships propelled by internal combustion
machinery
(1) Rooms clear of machinery casing
(2) Rooms abreast of but not
adjoining machinery casing
(3) Rooms adjoining machinery casing (other than mess rooms,
smoking rooms and recreation rooms)
12
12
15
1.42
1.42
1.7
(4) Mess rooms, smoking rooms, and recreation rooms (in each
case adjoining machinery casing)
18
0.71
F
Rooms in tween decks
(including shelter tween decks) of steamships :-
(1) Rooms clear of machinery casing
(2) Rooms abreast of, but not
adjoining machinery casing.
(3) Rooms immediately above
machinery casing or abreast of and adjoining machinery casing
(other than mess rooms, smoking rooms and recreation rooms)
(4) Mess room, smoking rooms and recreation rooms (in each
case adjoining machinery casing)
12
15
18
20
1.42
1.7
1.7
0.85**
Table II
Category
Space
Fresh air change per hour
Supply
Exhaust
(1)
(2)
(3)
(4)
G
Galleys
20 (a)(b)
40(b)
H
Sanitary accommodation, drying rooms and pantries
10
20
J
Wards in permanent hospitals
12 or such greater number as would result in the
supply of not less than 1.42 cubic metres of fresh air per minute
for each bed in the room.
--
K
Dry provision store rooms
Not less than 10 and not more than 20
--
(a) if at least two sides of the galley are exposed to the weather.
(b) The Central Government may exempt any ship from these requirements to the extent that it is satisfied that compliance therewith is unnecessary by reason of the insulation of the equipment in the galley, or by reason of the size of the galley.
Third Schedule
[ See Schedule 1, Para 1(11)(a)]
Certified for (*) seafarer(s)
Certified for [Chief Officer]/[Master]/[Chief Engineer]/[**]
Certified for (*) officers.
Certified for (*) [ratings]/[petty officer].
Fourth Schedule
[ See Schedule 1,para3(3)]
Electric Lighting
(A) Sleeping Room and Day Room:
(1)
At general measurement points
50 lux
(2)
At every Mirror
200 lux
(3)
At every seat at a writing deck or table
150 lux
(4)
At not less than half the seats (other than those mentioned in
(3) above) in a sleeping room provided for use of more than one
person
150 lux
(B) Mess Room
(1)
At general measurement points
100 lux
(2)
At every table and sink
150 lux
(C) Recreational Rooms (including for watching films and
television hobbies, and games room):
(1)
At general measurement points
50 lux
(2)
At every recreational table
100 lux
(3)
At every seat at a writing deck or table
150 lux
(4)
At not less than half the seats (other than those mentioned in
(3) above)
150 lux
(D) Hospital
(1)
At general measurement points
50 lux
(2)
At any wash room
200 lux
(3)
At least one fixed lamp shall be installed in addition to the
electric reading lamp required by subpara (2) of para 3 to be
provided at the head of each bed.
150 lux
(E) Offices and Studies
(1)
At general measurement points
100 lux
(2)
At every seat at writing desk or table
200 lux
(F) Sanitary Accommodation (including sanitary accommodation
in hospital):
(1)
At general measurement points
50 lux
(2)
At every Mirror
200 lux
(G) Laundries
(1)
At general measurement points
100 lux
(H) Drying Room:
(1)
At the center of spaces
50 lux
(I) Galley (including bakeries and pantries):
(1)
At working positions
The light shall be so disposed as to ensure that shelves and
cupboards receive the maximum amount of light
300 lux
(J) Dry Provision Store Room and Cold Store Room:
(1)
At general measurement points
The light shall be so disposed as to ensure that shelves and
cupboards receive the maximum amount of light
100 lux
(K) Passage ways companionways and covered deck recreation
spaces:
(1)
At general measurement points
50 lux
A light shall be placed -
(a) at the
head of each stairway, ladder and hatchway, and
(b) at or
near the lockers provided for oilskins or working clothes.
Fifth Schedule
Certificate of Seafarer Accommodation
[See rule 6]
Certificate of Seafarer Accommodation
Certificate No.
Issued under the provisions of the
Merchant Shipping (Seafarer Accommodation) Rules, 2016.
Under the authority of the Government of India
Name of Ship
Distinctive Number or Call Sign
IMO Number
Port of Registry
Gross Tonnage
Date of Keel Laid*
Type of Ship
:
.................................
Area of Operation
:
Unlimited / Restricted (see Remarks)
Master
:
persons
Officer
:
persons
Petty Officers
:
persons
Ratings
:
persons
Total
:
persons