107. Fixed electric wiring

(i) approved armoured cable with correctly designed terminations, complete with armour clamps, the armouring being carried and electrical clamps to provide mechanical support to the cable and electrical continuity; or
(ii) approved metal sheathed cable with correctly designed and installed terminations; or
(iii) single or multicored insulated cables accommodated in solid drawn heavy gauge screwed galvanised conduits used in conjunction with approved flame-proof fittings, the conduit being sealed at both ends and installed in such a manner as to permit internal condensation to drain to a point or points from which it may be removed; where a conduit runs from a zone "1" area to zone "2" area or an area which is not hazardous area, an adequate seal shall be provided outside the boundary of zone "1" area;
(iv) single or multicored mineral insulated cable of approved type in conjunction with approved flame-proof type glands at all joints and terminations;
(v) bare conductors contained in an approved flame-proof or forming part of an intrinsically safe circuit.
(i) separately protected by a fuse or circuit breaker set to operate when the current in the circuit so exceeds the rated current for such a period of time as to involve danger; and
(ii) provided with an individual isolating switch at the main supply point for each electric pump including its integral lighting system, if any.