    "act_title": "The Petroleum Rules, 2002",
    "act_slug": "the-petroleum-rules-2002",
    "section_label": "Section",
    "section": {
        "number": "107",
        "title": "107. Fixed electric wiring",
        "chapter": null,
        "content": "(i) approved armoured cable with correctly designed terminations, complete with armour clamps, the armouring being carried and electrical clamps to provide mechanical support to the cable and electrical continuity; or\n(ii) approved metal sheathed cable with correctly designed and installed terminations; or\n(iii) single or multicored insulated cables accommodated in solid drawn heavy gauge screwed galvanised conduits used in conjunction with approved flame-proof fittings, the conduit being sealed at both ends and installed in such a manner as to permit internal condensation to drain to a point or points from which it may be removed; where a conduit runs from a zone \"1\" area to zone \"2\" area or an area which is not hazardous area, an adequate seal shall be provided outside the boundary of zone \"1\" area;\n(iv) single or multicored mineral insulated cable of approved type in conjunction with approved flame-proof type glands at all joints and terminations;\n(v) bare conductors contained in an approved flame-proof or forming part of an intrinsically safe circuit.\n(i) separately protected by a fuse or circuit breaker set to operate when the current in the circuit so exceeds the rated current for such a period of time as to involve danger; and\n(ii) provided with an individual isolating switch at the main supply point for each electric pump including its integral lighting system, if any.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 109
    },
    "prev_section": "106",
    "next_section": "108"
}