(1) General.
(a) every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency;
(b) in every building exits shall comply with the minimum requirements of this part except those not accessible for general public use;
(c) all exits shall be free of obstruction;
(d) no building shall be altered so as to reduce the number, width or protection of exits to less than that required;
(e) exits shall be clearly visible and the routes to reach the exit shall be clearly marked and sign posted to guide the population of floor concerned;
(f) all exit ways shall be properly illuminated;
(g) fire fighting equipment, where provided along exits, shall be suitably located and clearly marked but must not obstruct the exit way and yet there should be clear indication about its location from either side of the exit way;
(h) alarm devices shall be installed to ensure prompt evacuation of persons inside through the exits;
(i) all exits shall provide continuous means of access to the exterior of a building or to an exterior open space leading to a street; and
(j) exits shall be so arranged that they may be reached without passing through another occupied unit, except in the case of residential buildings.
(2) Types of Exits.
(b) Lifts and escalators shall not be considered as exits.
(3) Number and size of Exits.
(i) Arrangement of Exit. - Exits shall be so located that the travel distance on the floor shall not exceed 22.5 metres for residential, educational, institutional and hazardous occupancies and 30 metres for assembly, business, mercantile, industrial and storage occupancies. Whenever more than one exit is required for a floor of a building, exits shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels.
(i) Arrangement of Exit.
(ii) Occupant Load. - The population in rooms, areas of floors shall be calculated based on the occupant load given in Table 9 :
(ii) Occupant Load.
Table 9
Table 9
Occupant Load
Occupant Load
[Rule 82]
S. No.
S. No.
Group of Occupancy
Group of Occupancy
Occupant load Gross Area* in square metres
per person
Occupant load Gross Area* in square metres
per person
1.
Residential
12.5
2.
Educational
4
3.
Institutional
15#
4.
Assembly-
(a) with fixed or loose seats and dance floor
0.6$
(b) without seating facilities including dining rooms
1.5$
5.
Mercantile-
(a) street floor and sales basement
3
(b) upper sale floors
6
6.
Business and Industrial
10
7.
Storage
30
8.
Hazardous
10
* The gross area shall mean plinth area or covered area.
# Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums and the like, where sleeping accommodation is provided, shall be calculated at not less than 7.5 square metres gross area/person.
$ The gross area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below, where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly place. No deductions shall be made in the gross area for corridors, closets or other sub-divisions, and area shall include all space serving the particular assembly occupancy.
(iii) Capacity of Exits. - The capacity of exits (doors and stairways) indicating the number of persons that could be safely evacuated through a unit exit width of 50 centimetres shall be as given in Table 10 :
(iii) Capacity of Exits.
Table 10
Table 10
[Rule 82 (3)(iii)]
S. No.
S. No.
Group of occupancy
Group of occupancy
Number of occupants
Number of occupants
Stairways
Stairways
Doors
Doors
1.
Residential
25
75
2.
Educational
25
75
3.
Institutional
25
75
4.
Assembly
60
90
5.
Business
50
75
6.
Mercantile
50
75
7.
Industrial
50
75
8.
Storage
50
75
9.
Hazardous
25
40
(iv) Number of staircases. - For all other buildings excepting single and multi-family dwellings below 15 metres in height, there shall be a minimum of two stairways and one of them shall be an enclosed stairway and the other shall be on the external wall of building and shall open directly to the exterior, interior open space or to any open place of safety.
(iv) Number of staircases.
(v) Minimum width for stairways. - Notwithstanding the detailed provision for exits as per clause (i) to (iii) above the provisions of sub-rule (2) of Rule 77 will govern the width of stairways.
(v) Minimum width for stairways.
(4) Other requirements of individual exits.
(I) Doorways
(a) Every exit doorway shall open into an enclosed stairway, a horizontal exit, or a corridor or passage way providing continuous and protected means of egress.
(b) No exit doorway shall be less than 100 centimetres in width. Doorway, shall be not less than 200 centimetres in height. Doorways for bathrooms, water closet or stores shall not be less than 75 centimetres.
(c) Exit doorways shall, as far as possible, open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 90 centimetres over head or sliding doors shall not be installed.
(d) Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway level of landing shall be the same as that of the floor which it serves.
(e) Exit doorways shall be openable from the side which they serve without the use of a key.
(II) Revolving Doors
(a) Revolving doors shall not be used as required exits except in residential, business and mercantile occupancies, but shall not constitute more than half the total required door width.
(b) When revolving doors are considered as required exit way the following assumptions shall be made
(i) each revolving door shall be credited one half a unit exit width;
(ii) revolving doors shall not be located at the foot of a stairway. Any stairway served by a revolving door shall discharge through a lobby or foyer.
(III) Stairways.
(a) interior stairs shall not be constructed of ordinarily combustible materials throughout.
(b) interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall. Wherever a building is not identified by clause (ii) of sub-rule (6) of Rule 17 exceeds 10.5 metres in height and is served by a staircase the same shall be of enclosed type.
(c) A staircase shall not be arranged round a lift shaft unless the latter if entirely enclosed by a material of fire resistance rating as that for type of construction itself. For buildings more than 15 metres in height, the staircase location shall be to the satisfaction of the competent fire Authority as approved by the Government.
(d) The minimum width of treads shall be governed by sub-rule (4) of Rule 77. The treads shall be constructed and maintained in a manner to prevent slipping.
(e) The maximum height of riser shall be governed by sub-rule (5) of Rule 77.
(f) Handrails shall be provided with a minimum height of 90 centimetres from the centre of the tread.
(g) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be governed by sub-rule (6) of Rule 77.
(h) No living space, store or other fire risk shall open directly into the staircase.
(i) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a drought lobby.
(j) In the case of assembly, institutional residential hotels and business buildings the exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5 metre from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exits way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further all landings of floor shall have floor indication boards indicating the number of floor as defined in Rule 2 (28). The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 X 0.5 metre.
(k) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. Wherever the building is served by more than one staircase one of the staircase may lead to basement level provided the same is separated at ground level by either a ventilated lobby with the discharge points at two different ends or through enclosure.
(IV) Fire Escape or External Stair
(a) Fire escapes shall not be taken into account in calculating the evacuation time of a building.
(b) All fire escape shall be directly connected to the ground.
(c) Entrance to fire escape shall be separate and remote from the internal staircase.
(d) The route to fire escape shall be free from obstructions at all times, except a doorway leading to the fire escape which shall have the required fire resistance.
(e) Fire escape shall be constructed of non-combustible materials.
(f) Fire escape stairs shall have straight flight not less than 75 centimetres wide with 15 centimetres treads and risers not higher than 19 centimetres. The number of risers shall be limited to 16 per flight.
(g) Handrails shall be of a height not less than 90 centimetres.
(V) Spiral Stairs (fire escape).
(a) The use of spiral staircase shall be limited to low occupant load and to a building of height of 9 metres unless they are connected to platforms, such as balconies and terraces to allow escapes to pause.
(b) A spiral fire escape shall be not less than 150 centimetres in diameter and shall be designed to give adequate headroom.
(VI) Roof Exit.
(VII) Ramps.
(a) Ramps with a slope of not more than 1 in 40 may be permitted for and shall comply with all the applicable requirements of required stairways as to enclosure, capacity and limiting dimensions, Ramps shall be surfaced with approved non-slipping material.
(b) The minimum width of the ramps in hospitals shall be 2.25 metres.
(c) Handrails shall be provided on both side of the ramp.
(d) Ramps shall lead directly to outside open space at ground level of courtyards or safe place.
(VIII) Corridors.
(a) The minimum width of a corridor shall be 1.0 metre.
(b) For building more than 15 metres in height the interconnecting corridor between staircases shall be provided with at least one smoke stop door across the corridor or enclosed space between the doors in the enclosing walls of any two staircases.
(IX) Refuge areas.
(a) For all buildings exceeding 15 metres in height excepting multi-family building, one refuge area on the floor immediately above 18 metres shall be provided.
(b) Refuge area shall be provided on the external walls as cantilever projections or in any other manner (which will not be covered in floor area ratio) with a minimum area of 15 square metres and to be calculated based on the population on each floor at the rate of 1 square metres per person.
(X) Fire and Structural Safety and Services
[82A. Facilities for physically handicapped persons in all Public buildings/Public residence.
(1) Access Path/Walk way.
(2) Parking.
(a) Surface parking for two car spaces shall be provided near entrance for the physically handicapped persons with maximum travels distance of 30.0 meter from building entrance;
(b) The width of parking bay shall be minimum 3.6 meter ;
(c) The information stating that the space is reserved for wheel chair users shall be conspicuously displayed;
(d) Guiding floor material shall be provided or a device which guides visually impaired persons with audible signals or other devices which serves the same purpose shall be provided.
(3) Building requirements.
(a) Approach to plinth level;
(b) Corridor connecting the entrance/exit for the handicapped;
(c) Stair-ways;
(d) Lift;
(e) Toilet;
(f) Drinking water
(4) Approach to plinth level.
(5) Ramped Approach.
(6) Stepped Approach.
(7) Exit/Entrance Door.
(8) Entrance Landing.
(9) Corridor connecting the entrance/exit for the handicapped.
(a) Guiding floor materials shall be provided or devices that emit sound to guide visually impaired persons;
(b) The minimum width shall be 1500 mm ;
(c) In case there is a difference of level slope ways shall be provided with slope of 1 : 2;
(d) Handrails shall be provided for ramps/slope ways.
(10) Stair ways.
(a) The minimum width shall be 1350 mm;
(b) Height of the riser shall not be more .than 150 mm. and width of the tread 300 mm. The steps shall not have abrupt (square) nosing;
(c) Maximum number of risers on a height shall be limited to 12;
(d) Handrails shall be provided on both sides and shall extend 300 mm. on the top and bottom of each flight of steps.
(11) Lifts.
Clear internal depth
:
1100 mm.
Clear internal width
:
2000 mm.
Entrance door width
:
900 mm.
(a) A handrail not less than 600 mm. long at 1000 mm. above floor level shall be fixed adjacent to the control panel.
(b) The lift lobby shall be of an inside measurement of 1800 mm. x 1800 mm. or more;
(c) The time of an automatically closing door should be minimum 5 seconds and the closing speed should not exceed 0.25 Meter per Second;
(d) The interior of the cage shall be provided with a device that audibly indicate the floor the cage has reached and indicates that the door of the cage for entrance/exit is either open or closed.
(12) Toilets.
(a) The minimum size shall be 1500 mm x 1750 mm;
(b) Minimum clear opening of the door shall be 900 mm. and the door shall swing out;
(c) Suitable arrangement of vertical/horizontal Handrails with 50 mm. clearance from wall shall be made in the toilet;
(d) The W. C. seat shall be 500 mm. from the door.
(13) Drinking Water.
(14) Designing for Children.
[83. Fire protection Requirements.
(b) No high rise building shall be approved unless cleared, in writing by the Fire Authority.
(c) Every building shall be designed and constructed to ensure fire safety and this shall be done in accordance with Para IV.
[84. Structural Design.
For R.C.C. Construction & Pucca-brick construction
(i) IS : 1893 - 1986
(ii) IS : 13920 - 1993 (to be read with IS : 456, IS : 1893)
(iii) IS : 4326 - 1993 (to be read with IS : 1893)
For low-strength masonary or clay mud and blocks
(iv) IS : 13827 - 1993
(v) IS : 13828 - 1993
For Repair & Strengthening
(vi) IS : 13935 - 1993]
Section 82 • The M.P. Bhumi Vikas Rules, 1984
82. Exit Requirements.
the-m-p-bhumi-vikas-rules-1984-sec-82.json
•
Section 82
{
"act_title": "The M.P. Bhumi Vikas Rules, 1984",
"act_slug": "the-m-p-bhumi-vikas-rules-1984",
"section_label": "Section",
"section": {
"number": "82",
"title": "82. Exit Requirements.",
"chapter": null,
"content": "(1) General.\n(a) every building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants in case of fire or other emergency;\n(b) in every building exits shall comply with the minimum requirements of this part except those not accessible for general public use;\n(c) all exits shall be free of obstruction;\n(d) no building shall be altered so as to reduce the number, width or protection of exits to less than that required;\n(e) exits shall be clearly visible and the routes to reach the exit shall be clearly marked and sign posted to guide the population of floor concerned;\n(f) all exit ways shall be properly illuminated;\n(g) fire fighting equipment, where provided along exits, shall be suitably located and clearly marked but must not obstruct the exit way and yet there should be clear indication about its location from either side of the exit way;\n(h) alarm devices shall be installed to ensure prompt evacuation of persons inside through the exits;\n(i) all exits shall provide continuous means of access to the exterior of a building or to an exterior open space leading to a street; and\n(j) exits shall be so arranged that they may be reached without passing through another occupied unit, except in the case of residential buildings.\n(2) Types of Exits.\n(b) Lifts and escalators shall not be considered as exits.\n(3) Number and size of Exits.\n(i) Arrangement of Exit. - Exits shall be so located that the travel distance on the floor shall not exceed 22.5 metres for residential, educational, institutional and hazardous occupancies and 30 metres for assembly, business, mercantile, industrial and storage occupancies. Whenever more than one exit is required for a floor of a building, exits shall be placed as remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels.\n(i) Arrangement of Exit.\n(ii) Occupant Load. - The population in rooms, areas of floors shall be calculated based on the occupant load given in Table 9 :\n(ii) Occupant Load.\nTable 9\nTable 9\nOccupant Load\nOccupant Load\n[Rule 82]\nS. No.\nS. No.\nGroup of Occupancy\nGroup of Occupancy\nOccupant load Gross Area* in square metres\n\t\t\t\t\tper person\nOccupant load Gross Area* in square metres\n\t\t\t\t\tper person\n1.\nResidential\n12.5\n2.\nEducational\n4\n3.\nInstitutional\n15#\n4.\nAssembly-\n(a) with fixed or loose seats and dance floor\n0.6$\n(b) without seating facilities including dining rooms\n1.5$\n5.\nMercantile-\n(a) street floor and sales basement\n3\n(b) upper sale floors\n6\n6.\nBusiness and Industrial\n10\n7.\nStorage\n30\n8.\nHazardous\n10\n* The gross area shall mean plinth area or covered area.\n# Occupant load in dormitory portions of homes for the aged, orphanages, insane asylums and the like, where sleeping accommodation is provided, shall be calculated at not less than 7.5 square metres gross area/person.\n$ The gross area shall include, in addition to the main assembly room or space, any occupied connecting room or space in the same storey or in the storeys above or below, where entrance is common to such rooms and spaces and they are available for use by the occupants of the assembly place. No deductions shall be made in the gross area for corridors, closets or other sub-divisions, and area shall include all space serving the particular assembly occupancy.\n(iii) Capacity of Exits. - The capacity of exits (doors and stairways) indicating the number of persons that could be safely evacuated through a unit exit width of 50 centimetres shall be as given in Table 10 :\n(iii) Capacity of Exits.\nTable 10\nTable 10\n[Rule 82 (3)(iii)]\nS. No.\nS. No.\nGroup of occupancy\nGroup of occupancy\nNumber of occupants\nNumber of occupants\nStairways\nStairways\nDoors\nDoors\n1.\nResidential\n25\n75\n2.\nEducational\n25\n75\n3.\nInstitutional\n25\n75\n4.\nAssembly\n60\n90\n5.\nBusiness\n50\n75\n6.\nMercantile\n50\n75\n7.\nIndustrial\n50\n75\n8.\nStorage\n50\n75\n9.\nHazardous\n25\n40\n(iv) Number of staircases. - For all other buildings excepting single and multi-family dwellings below 15 metres in height, there shall be a minimum of two stairways and one of them shall be an enclosed stairway and the other shall be on the external wall of building and shall open directly to the exterior, interior open space or to any open place of safety.\n(iv) Number of staircases.\n(v) Minimum width for stairways. - Notwithstanding the detailed provision for exits as per clause (i) to (iii) above the provisions of sub-rule (2) of Rule 77 will govern the width of stairways.\n(v) Minimum width for stairways.\n(4) Other requirements of individual exits.\n(I) Doorways\n(a) Every exit doorway shall open into an enclosed stairway, a horizontal exit, or a corridor or passage way providing continuous and protected means of egress.\n(b) No exit doorway shall be less than 100 centimetres in width. Doorway, shall be not less than 200 centimetres in height. Doorways for bathrooms, water closet or stores shall not be less than 75 centimetres.\n(c) Exit doorways shall, as far as possible, open outwards, that is, away from the room but shall not obstruct the travel along any exit. No door, when opened, shall reduce the required width of stairway or landing to less than 90 centimetres over head or sliding doors shall not be installed.\n(d) Exit door shall not open immediately upon a flight of stairs; a landing equal to at least the width of the door shall be provided in the stairway at each doorway level of landing shall be the same as that of the floor which it serves.\n(e) Exit doorways shall be openable from the side which they serve without the use of a key.\n(II) Revolving Doors\n(a) Revolving doors shall not be used as required exits except in residential, business and mercantile occupancies, but shall not constitute more than half the total required door width.\n(b) When revolving doors are considered as required exit way the following assumptions shall be made\n(i) each revolving door shall be credited one half a unit exit width;\n(ii) revolving doors shall not be located at the foot of a stairway. Any stairway served by a revolving door shall discharge through a lobby or foyer.\n(III) Stairways.\n(a) interior stairs shall not be constructed of ordinarily combustible materials throughout.\n(b) interior staircase shall be constructed as a self-contained unit with at least one side adjacent to an external wall. Wherever a building is not identified by clause (ii) of sub-rule (6) of Rule 17 exceeds 10.5 metres in height and is served by a staircase the same shall be of enclosed type.\n(c) A staircase shall not be arranged round a lift shaft unless the latter if entirely enclosed by a material of fire resistance rating as that for type of construction itself. For buildings more than 15 metres in height, the staircase location shall be to the satisfaction of the competent fire Authority as approved by the Government.\n(d) The minimum width of treads shall be governed by sub-rule (4) of Rule 77. The treads shall be constructed and maintained in a manner to prevent slipping.\n(e) The maximum height of riser shall be governed by sub-rule (5) of Rule 77.\n(f) Handrails shall be provided with a minimum height of 90 centimetres from the centre of the tread.\n(g) The minimum headroom in a passage under the landing of a staircase and under the staircase shall be governed by sub-rule (6) of Rule 77.\n(h) No living space, store or other fire risk shall open directly into the staircase.\n(i) External exit door of staircase enclosure at ground level shall open directly to the open spaces or can be reached without passing through any door other than a door provided to form a drought lobby.\n(j) In the case of assembly, institutional residential hotels and business buildings the exit sign with arrow indicating the way to the escape route shall be provided at a height of 0.5 metre from the floor level on the wall and shall be illuminated by electric light connected to corridor circuits. All exits way marking signs should be flush with the wall and so designed that no mechanical damage shall occur to them due to moving of furniture or other heavy equipments. Further all landings of floor shall have floor indication boards indicating the number of floor as defined in Rule 2 (28). The floor indication board shall be placed on the wall immediately facing the flight of stairs and nearest to the landing. It shall be of size not less than 0.5 X 0.5 metre.\n(k) In case of single staircase it shall terminate at the ground floor level and the access to the basement shall be by a separate staircase. Wherever the building is served by more than one staircase one of the staircase may lead to basement level provided the same is separated at ground level by either a ventilated lobby with the discharge points at two different ends or through enclosure.\n(IV) Fire Escape or External Stair\n(a) Fire escapes shall not be taken into account in calculating the evacuation time of a building.\n(b) All fire escape shall be directly connected to the ground.\n(c) Entrance to fire escape shall be separate and remote from the internal staircase.\n(d) The route to fire escape shall be free from obstructions at all times, except a doorway leading to the fire escape which shall have the required fire resistance.\n(e) Fire escape shall be constructed of non-combustible materials.\n(f) Fire escape stairs shall have straight flight not less than 75 centimetres wide with 15 centimetres treads and risers not higher than 19 centimetres. The number of risers shall be limited to 16 per flight.\n(g) Handrails shall be of a height not less than 90 centimetres.\n(V) Spiral Stairs (fire escape).\n(a) The use of spiral staircase shall be limited to low occupant load and to a building of height of 9 metres unless they are connected to platforms, such as balconies and terraces to allow escapes to pause.\n(b) A spiral fire escape shall be not less than 150 centimetres in diameter and shall be designed to give adequate headroom.\n(VI) Roof Exit.\n(VII) Ramps.\n(a) Ramps with a slope of not more than 1 in 40 may be permitted for and shall comply with all the applicable requirements of required stairways as to enclosure, capacity and limiting dimensions, Ramps shall be surfaced with approved non-slipping material.\n(b) The minimum width of the ramps in hospitals shall be 2.25 metres.\n(c) Handrails shall be provided on both side of the ramp.\n(d) Ramps shall lead directly to outside open space at ground level of courtyards or safe place.\n(VIII) Corridors.\n(a) The minimum width of a corridor shall be 1.0 metre.\n(b) For building more than 15 metres in height the interconnecting corridor between staircases shall be provided with at least one smoke stop door across the corridor or enclosed space between the doors in the enclosing walls of any two staircases.\n(IX) Refuge areas.\n(a) For all buildings exceeding 15 metres in height excepting multi-family building, one refuge area on the floor immediately above 18 metres shall be provided.\n(b) Refuge area shall be provided on the external walls as cantilever projections or in any other manner (which will not be covered in floor area ratio) with a minimum area of 15 square metres and to be calculated based on the population on each floor at the rate of 1 square metres per person.\n(X) Fire and Structural Safety and Services\n[82A. Facilities for physically handicapped persons in all Public buildings/Public residence.\n(1) Access Path/Walk way.\n(2) Parking.\n(a) Surface parking for two car spaces shall be provided near entrance for the physically handicapped persons with maximum travels distance of 30.0 meter from building entrance;\n(b) The width of parking bay shall be minimum 3.6 meter ;\n(c) The information stating that the space is reserved for wheel chair users shall be conspicuously displayed;\n(d) Guiding floor material shall be provided or a device which guides visually impaired persons with audible signals or other devices which serves the same purpose shall be provided.\n(3) Building requirements.\n(a) Approach to plinth level;\n(b) Corridor connecting the entrance/exit for the handicapped;\n(c) Stair-ways;\n(d) Lift;\n(e) Toilet;\n(f) Drinking water\n(4) Approach to plinth level.\n(5) Ramped Approach.\n(6) Stepped Approach.\n(7) Exit/Entrance Door.\n(8) Entrance Landing.\n(9) Corridor connecting the entrance/exit for the handicapped.\n(a) Guiding floor materials shall be provided or devices that emit sound to guide visually impaired persons;\n(b) The minimum width shall be 1500 mm ;\n(c) In case there is a difference of level slope ways shall be provided with slope of 1 : 2;\n(d) Handrails shall be provided for ramps/slope ways.\n(10) Stair ways.\n(a) The minimum width shall be 1350 mm;\n(b) Height of the riser shall not be more .than 150 mm. and width of the tread 300 mm. The steps shall not have abrupt (square) nosing;\n(c) Maximum number of risers on a height shall be limited to 12;\n(d) Handrails shall be provided on both sides and shall extend 300 mm. on the top and bottom of each flight of steps.\n(11) Lifts.\nClear internal depth\n:\n1100 mm.\nClear internal width\n:\n2000 mm.\nEntrance door width\n:\n900 mm.\n(a) A handrail not less than 600 mm. long at 1000 mm. above floor level shall be fixed adjacent to the control panel.\n(b) The lift lobby shall be of an inside measurement of 1800 mm. x 1800 mm. or more;\n(c) The time of an automatically closing door should be minimum 5 seconds and the closing speed should not exceed 0.25 Meter per Second;\n(d) The interior of the cage shall be provided with a device that audibly indicate the floor the cage has reached and indicates that the door of the cage for entrance/exit is either open or closed.\n(12) Toilets.\n(a) The minimum size shall be 1500 mm x 1750 mm;\n(b) Minimum clear opening of the door shall be 900 mm. and the door shall swing out;\n(c) Suitable arrangement of vertical/horizontal Handrails with 50 mm. clearance from wall shall be made in the toilet;\n(d) The W. C. seat shall be 500 mm. from the door.\n(13) Drinking Water.\n(14) Designing for Children.\n[83. Fire protection Requirements.\n(b) No high rise building shall be approved unless cleared, in writing by the Fire Authority.\n(c) Every building shall be designed and constructed to ensure fire safety and this shall be done in accordance with Para IV.\n[84. Structural Design.\nFor R.C.C. Construction & Pucca-brick construction\n(i) IS : 1893 - 1986\n(ii) IS : 13920 - 1993 (to be read with IS : 456, IS : 1893)\n(iii) IS : 4326 - 1993 (to be read with IS : 1893)\nFor low-strength masonary or clay mud and blocks\n(iv) IS : 13827 - 1993\n(v) IS : 13828 - 1993\nFor Repair & Strengthening\n(vi) IS : 13935 - 1993]",
"footnote": "",
"is_definition": false,
"sort_order": 78
},
"prev_section": "79",
"next_section": "85"
}