(1) Front open space.
Front open space Min.
Front open space Min.
Width of street facing the plot
Width of street facing the plot
(i)
1.5 metres
upto 7.5 metres.
(ii)
3.0 metres
7.5 to 18 metres*
(iii)
4.5 metres
18 to 30 metres.
(iv)
6.0 metres
above 30 metres.
*For building up to a maximum height of 7 metres.
Note. - In case the two or more sides of the building front a street, the values apply to the average width subject to a minimum of 1.8 metres for cases (ii) (iii) and (iv).
Note.
(b) For streets less than 7.5 metres in width the distances of the building (building line) shall be at 5 metres from the centre line of the street.
Note. - This limiting distance has to be determined by the Authority for the individual road/street width taking into account the traffic flow.
Note.
(2) Rear Open Space.
(b) Rear open space to extend through the rear wall. - The rear open space shall be co-extensive with the entire face of the rear wall. If a building abuts on two or more streets, such rear open space shall be provided throughout the entire face of the rear wall. Such rear wall shall be the wall on the opposite side of the face of the building abutting on the wider street unless the Authority otherwise directs.
(b) Rear open space to extend through the rear wall.
(3) Side open space.
(i) For detached buildings there shall be minimum side open spaces of 5 metres on both the sides.
Note. - For detached residential building upto 7 metres in height on plots with a frontage less than 12 metres one of the side open space may be reduced to 1.5 metres.
Note.
(ii) For semi-detached buildings there shall be a minimum side open space of 3 metres on one side.
Note. - For semi-detached, buildings up to 7 metres in height on plots with a frontage less than 9 metres ( See Rule 53(i) the side open space may be reduced to 1.5 metres.
Note.
(iii) For row-type buildings, no side open space is required.
(b) In the case of semi-detached buildings, the open spaces provided on one side shall be as in this sub-rule and all habitable rooms shall abut either on this side open space or front and rear open spaces or an interior open space.
(4) Provision of sub-rules (2) and (3) not to apply to certain parking lock up garage.
(5) Provision of sub-rules (1) to (3) to apply to residential building up to 10 metres in height.
(6) Open space for building of more than 10 metres height.
Table 5
Table 5
Open spaces for different heights of buildings
Open spaces for different heights of buildings
[Rule 56 (6)]
S.No.
S.No.
Height of building in metres
Height of building in metres
Open spaces to be left around building
excepting front on plot in metres
Open spaces to be left around building
excepting front on plot in metres
1.
10
3
2.
15
5
3.
18
6
4.
21
7
5.
24
8
6.
27
9
7.
30
10
8.
35
11
9.
40
12
10.
45
13
11.
50
14
12.
53 and above
15
Note 1. - For buildings above 24 metres in height, there shall be a minimum front open space of 6 metres.
Note 1.
Note 2. - Where rooms do not derive light and ventilation from exterior open space the width of such exterior open space as given in column (3) may be reduced by 1 metre subject to a minimum of 3 metres and a maximum of 8 metres. No further projections shall be permitted.
Note 2.
Note 3. - If the length or depth of the building exceeds 40 metres, add to column (3) 10 per cent of length or depth of building minus 4.0 metres.
Note 3.
(8) Interior open spaces. - (a) Inner Courtyard.
(ii) Further the inner courtyard shall have an area, through out its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard; provided that when any room (excluding staircase bay and bath rooms and water closet) is dependent for its light and ventilation on an inner courtyard, the dimension shall be such as is required for each wing of the building.
(iii) Where only water closet and bath room are abutting on the interior courtyard, the size of the interior courtyard shall be in line with the provision for ventilation shaft as given in clause (b).
(b) Ventilation Shaft. - For ventilating the spaces for water closet and bath room if not opening on the front, side, rear and interior open spaces, shall open on to the ventilation shaft, the size of which shall not be less than the values given below :-
(b) Ventilation Shaft.
Height of buildings in metres
Height of buildings in metres
Size of ventilation shaft in square metres
Size of ventilation shaft in square metres
Minimum size of shaft in metres
Minimum size of shaft in metres
Upto 10
1.2
0.9
12
2.8
1.2
18
4.0
1.5
24
5.4
1.8
30
8.0
2.4
above 30
9.0
3.0
Note 1. - For buildings above 30 metres mechanical ventilation system shall be installed besides the provision of minimum ventilation shaft.
Note 1.
Note 2. - For fully air-conditioned residential buildings for lodging purposes the ventilation shaft need not be insisted provided the air-conditioning system works in an uninterrupted manner; also there is an alternate source of power supply.
Note 2.
(c) Outer Courtyard. - The minimum width of outer courtyard (as distinguished from its depth) shall be not less than 24 metres. If the width of the outer courtyard is less than 2.4 metres, then it shall be treated as a notch and the provisions of outer courtyard shall not apply. However, if the depth of outer courtyard is more than the width, the provisions of Rule 55 (3) shall apply for the open spaces to be left between the wings.
(c) Outer Courtyard.
(9) Joint open air space.
(b) If such interior or exterior open air space is intended to be used for the benefit of more than one building belonging to the same owner, then the width of such open air space shall be the one specified for the tallest building as specified in sub-rules (5) and (6) of Rule 56 abutting on such open air space.
(c) If such interior or exterior open air space is jointly owned by more than one person, then its width shall also be as specified in Rules 59 provided that every such person agrees in writing to allow his portion of such joint open air space to be used for the benefit of every building abutting on such joint open air space and provided he sends such written consent to the Authority for record. Such common open air space shall thenceforth be treated as a permanently open air space required for the purposes of these rules. No boundary wall between such joint open air space shall be erected or raised to a height of more than 2.0 metres.
Section 56 • The M.P. Bhumi Vikas Rules, 1984
56. Residential Buildings-Exterior open spaces.
the-m-p-bhumi-vikas-rules-1984-sec-56.json
•
Section 56
{
"act_title": "The M.P. Bhumi Vikas Rules, 1984",
"act_slug": "the-m-p-bhumi-vikas-rules-1984",
"section_label": "Section",
"section": {
"number": "56",
"title": "56. Residential Buildings-Exterior open spaces.",
"chapter": null,
"content": "(1) Front open space.\nFront open space Min.\nFront open space Min.\nWidth of street facing the plot\nWidth of street facing the plot\n(i)\n1.5 metres\nupto 7.5 metres.\n(ii)\n3.0 metres\n7.5 to 18 metres*\n(iii)\n4.5 metres\n18 to 30 metres.\n(iv)\n6.0 metres\nabove 30 metres.\n*For building up to a maximum height of 7 metres.\nNote. - In case the two or more sides of the building front a street, the values apply to the average width subject to a minimum of 1.8 metres for cases (ii) (iii) and (iv).\nNote.\n(b) For streets less than 7.5 metres in width the distances of the building (building line) shall be at 5 metres from the centre line of the street.\nNote. - This limiting distance has to be determined by the Authority for the individual road/street width taking into account the traffic flow.\nNote.\n(2) Rear Open Space.\n(b) Rear open space to extend through the rear wall. - The rear open space shall be co-extensive with the entire face of the rear wall. If a building abuts on two or more streets, such rear open space shall be provided throughout the entire face of the rear wall. Such rear wall shall be the wall on the opposite side of the face of the building abutting on the wider street unless the Authority otherwise directs.\n(b) Rear open space to extend through the rear wall.\n(3) Side open space.\n(i) For detached buildings there shall be minimum side open spaces of 5 metres on both the sides.\nNote. - For detached residential building upto 7 metres in height on plots with a frontage less than 12 metres one of the side open space may be reduced to 1.5 metres.\nNote.\n(ii) For semi-detached buildings there shall be a minimum side open space of 3 metres on one side.\nNote. - For semi-detached, buildings up to 7 metres in height on plots with a frontage less than 9 metres ( See Rule 53(i) the side open space may be reduced to 1.5 metres.\nNote.\n(iii) For row-type buildings, no side open space is required.\n(b) In the case of semi-detached buildings, the open spaces provided on one side shall be as in this sub-rule and all habitable rooms shall abut either on this side open space or front and rear open spaces or an interior open space.\n(4) Provision of sub-rules (2) and (3) not to apply to certain parking lock up garage.\n(5) Provision of sub-rules (1) to (3) to apply to residential building up to 10 metres in height.\n(6) Open space for building of more than 10 metres height.\nTable 5\nTable 5\nOpen spaces for different heights of buildings\nOpen spaces for different heights of buildings\n[Rule 56 (6)]\nS.No.\nS.No.\nHeight of building in metres\nHeight of building in metres\nOpen spaces to be left around building\n\t\t\t\t\texcepting front on plot in metres\nOpen spaces to be left around building\n\t\t\t\t\texcepting front on plot in metres\n1.\n10\n3\n2.\n15\n5\n3.\n18\n6\n4.\n21\n7\n5.\n24\n8\n6.\n27\n9\n7.\n30\n10\n8.\n35\n11\n9.\n40\n12\n10.\n45\n13\n11.\n50\n14\n12.\n53 and above\n15\nNote 1. - For buildings above 24 metres in height, there shall be a minimum front open space of 6 metres.\nNote 1.\nNote 2. - Where rooms do not derive light and ventilation from exterior open space the width of such exterior open space as given in column (3) may be reduced by 1 metre subject to a minimum of 3 metres and a maximum of 8 metres. No further projections shall be permitted.\nNote 2.\nNote 3. - If the length or depth of the building exceeds 40 metres, add to column (3) 10 per cent of length or depth of building minus 4.0 metres.\nNote 3.\n(8) Interior open spaces. - (a) Inner Courtyard.\n(ii) Further the inner courtyard shall have an area, through out its height, of not less than the square of one-fifth the height of the highest wall abutting the courtyard; provided that when any room (excluding staircase bay and bath rooms and water closet) is dependent for its light and ventilation on an inner courtyard, the dimension shall be such as is required for each wing of the building.\n(iii) Where only water closet and bath room are abutting on the interior courtyard, the size of the interior courtyard shall be in line with the provision for ventilation shaft as given in clause (b).\n(b) Ventilation Shaft. - For ventilating the spaces for water closet and bath room if not opening on the front, side, rear and interior open spaces, shall open on to the ventilation shaft, the size of which shall not be less than the values given below :-\n(b) Ventilation Shaft.\nHeight of buildings in metres\nHeight of buildings in metres\nSize of ventilation shaft in square metres\nSize of ventilation shaft in square metres\nMinimum size of shaft in metres\nMinimum size of shaft in metres\nUpto 10\n1.2\n0.9\n12\n2.8\n1.2\n18\n4.0\n1.5\n24\n5.4\n1.8\n30\n8.0\n2.4\nabove 30\n9.0\n3.0\nNote 1. - For buildings above 30 metres mechanical ventilation system shall be installed besides the provision of minimum ventilation shaft.\nNote 1.\nNote 2. - For fully air-conditioned residential buildings for lodging purposes the ventilation shaft need not be insisted provided the air-conditioning system works in an uninterrupted manner; also there is an alternate source of power supply.\nNote 2.\n(c) Outer Courtyard. - The minimum width of outer courtyard (as distinguished from its depth) shall be not less than 24 metres. If the width of the outer courtyard is less than 2.4 metres, then it shall be treated as a notch and the provisions of outer courtyard shall not apply. However, if the depth of outer courtyard is more than the width, the provisions of Rule 55 (3) shall apply for the open spaces to be left between the wings.\n(c) Outer Courtyard.\n(9) Joint open air space.\n(b) If such interior or exterior open air space is intended to be used for the benefit of more than one building belonging to the same owner, then the width of such open air space shall be the one specified for the tallest building as specified in sub-rules (5) and (6) of Rule 56 abutting on such open air space.\n(c) If such interior or exterior open air space is jointly owned by more than one person, then its width shall also be as specified in Rules 59 provided that every such person agrees in writing to allow his portion of such joint open air space to be used for the benefit of every building abutting on such joint open air space and provided he sends such written consent to the Authority for record. Such common open air space shall thenceforth be treated as a permanently open air space required for the purposes of these rules. No boundary wall between such joint open air space shall be erected or raised to a height of more than 2.0 metres.",
"footnote": "",
"is_definition": false,
"sort_order": 51
},
"prev_section": "55",
"next_section": "57"
}