Vertically Metre
Vertically Metre
Horizontally Metre
Horizontally Metre
(a)
Low and Medium voltage lines and service lines.
2.5
1.2
(b)
High voltage lines up to and including 33000 volts.
3.7
1.2
(c)
Extra high voltage lines beyond 33000 volts.
(See Note)
Note. - For building close to extra high voltage lines beyond 33000 volts clear horizontal corridor of 15 metres, or as specified in the latest version of the Indian Electricity Rules shall be provided.
Note.
Section 52 • The M.P. Bhumi Vikas Rules, 1984
52. Distance from Electric Lines.
the-m-p-bhumi-vikas-rules-1984-sec-52.json
•
Section 52
{
"act_title": "The M.P. Bhumi Vikas Rules, 1984",
"act_slug": "the-m-p-bhumi-vikas-rules-1984",
"section_label": "Section",
"section": {
"number": "52",
"title": "52. Distance from Electric Lines.",
"chapter": null,
"content": "Vertically Metre\nVertically Metre\nHorizontally Metre\nHorizontally Metre\n(a)\nLow and Medium voltage lines and service lines.\n2.5\n1.2\n(b)\nHigh voltage lines up to and including 33000 volts.\n3.7\n1.2\n(c)\nExtra high voltage lines beyond 33000 volts.\n(See Note)\nNote. - For building close to extra high voltage lines beyond 33000 volts clear horizontal corridor of 15 metres, or as specified in the latest version of the Indian Electricity Rules shall be provided.\nNote.",