[(a) Sub-stations and switch-stations shall preferably be erected above ground, but where necessarily constructed underground due provisions for ventilation and drainage shall be made and any space housing switchgear shall not be used for storage of any materials especially inflammable and combustible materials or refuse.]
(b) Outdoor sub-stations except pole type sub-stations and outdoor switch-stations shall (unless the apparatus is completely enclosed in a metal covering connected with earth, the said apparatus also being connected with the system by armoured cables) be efficiently protected by fencing not less than [1.8 metres] in height or other means so as to prevent access to the electric supply lines and apparatus therein by an unauthorised person.
(c) Underground street boxes (other than sub-stations) which contain transformers shall not contain switches or other apparatus, and switches, cut-outs or other apparatus required for controlling or other purposes shall be fixed in separate receptacles above ground wherever practicable.
Section 68 • The Indian Electricity Rules, 1956
68. General conditions as to transformation and control of energy
the-indian-electricity-rules-1956-sec-68.json
•
Section 68
{
"act_title": "The Indian Electricity Rules, 1956",
"act_slug": "the-indian-electricity-rules-1956",
"section_label": "Section",
"section": {
"number": "68",
"title": "68. General conditions as to transformation and control of energy",
"chapter": null,
"content": "[(a) Sub-stations and switch-stations shall preferably be erected above ground, but where necessarily constructed underground due provisions for ventilation and drainage shall be made and any space housing switchgear shall not be used for storage of any materials especially inflammable and combustible materials or refuse.]\n(b) Outdoor sub-stations except pole type sub-stations and outdoor switch-stations shall (unless the apparatus is completely enclosed in a metal covering connected with earth, the said apparatus also being connected with the system by armoured cables) be efficiently protected by fencing not less than [1.8 metres] in height or other means so as to prevent access to the electric supply lines and apparatus therein by an unauthorised person.\n(c) Underground street boxes (other than sub-stations) which contain transformers shall not contain switches or other apparatus, and switches, cut-outs or other apparatus required for controlling or other purposes shall be fixed in separate receptacles above ground wherever practicable.",
"footnote": "",
"is_definition": false,
"sort_order": 67
},
"prev_section": "67",
"next_section": "69"
}