(a) where the earthed or earthed neutral conductor is the property of the supplier, at or near the point of commencement of supply;
(b) where a conductor forming part of a consumer's system is to be connected to the supplier's earthed or earthed neutral conductor, at the point where such connection is to be made;
(c) in all other cases, at a point corresponding to the point of commencement of supply or at such other points as may be approved by an Inspector or any officer appointed to assist the Inspector and [authorised under sub-rule (2) of rule 4-A]
(a) a link for testing purposes, or
(b) a switch for use in controlling a generator or transformer.
Section 32 • The Indian Electricity Rules, 1956
32. Identification of earthed and earthed neutral conductors and position of switches and cut-outs therein
the-indian-electricity-rules-1956-sec-32.json
•
Section 32
{
"act_title": "The Indian Electricity Rules, 1956",
"act_slug": "the-indian-electricity-rules-1956",
"section_label": "Section",
"section": {
"number": "32",
"title": "32. Identification of earthed and earthed neutral conductors and position of switches and cut-outs therein",
"chapter": null,
"content": "(a) where the earthed or earthed neutral conductor is the property of the supplier, at or near the point of commencement of supply;\n(b) where a conductor forming part of a consumer's system is to be connected to the supplier's earthed or earthed neutral conductor, at the point where such connection is to be made;\n(c) in all other cases, at a point corresponding to the point of commencement of supply or at such other points as may be approved by an Inspector or any officer appointed to assist the Inspector and [authorised under sub-rule (2) of rule 4-A]\n(a) a link for testing purposes, or\n(b) a switch for use in controlling a generator or transformer.",
"footnote": "",
"is_definition": false,
"sort_order": 34
},
"prev_section": "31",
"next_section": "33"
}