95C. Genset run on Diesel and Natural Gas (NG) or Diesel and Liquid Petroleum Gas (LPG) :-

A. Emission Limits.
Table
Table
Power Category
Power Category
Emission Limits (g/kW-hr)
Emission Limits (g/kW-hr)
Smoke Limit (light absorption coefficient,m -1 )
Smoke Limit (light absorption coefficient,m -1 )
NOX + THC or NOX + NMHCor RHC
NOX + THC or NOX + NMHCor RHC
CO
CO
PM
PM
Upto 19 kW
≤ 7.5
≤ 3.5
≤ 0.3
≤ 0.7
More than 19 kW upto 75 kW
≤ 4.7
≤ 3.5
≤ 0.3
≤ 0.7
More than 75 kW upto 800 kW
≤ 4.0
≤ 3.5
≤ 0.2
≤ 0.7
Notes. - The abbreviations used in the Table shall mean as under: 1. NOX - Oxides of Nitrogen; THC - Total Hydrocarbon; CO- Carbon Monoxide; PM - Particulate Matter; NMHC - Non - Methane Hydrocarbon; and RHC - Reactive Hydrocarbon.
Notes.