(b) Each lift machine operated a Polyphase A. C. Motor shall be protected against phase reversal or phase failure. This shall not apply to A. C. Motors used in motor generator sets.
(c) The installation of condensers, the operation or failure of which will cause an unsafe condition, shall be prohibited.
(d) Provision of emergency stop switches for short-circuiting the landing lock circuit is prohibited.
(e) All control circuits shall be fused, or otherwise protected against faults or overload, independently of the main circuits.
(f) The voltage of any controller operating circuits shall not exceed low pressure as defined in the Indian Electricity Rules, 1937.
(g) Controllers, operated by hand-ropes, levers or similar devices shall not be permitted.
Section 24 • The Bombay Lifts Rules, 1958
24. Controllers.
the-bombay-lifts-rules-1958-sec-24.json
•
Section 24
{
"act_title": "The Bombay Lifts Rules, 1958",
"act_slug": "the-bombay-lifts-rules-1958",
"section_label": "Section",
"section": {
"number": "24",
"title": "24. Controllers.",
"chapter": null,
"content": "(b) Each lift machine operated a Polyphase A. C. Motor shall be protected against phase reversal or phase failure. This shall not apply to A. C. Motors used in motor generator sets.\n(c) The installation of condensers, the operation or failure of which will cause an unsafe condition, shall be prohibited.\n(d) Provision of emergency stop switches for short-circuiting the landing lock circuit is prohibited.\n(e) All control circuits shall be fused, or otherwise protected against faults or overload, independently of the main circuits.\n(f) The voltage of any controller operating circuits shall not exceed low pressure as defined in the Indian Electricity Rules, 1937.\n(g) Controllers, operated by hand-ropes, levers or similar devices shall not be permitted.",
"footnote": "",
"is_definition": false,
"sort_order": 31
},
"prev_section": "23",
"next_section": "25"
}