Sl. No
Sl. No
Description
Description
All Areas
All Areas
A.
Minimum Road width
12m.
15m.
18m.
B.
Normally Permissible FSI
2.0
2.5
3.25
C.
Maximum Coverage
50%
D.
Minimum set back all around
Height of the building above ground level
Minimum required setback space from the property
boundary
Upto 30m.
7m.
Above 30m.
For every increase in height of 6m or part
thereof above 30m minimum extent of setback space to be left
additionally shall be one meter subject to the maximum setback of
20m.
E.
Spacing between blocks in case of more than one
block of High Rise building
Height of the building above ground level
Minimum required spacing between blocks
Upto 30m.
7m.
Above 30m.
For every increase in height of 6m. or par
thereof above 30m. space to be left additionally shall be one
meter subject to the maximum setback of 20m.
(ii) In the event of the road width being less than the qualifying width in certain portions then the total length of such portions shall not be more than 10% of the prescribed length. In such cases the average road width for the prescribed length shall be equal or above the qualifying width.
(iii) In the event of the sub-division for qualifying road not being incorporated in the Field Measurement Book sketch, in such cases road width certificate shall be obtained from the concerned Executive Authority of Local Body.
(iv) In the event of extent and dimension of the site between Patta and document the least extent of the site to be considered along with site dimension corresponding to the least extent.
(v) In the cases where street alignment has been prescribed, the front open space shall be left from the street alignment.
(ii) FSI benefit shall be permitted for the land left for OSR, link road, street alignment or road widening wherever it is insisted upon by competent authority.
(iii) FSI benefit shall not be permitted for the land left for road widening to make the road as qualifying road for the proposed development.
(iv) FSI benefit for the OSR area in the approved sub-division shall be permitted in proportionate to the plot extent.
(b) A watchman or caretaker booth or Kiosk not exceeding 2.5m.x 2.5m. in size at each gate and not exceeding 3m. in height and open transformer yard shall be permitted in the set back space after leaving 7 meters clear set back from the main structure.
(c) Gate pillars without or with arches with a min. headroom clearance of 5.50m at-least to a width of 3.5m. shall be permitted in the set back space after leaving 7 meters clear set back from the main structure.
(b) In cases where more than one basement is proposed for parking and incidental uses, sufficient provision for lighting and ventilation and also for protection from fire to the satisfaction of Directorate of Fire and Rescue Services shall be made.
(c) During the construction of the basement floor, it shall be the sole responsibility of the Building Permit holder to ensure that the building or structure in the adjoining sites are not weakened or damaged.
(d) The basement shall be permitted below the ground and beyond the building lines at ground level subject to a clear minimum front setback space of 4.5m and side and rear setback of 3m, subject to non habitable uses and provision for mechanical ventilation and all safety provisions and drainage. However, it is essential that the basement top slab below the external circulation at ground level should be designed for firefighting vehicular loads
(b) Every High Rise Building erected shall be provided with
(i) lifts as prescribed in National Building Code of India, 2016;
(ii) a stand-by electric generator of adequate capacity for running lift and water pump, and a room to accommodate the generator;
(iii) an electrical room confirming to the rule 44.
(iv) at least one meter room of size 2.4 meters by 2.4 meters for every 10 consumers or 3 floor whichever is less. The meter room shall be provided in the ground floor.
(ii) In building of such size, arrangement or occupancy that a fire may not itself provide adequate warning to occupants, automatic fire detecting and alarming facilities shall be provided where necessary to warn occupants or the existence of fires, so that they may escape, or to facilitate the orderly conduct of fire exit drills.
(iii) Fire protecting and extinguishing system shall conform to accepted standards and shall be installed in accordance with good practice as recommended in the National Building Code of India, 2016 and to the satisfaction of the Director of Fire and Rescue Services by obtaining a no objection certificate from him.
(b) The applicant not being a Government department or agency shall pay a sum of Rs. 10,000/- (Rupees ten thousand only) as earnest money non-interest bearing refundable deposit and same should be utilized for the purpose of installing the prescribed size board on the site by local body, in the event of the applicant not fulfilling the conditions stated in clause (a) above.
(a) Where number of dwelling units exceeds 50 nos. or 2500 sq.m. of commercial area sewage treatment plant shall be provided and maintained for the disposal of the sewage within the site itself as per the designs approved by such other Technical agencies as Government may impaneled from time to time.
(b) where number of dwelling units is less than 50 nos. or 2500 sq.m. of commercial area, septic tank with up-flow filters shall be provided and maintained for the disposal of the sewage within the site itself.
(b) Premium FSI charges shall not be collected for the excess FSI area over and above normally permissible FSI area for affordable housing projects.
Section 39 • Tamil Nadu Combined Development and Building Rules, 2019
39. Special rules for High Rise Buildings.
tamil-nadu-combined-development-and-building-rules-2019-sec-39.json
•
Section 39
{
"act_title": "Tamil Nadu Combined Development and Building Rules, 2019",
"act_slug": "tamil-nadu-combined-development-and-building-rules-2019",
"section_label": "Section",
"section": {
"number": "39",
"title": "39. Special rules for High Rise Buildings.",
"chapter": null,
"content": "Sl. No\nSl. No\nDescription\nDescription\nAll Areas\nAll Areas\nA.\nMinimum Road width\n12m.\n15m.\n18m.\nB.\nNormally Permissible FSI\n2.0\n2.5\n3.25\nC.\nMaximum Coverage\n50%\nD.\nMinimum set back all around\nHeight of the building above ground level\nMinimum required setback space from the property\n\t\t\t\tboundary\nUpto 30m.\n7m.\nAbove 30m.\nFor every increase in height of 6m or part\n\t\t\t\tthereof above 30m minimum extent of setback space to be left\n\t\t\t\tadditionally shall be one meter subject to the maximum setback of\n\t\t\t\t20m.\nE.\nSpacing between blocks in case of more than one\n\t\t\t\tblock of High Rise building\nHeight of the building above ground level\nMinimum required spacing between blocks\nUpto 30m.\n7m.\nAbove 30m.\nFor every increase in height of 6m. or par\n\t\t\t\tthereof above 30m. space to be left additionally shall be one\n\t\t\t\tmeter subject to the maximum setback of 20m.\n(ii) In the event of the road width being less than the qualifying width in certain portions then the total length of such portions shall not be more than 10% of the prescribed length. In such cases the average road width for the prescribed length shall be equal or above the qualifying width.\n(iii) In the event of the sub-division for qualifying road not being incorporated in the Field Measurement Book sketch, in such cases road width certificate shall be obtained from the concerned Executive Authority of Local Body.\n(iv) In the event of extent and dimension of the site between Patta and document the least extent of the site to be considered along with site dimension corresponding to the least extent.\n(v) In the cases where street alignment has been prescribed, the front open space shall be left from the street alignment.\n(ii) FSI benefit shall be permitted for the land left for OSR, link road, street alignment or road widening wherever it is insisted upon by competent authority.\n(iii) FSI benefit shall not be permitted for the land left for road widening to make the road as qualifying road for the proposed development.\n(iv) FSI benefit for the OSR area in the approved sub-division shall be permitted in proportionate to the plot extent.\n(b) A watchman or caretaker booth or Kiosk not exceeding 2.5m.x 2.5m. in size at each gate and not exceeding 3m. in height and open transformer yard shall be permitted in the set back space after leaving 7 meters clear set back from the main structure.\n(c) Gate pillars without or with arches with a min. headroom clearance of 5.50m at-least to a width of 3.5m. shall be permitted in the set back space after leaving 7 meters clear set back from the main structure.\n(b) In cases where more than one basement is proposed for parking and incidental uses, sufficient provision for lighting and ventilation and also for protection from fire to the satisfaction of Directorate of Fire and Rescue Services shall be made.\n(c) During the construction of the basement floor, it shall be the sole responsibility of the Building Permit holder to ensure that the building or structure in the adjoining sites are not weakened or damaged.\n(d) The basement shall be permitted below the ground and beyond the building lines at ground level subject to a clear minimum front setback space of 4.5m and side and rear setback of 3m, subject to non habitable uses and provision for mechanical ventilation and all safety provisions and drainage. However, it is essential that the basement top slab below the external circulation at ground level should be designed for firefighting vehicular loads\n(b) Every High Rise Building erected shall be provided with\n(i) lifts as prescribed in National Building Code of India, 2016;\n(ii) a stand-by electric generator of adequate capacity for running lift and water pump, and a room to accommodate the generator;\n(iii) an electrical room confirming to the rule 44.\n(iv) at least one meter room of size 2.4 meters by 2.4 meters for every 10 consumers or 3 floor whichever is less. The meter room shall be provided in the ground floor.\n(ii) In building of such size, arrangement or occupancy that a fire may not itself provide adequate warning to occupants, automatic fire detecting and alarming facilities shall be provided where necessary to warn occupants or the existence of fires, so that they may escape, or to facilitate the orderly conduct of fire exit drills.\n(iii) Fire protecting and extinguishing system shall conform to accepted standards and shall be installed in accordance with good practice as recommended in the National Building Code of India, 2016 and to the satisfaction of the Director of Fire and Rescue Services by obtaining a no objection certificate from him.\n(b) The applicant not being a Government department or agency shall pay a sum of Rs. 10,000/- (Rupees ten thousand only) as earnest money non-interest bearing refundable deposit and same should be utilized for the purpose of installing the prescribed size board on the site by local body, in the event of the applicant not fulfilling the conditions stated in clause (a) above.\n(a) Where number of dwelling units exceeds 50 nos. or 2500 sq.m. of commercial area sewage treatment plant shall be provided and maintained for the disposal of the sewage within the site itself as per the designs approved by such other Technical agencies as Government may impaneled from time to time.\n(b) where number of dwelling units is less than 50 nos. or 2500 sq.m. of commercial area, septic tank with up-flow filters shall be provided and maintained for the disposal of the sewage within the site itself.\n(b) Premium FSI charges shall not be collected for the excess FSI area over and above normally permissible FSI area for affordable housing projects.",
"footnote": "",
"is_definition": false,
"sort_order": 39
},
"prev_section": "38",
"next_section": "40"
}