← Back to Jharkhand Building Byelaws 2016

32. Distance from Electric lines.

Table - 5: Minimum distance from electric line
Table - 5: Minimum distance from electric line
Vertical distance in meters
Vertical distance in meters
Horizontal distance in meters
Horizontal distance in meters
Low and medium voltage lines and service lines
2.5
2.5
High voltage lines up to and including 11.000
Volt
Not Permitted
3.7
High voltage lines above 11.000 volt and up to
and including 33,000 Volt
Not Permitted
3.7
Extra high voltage line beyond 33.000 Volt
Not Permitted
3.7 (Plus 0.3 meters for every additional 33,000
volts or part thereof)