(i) the urinal shall be provided with a basin, stall, through or other receptacle of non-absorbent material;
(ii) the outset from the receptacle shall be provided with an efficient grating.
(iii) the urinals shall be provided with suitable apparatus for effectually flushing and cleansing the receptacle.
(iv) no part of the urinal apparatus, other than the flushing apparatus shall be directly connected with a supply or distributing pipe;
(v) if the urinal can be entered from within the building, and is constructed to discharge into a waste pipe which also receives the discharge from another urinal, or from a water closet, bath, sink, bidet or lavatory basin, the trap of urinal shall be ventilated by a pipe which shall :-
(a) be of an internal diameter not less than that of the trap or 50 millimetre whichever is less;
(b) be connected with the waste pipe from the urinal at a point not less than 7.5 centimetre and not more than 30 centimetre from the highest part of the trap, on that side of the water seal which is nearer to the waste pipe; and
(c) either have an open end as high as the top of the waste pipe or be carried into a waste pipe at a point not less than 1.0 metre above the highest connection to the waste pipe.
60.
(a) be of suitable size, and if it is intended for the conveyance of foul water shall have an internal diameter of not less than 100 millimetre;
(b) be laid with a suitable fall and where practicable in a direct line. The standard gradient shall be 1 in 40 for a 100 millimetre drain and 1 in 60 for 150 millimetre drain. The maximum and minimum gradient shall respectively be 1 in 20 and 1 in 80 for a 100 millimetre drain and 1 in 40 and 1 in 140 respectively for 150 millimetre drain.
(b) Where a drain or part thereof is constructed within or under a building, such drain or such part thereof shall be laid or fixed in a direct line, where practicable and be provided with adequate means of access.
(c) Such drains within the built area shall be either Hard Cast Iron pipes or shall be encased with 15 centimetres of cement concrete of M150 all round if any other pipe is used.
(a) 5 centimetre where such inlet has an internal diameter of less than 80 millimetres.
(b) 7.5 centimetre where such inlet has an internal diameter of more than 80 millimetre.
(c) Every trapped gully shall be covered with a granting the bars of which shall be no more than 10 millimetre apart.
Section 59 • Faridabad Complex Administration Building Rules, 1989
59. Urinals. Sections 43(2), 57(2)(m).
faridabad-complex-administration-building-rules-1989-sec-59.json
•
Section 59
{
"act_title": "Faridabad Complex Administration Building Rules, 1989",
"act_slug": "faridabad-complex-administration-building-rules-1989",
"section_label": "Section",
"section": {
"number": "59",
"title": "59. Urinals. Sections 43(2), 57(2)(m).",
"chapter": null,
"content": "(i) the urinal shall be provided with a basin, stall, through or other receptacle of non-absorbent material;\n(ii) the outset from the receptacle shall be provided with an efficient grating.\n(iii) the urinals shall be provided with suitable apparatus for effectually flushing and cleansing the receptacle.\n(iv) no part of the urinal apparatus, other than the flushing apparatus shall be directly connected with a supply or distributing pipe;\n(v) if the urinal can be entered from within the building, and is constructed to discharge into a waste pipe which also receives the discharge from another urinal, or from a water closet, bath, sink, bidet or lavatory basin, the trap of urinal shall be ventilated by a pipe which shall :-\n(a) be of an internal diameter not less than that of the trap or 50 millimetre whichever is less;\n(b) be connected with the waste pipe from the urinal at a point not less than 7.5 centimetre and not more than 30 centimetre from the highest part of the trap, on that side of the water seal which is nearer to the waste pipe; and\n(c) either have an open end as high as the top of the waste pipe or be carried into a waste pipe at a point not less than 1.0 metre above the highest connection to the waste pipe.\n60.\n(a) be of suitable size, and if it is intended for the conveyance of foul water shall have an internal diameter of not less than 100 millimetre;\n(b) be laid with a suitable fall and where practicable in a direct line. The standard gradient shall be 1 in 40 for a 100 millimetre drain and 1 in 60 for 150 millimetre drain. The maximum and minimum gradient shall respectively be 1 in 20 and 1 in 80 for a 100 millimetre drain and 1 in 40 and 1 in 140 respectively for 150 millimetre drain.\n(b) Where a drain or part thereof is constructed within or under a building, such drain or such part thereof shall be laid or fixed in a direct line, where practicable and be provided with adequate means of access.\n(c) Such drains within the built area shall be either Hard Cast Iron pipes or shall be encased with 15 centimetres of cement concrete of M150 all round if any other pipe is used.\n(a) 5 centimetre where such inlet has an internal diameter of less than 80 millimetres.\n(b) 7.5 centimetre where such inlet has an internal diameter of more than 80 millimetre.\n(c) Every trapped gully shall be covered with a granting the bars of which shall be no more than 10 millimetre apart.",
"footnote": "",
"is_definition": false,
"sort_order": 57
},
"prev_section": "58",
"next_section": "42"
}