62. Electricity and Telephone Connection.

Table 5: Specifications for Electricity lines
Table 5: Specifications for Electricity lines
Vertical distance in meters from the building
Horizontal distance in meters from the building
Low and medium voltage lines and service lines
2.5
1.2
High Voltage lines up to and including 33 KV
3.7
2.0
Extra High Voltage lines beyond 33 KV
4.6
4.5
(Plus 0.3 meters for every additional 33 KV or part
thereof)
(Plus 0.3 meters for every additional 33 KV or part
thereof)