Vertical Clearance
Horizontal clearance
(a)
Low and medium voltage lines including service lines
2.5m
1.2m
(b)
High voltage lines up to and including 11,000 volts
3.7m
1.2m
(c)
High voltage lines above 11,000 volts and up to and including
33,000 volts
3.7m
2.0m
(d)
For extra high voltage lines beyond 33,000 volts
3.7m plus .3 for every additional 33,000 volts or parts
thereof
2.m plus 0.3 for every additional 33,000 volts or parts
thereof
Section 43 • West Bengal Municipal (Building) Rules, 2007
43. Distance from electric lines.
west-bengal-municipal-building-rules-2007-sec-43.json
•
Section 43
{
"act_title": "West Bengal Municipal (Building) Rules, 2007",
"act_slug": "west-bengal-municipal-building-rules-2007",
"section_label": "Section",
"section": {
"number": "43",
"title": "43. Distance from electric lines.",
"chapter": null,
"content": "Vertical Clearance\nHorizontal clearance\n(a)\nLow and medium voltage lines including service lines\n2.5m\n1.2m\n(b)\nHigh voltage lines up to and including 11,000 volts\n3.7m\n1.2m\n(c)\nHigh voltage lines above 11,000 volts and up to and including\n\t\t\t\t33,000 volts\n3.7m\n2.0m\n(d)\nFor extra high voltage lines beyond 33,000 volts\n3.7m plus .3 for every additional 33,000 volts or parts\n\t\t\t\tthereof\n2.m plus 0.3 for every additional 33,000 volts or parts\n\t\t\t\tthereof",