168. Special conditions.

(b) The total floor area, height and ground coverage after addition to an existing building shall not exceed the provisions of maximum permissible floor area, height and open space as per the criteria specified in the rules 162, 163, 164 and other relevant rules, while additions to an existing building shall further conform to the provisions for front, rear and side setback as specified in these rules.
(b) Individual column of all RCC framed buildings as well as all external and internal walls of a load bearing structure, shall be interconnected in two directions at right angles by RCC beams at plinth level adequately designed in accordance with BIS Codes of Practice;
(c) There shall be adequately designed RCC lintel bands in all external and internal brick and stone masonry walls at vertical intervals not more than 0.9 metre. These shall be continuous and connected to each other at the same level in the case of all load bearing walls and tied to the columns in case of RCC framed structures.
Residential tenement (internal)
0.9 metres;
Mercantile, Business and Assembly buildings
2.0 metres;
Access to shop in mercantile buildings:
Shops on one side only
2.0 metres;
Shops on both sides
3.0 metres;