118. Lighting and Ventilation of rooms.

(b) Cross ventilation by means of windows shall be effected in at least one living room of a tenement either by means of windows in opposite walls, or if this is not possible or advisable, then, at least in the adjoining walls.
(a) windows having an area of not less than 10 per cent of the floor area and located in an exterior wall facing a street alley yard or an airshaft whose dimension in the direction perpendicular to the window is not less than 1/3 of the height of the building on which ti, window is located subject to a maximum and a minimum limit of 6 m (20 ft) and 1 m (3 ft) respectively;
(b) skylights, the construction of which shall provide light and ventilation as required in clause (a):
(c) ventilation ducts, provided such ducts have 1.30 cm2 of area for each m2 (2 in2 of area for each ft2) of floor area with a minimum total area of 330 m2 (48 in2) and a least dimension of 9 cm (31/2 in). The vent register or grills to the duct shall be located in or next to the ceiling or the ventilated space. A separate duct from each space or room shall run to and above the roof and shall be provided with a lowered vent stack :
(i) smoke shall not come out during the time of firing and cooking;
(ii) each kitchen shall be provided with a separate chimney;
(iii) chimneys provided for smokeless chullas shall be made of suitable diameter;
(iv) suitable provision shall be made at the bottom of chimney for clearing.
(i) 3 m (10 ft) in case of ground and one upper floor structure;
(ii) 4 m (15 ft) in case of ground and two upper floor structures;
(iii) 6 m (20 ft) in case of further higher structures :