(a) Single-phase 2 wire 240 volts between phase and neutral for supply to a total connected load not exceeding 4,000 watts (including power loads).
(b) three-phase 4 wire 415 volts between phases and 240 volts between phase and neutral for supply to a total connected load exceeding 4,000 watts but not exceeding a demand of 112 KW.
(c) The consumer may elect to avail supply under any one of the above categories where the connected load does not exceed 4,000 watts.
(d) Three-phase 3 wire, 11,000 volts and above between phases for power installation exceeding a demand of 112 KW, the minimum demand however being 63 KVA.
(e) The consumer shall avail supply at 33 KV and above when the demand is 5 MVA and above.
Section 3 • The Tamil Nadu Electricity Supply Code, 2004
3. Categories of supply.
the-tamil-nadu-electricity-supply-code-2004-sec-3.json
•
Section 3
{
"act_title": "The Tamil Nadu Electricity Supply Code, 2004",
"act_slug": "the-tamil-nadu-electricity-supply-code-2004",
"section_label": "Section",
"section": {
"number": "3",
"title": "3. Categories of supply.",
"chapter": null,
"content": "(a) Single-phase 2 wire 240 volts between phase and neutral for supply to a total connected load not exceeding 4,000 watts (including power loads).\n(b) three-phase 4 wire 415 volts between phases and 240 volts between phase and neutral for supply to a total connected load exceeding 4,000 watts but not exceeding a demand of 112 KW.\n(c) The consumer may elect to avail supply under any one of the above categories where the connected load does not exceed 4,000 watts.\n(d) Three-phase 3 wire, 11,000 volts and above between phases for power installation exceeding a demand of 112 KW, the minimum demand however being 63 KVA.\n(e) The consumer shall avail supply at 33 KV and above when the demand is 5 MVA and above.",
"footnote": "",
"is_definition": false,
"sort_order": 2
},
"prev_section": "2",
"next_section": "4"
}