73J. Thermic Fluit Heaters.

(i) level control in the expansion tank;
(ii) temperature control of thermic fluid;
(iii) differential pressure switch on the out let line of the heater tubes; and
(iv) temperature control device for the fuel oil supply to the burner.
(i) weekly checks carried out conforming the effectiveness of the interlock;
(ii) weekly checks confirming that all accessories are in good state of repairs; and
(iii) information regarding fuel oil temperature pressure, thermic fluid inlet/outlet pressure and temperature fuel gas temperature, recorded at 4 hourly interval.