Clearance from Overhead Electric Lines
Clearance from Overhead Electric Lines
Sl.No
Sl.No
Type of Electric supply Line
Type of Electric supply Line
Minimum Vertical clearance in metres
Minimum Vertical clearance in metres
Minimum Horizontal clearance in metres.
Minimum Horizontal clearance in metres.
1
Low and medium voltage lines
2.40
1.20
2
High voltage lines up to and including 33000
volts
3.70
1.85
3
Extra high voltage lines above 33000 volts
3.70 plus 0.30m for every additional 33000 volts
or part thereof
1.85 plus 0.30m for every additional 33000 volts
or part thereof
Section 26 • The Kerala Panchayat Buildings Rules, 2011
26. General requirements regarding plot.
the-kerala-panchayat-buildings-rules-2011-sec-26.json
•
Section 26
{
"act_title": "The Kerala Panchayat Buildings Rules, 2011",
"act_slug": "the-kerala-panchayat-buildings-rules-2011",
"section_label": "Section",
"section": {
"number": "26",
"title": "26. General requirements regarding plot.",
"chapter": null,
"content": "Clearance from Overhead Electric Lines\nClearance from Overhead Electric Lines\nSl.No\nSl.No\nType of Electric supply Line\nType of Electric supply Line\nMinimum Vertical clearance in metres\nMinimum Vertical clearance in metres\nMinimum Horizontal clearance in metres.\nMinimum Horizontal clearance in metres.\n1\nLow and medium voltage lines\n2.40\n1.20\n2\nHigh voltage lines up to and including 33000\n\t\t\t\tvolts\n3.70\n1.85\n3\nExtra high voltage lines above 33000 volts\n3.70 plus 0.30m for every additional 33000 volts\n\t\t\t\tor part thereof\n1.85 plus 0.30m for every additional 33000 volts\n\t\t\t\tor part thereof",
"footnote": "",
"is_definition": false,
"sort_order": 28
},
"prev_section": "25",
"next_section": "27"
}