61A. Fire fighting apparatus and water supply.

(a) Two fire buckets of not less than 5 gallons capacity for every 1000 sq. ft. of floor area subjects to a minimum of four buckets on each floor.
(b) Every bucket provided under this sub-rule shall-
(i) conform to appropriate Indian Standards specification ;
(ii) be kept in a position approved by the Inspector and shall be used for no other purpose than fire extinguishing ; and
(iii) at all times be kept full of water, but if the principal fire risk arises from inflammable liquid or other substances where water cannot be used, it shall be kept full of clean, fine dry and, stone dust or other inert material:
(b) In factories where fires may occur due to inflammable liquids or grease or paint, the extinguishers to be provided at the scale laid down in clause (a) shall consist of foam, carbon tetrachloride, dry powder, carbondioxide, chlorobrome methane or other equivalent type.
(c) In factories where fires may occur due to electrical equipment, the extinguisher to be provided at the scale laid in clause (a) shall consist of carbon tetrachloride or equivalent types.
(d) In factories where fires may occur due to magnesium, aluminum or zinc dust or shavings of other ignitable metals, the use of liquids, carbondioxide and foam type extinguishers shall be prohibited and an ample supply of clean, fine dry, sand, stone dust or other inert material shall be kept ready for segregating such fires.
(e) Every type of portable fire extinguisher shall be kept mounted in a position approved by the Inspector :
(i) conform to the appropriate Indian Standards Specification ;
(ii) be kept charged ready for use, properly mounted in a position approved by the Inspector and accompanied by the maker's printed instructions for its use ; and
(iii) be examined, tested or discharged periodically in accordance with the maker's recommendation.
(b) The manager of every factory shall keep and maintain sufficient number of spare for each type of extinguisher provided in the factory with a minimum of 12 spare charges always in stock and readily available.
Schedule
A Equipment for Trailer pumps
A Equipment for Trailer pumps
(A) For light trailer pump (120-150 g. p.m.) 30 ft. length of armoured suction hose, with wrenches :
1
Metal suction strainer.
1
Basket strainer.
1
Two-way suction collecting-head.
1
Suction adapter.
10
Seventy-five ft. length of unlined 2-½ inch delivery hose
complete with quick-release couplings.
1
Dividing Breeching piece.
2
Branch pipes with ⅝ inch nozzels.
1
Diffuser Nozzel.
1
Standpipe with blank cap.
1
Hydrant-key.
4
Collapsible canvas buckets.
1
Fire hook (preventer) with cutting edge.
1
C. T. C. Extinguisher 1 /4 gallon capacity;
1
One hundred ft. length of 1 inch manila rope.
1
Thirty ft, extension ladder (where necessary)
1
Heavy axe.
1
Spade.
1
Pick axe.
1
Crowbar.
1
Saw.
1
Hurricane lamp.
1
Electric Torch.
1
Pair Rubber Gloves.
(B) For large trailer pump (350-500 g. p. m.) 30 ft. length of armoured suction hose, with wrenches :
1
Metal strainer.
1
Basket strainer.
1
Three-way suction collecting-head.
1
Suction adapter.
14
Seventy-five ft. lengths of unlined canvas 2-½ inch delivery
hoses complete with quick -release couplings.
1
Dividing breaching piece.
1
Collecting breaching-piece.
4
Breach pipes with one inch, two ¾ inch, and one diffuser
nozzle.
1
Standpipes with blank caps.
2
Hydrant keys.
6
Collapsible canvas buckets.
1
Ceiling hook(prevented) with cutting edge.
1
C.T.C. extinguisher ¼ gallon capacity.
1
Thirty ft. extension ladder (where necessary).
1
Pair Rubber Gloves.
1
Heavy axe.
1
Spade.
1
Pick axe.
1
One Hundred ft. length of 2 inch manila rope.
1
Crowbar.
1
Saw.
2
Hurricane lamps.
1
Electric torch.
Note.- If it appears to the Chief Inspector of Factories that in any factory the provision of breathing apparatus is necessary he may by order in writing require the occupier to provide suitable breathing apparatus in addition to the equipment for light trailer pump or large trailer pump as the case may be.