7. Part of the building.

(b) Plinth - All public buildings shall be plinth to a height of 5 metres above the highest flood level.
Plinth
(c) Superstructure - (i) Burnt brick stones, concrete blocks or similar durable materials shall only be used for superstructure.
Superstructure
(ii) The superstructure shall be anchored solidly to the foundation using enforcing bars, tie rods or other connectors suited to the material. The anchorage should be embedded at least 25 cubic metres into the foundation footing. Such rods shall be 16 millimetre diameter and spaced not more than 2 metres apart as shown in Figure-3 of Appendix-B.
(iii) If the floor is raised off the ground and supported on posts, piers or pilings, the comers shall be anchored to the ground using galvanised steel anchor pipes as shown in Figure-4 of Appendix-B.
(iv) The intersecting walls shall be made continuous by means of tie bars and/or horizontal reinforcement that shall extend into neighbouring walls and partitions as shown in Figure-5 of Appendix-B.
(v) All masonry building shall have bond connecting all load-bearing masonry elements as shown in Figure-6 of Appendix-B.
(d) Roof. - (i) In the case of pitched roof, the slope of roof shall be between 30 degrees and 40 degrees to the horizontal plane.
Roof.
(ii) The roof frame shall be connected with the masonry wall by extending the fastener strap around the roof joint and the ends duly embedded in the concrete or masonry to a depth of 25 cubic metres or braced diagonally with timber brace nailed to wall studs, joint and rafter as shown in Figures-7 and 8 of Appendix-B.
(iii) In the case of pitched roof with tiles, states, asbestos sheets or other light roofing materials, as the case may be, it shall be ensured that the roofing materials, is sufficiently anchored to the roof structure, and the connections shall be checked for the uplift of the roof due to wind or punching as shown in Figure-9 of Appendix-B.
(iv) The regions of the roof like eaves, junction and ridges liable for higher uplift force shall be provided with reinforcing bond as shown in Figure-10 of Appendix-B.
(v) Slots shall be provided at the ridge of large assembly, industrial and godown buildings with pitched roof ventilation as shown in Figure-11 of Appendix-B.
(e) Overhangs. - (i) No overhangs in the pitched roof shall exceed 30 centimetres beyond the outer surface of the wall. The end of the tile or other roofing materials shall be securely fixed at the eaves by means of tile clips nailed to the eave board or rafters as shown in Figure-12 of Appendix-B.
Overhangs.
(ii) No sunshade, balcony or other projections attached to the wall shall project beyond 60 centimetres from the outer surface of the wall. If the projection exceeds 60 centimetres, it shall be designed to prevent uplift due to wind. Continuous sunshade whether board and similar structure shall not be provided with. No sunshade or other projections in the vertical direction shall be permissible.
(f) Parapet. - A parapet wall of not less than 75 centimetres height shall be provided over the outer wall of the building of flat roof.
Parapet.
(g) Opening. - (i) Openings in an outer wall shall be located away from the comer of the building by a clear distance of not less than 8th the height of such opening or 6 metres whichever is higher and they shall be provided with proper shutters which can be securely closed during cyclone.
Opening.
(ii) The horizontal distance between two openings in an outer wall shall not be less than half the height of the larger opening.
(iii) Between two openings, there shall be not less than 75 centimetres measured vertically.
(iv) No vent holes just beneath roof shall be permitted in the outer walls of a building so as to avoid internal pressure.
(v) Windows and ventilators in buildings whose height exceeds 15 metres or four storeys shall be firmly secured to the superstructure. Glazed windows shall be protected width louvers or other means to avoid breakage.
(h) Chimneys and flues. - Chimneys and flues, separated from the main building, shall be constructed to the height exceeding 10 metres by reinforced cement concrete.
Chimneys and flues.
(i) Compound wall. - Compound wall of height more than one metre shall be strengthened by adequate number of plasters at intervals of not more than 3 metres and also be provided with reinforced concrete ties at plinth.
Compound wall.
(j) Staircase. - Staircase, landings, ramps in a multi-storeyed building shall be so designed as to form integral part of the main building and in rub case shall they project beyond the external wall of the building.
Staircase.
(k) Huts and pole type construction. - (i) The foundation shall be firmly connected to the wall or pole as shown in Figure-13 of Appendix-B.
Huts and pole type construction.
(ii) The wall or pole shall be firmly connected with the roof frame shown in Figure-14 of Appendix-B.
(iii) The number of poles in a roof frame shall be firmly secured as shown in Figure-15 of Appendix-B.
Appendix-A
Appendix-A
Source: National Building Code of India, 1970.
Source: National Building Code of India, 1970.
Wind Load
Wind Load
Pressure in kg/m2 up to a zone height of 30
meters above the main retarding surface
Pressure in kg/m2 at height ( in meters ) of
Pressure in kg/m2 at height ( in meters ) of
30
40
45
50
60
70
80
100
120
150
Local bodies as per Schedule Appended in these
rules (vide rules 1.2)
200
208
210
217
222
230
236
244
254
264
276
Note 1. - The relationship between wind pressure and velocity is P: KV/2 where P is the pressure, V the velocity and K is co-efficient which is to be assumed as 0.006. Pressure is expressed in kg/m2 and V in Km/h.
Note 1.
Note 2. - The basic wind pressures indicated above are the maximum ever likely to occur in the respective areas under fully exposed conditions. In the case of mountainous areas, the values indicated above should be modified according to the local conditions (see rule 4).
Note 2.
(a) a building whose height "h" does not exceed twice the effective width;
(b) a portion in between two parts of an adequately stiffened by if the height of that portion does not exceed twice its width and the length of that portion does not exceed four times its width; and
(c) a wing of a building if it does not project more than twice its own width.
SI. No.
SI. No.
Shape (in plan) Plan shape of the structure
Shape (in plan) Plan shape of the structure
Factors
Factors
Ratio of height to base width 0.4
Ratio of height to base width 0.4
Factor ratio of height to base width 4.8
Factor ratio of height to base width 4.8
Ratio of height to base width 8 or over
Ratio of height to base width 8 or over
(1)
(2)
(3)
(4)
(5)
1.
Circular
0.7
0.7
0.7
2.
Octagonal
0.8
0.9
1.0
3.
Square (wind perpendicular to diagonal)
0.8
0.9
1.0
4.
Square (wind perpendicular to face)
1.0
1.15
1.3
Note 1. - In the case of projections above the general roof level, the base width shall be taken as the width of the construction where it rises from the surface of the roof and the height governing the ratio of height to base width shall be that from the roof surface to the top of construction.
Note 1.
Note 2. - The division of wind load into that acting on windward and leeward sides shall be the same as that for rectangular buildings as effected by the openings.
Note 2.
(a) 0.05 p. measured on the plan area of the roof where the direction of wind is normal to the ridge; and
(b) 0.025 p. measured on the total area of roof ignoring openings where the direction of wind is parallel to the ridge;
(c) Where the wind direction is parallel to a wall, the effect of wind drag on the wall may be taken at 0.025 p. measured on the total area of wall ignoring openings.
SI. No.
SI. No.
Slope on roof on wind-ward side (x)
Slope on roof on wind-ward side (x)
External wind pressure
External wind pressure
Windward slope
Windward slope
Leeward slope
Leeward slope
(1)
(1)
(2)
(2)
(3)
(3)
(4)
(4)
1.
0
(-) 1.00 P
(-) 0.50 P
2.
10
(-) 0.70 P
(-) 0.50 P
3.
20
(-) 0.40 P
(-) 0.50 P
4.
30
(-) 0.10 P
(-) 0.50 P
5.
40
(+) 0.10 P
(-) 0.50 P
6.
50
(+) 0.30 P
(-) 0.50 P
7.
60
(+) 0.40 P
(-) 0.50 P
8.
70 to 90
(+) 0.50 P
(-) 0.50 P
Note 1. - In the above Table, plus (+) means an external positive pressure on the roof normal to the surface of the roof and minus (-) means an external suction on the roof normal to the surface of the roof.
Note 1.
Note 2. - Wind pressures for intermediate slopes may be interpolated.
Note 2.
Note 3. - In the case of flat roof, windward slope means windward half of1 the roof and leeward slope means leeward half of the roof.
Note 3.
- 0.6 p. on the both slopes of the roof over a length from the gable end usual to the mean height of the roof from the surrounding ground level; and
- 0.4 p. over the remaining length of the roof on both slopes.