Rule prescribed under sub-section (2) of section 12
Rule prescribed under sub-section (2) of section 12
[17. Disposal of Trade Wastes and Effluents.
[17A. Limits of temperature and air movement.
Schedule
Dry bulb temperature
Wet bulb temperature
°C
°C
30
29.0
31
28.9
32
28.8
33
28.7
34
28.6
35
28.5
36
28.4
37
28.3
38
28.2
39
28.1
40
28.0
41
27.9
42
27.8
43
27.7
44
27.6
45
27.5
46
27.4
47
27.3
Provision of thermometers.
(ii) If the Inspector has reason to believe that a substantial amount of heat is added inside the environment of a work room by radiation from walls, roofs or other solid surroundings, he may serve on the manager of the factory an order requiring him to provide one or more globe thermometers referred to in the first proviso, in sub-rule (1) and further requiring him to place the globe thermometers at places specified by him and keep a record of the temperatures in a suitable register.
Ventilation.
(i) covered by section 15; or
(ii) in which temperature and humidity are controlled by refrigeration;
(iii) where in any factory owing to special circumstances such as situation with respect to adjacent buildings and height of the building with respect to floor space, the requirement of ventilation openings under sub-clause (1) cannot be complied with or in the opinion of the Inspector the temperature of air in a work room is sufficiently high and is likely to exceed the limits prescribed in sub-rule, he may serve on manager of the factory an order requiring him to provide additional ventilation either by means of roof ventilators or by mechanical means;
(iv) amount of fresh air supplied by mechanical means of ventilation in an hour shall be equivalent to at least six times the cubic capacity of the work room and shall be distributed evenly throughout the work room without dead air pockets or undue draughts caused by high inlet velocities;
(v) in regions where in summer (15th March to 15th July) dry bulb temperatures of outside air in the shade during most part of the day exceed 35°C and simultaneous wet bulb temperatures are 25°C or below and in the opinion of the Inspector the manufacturing process carried on in the work room of a factory permits thermal environments with relative humidity of 50% or more, the Inspector may serve on the manager of the factory an order to have sufficient supply of outside air for ventilation cooled by passing it through water sprays either by means of unit type of evaporative air coolers (desert cooler) or, where supply of outside air is provided by mechanical means through ducts in a plenum system, by means of Central air washing plants.]
Rules 18 to 28 prescribed under sub-section (1) of section 15
Rules 18 to 28 prescribed under sub-section (1) of section 15
Section 16A • Rajasthan Factories Rules, 1951
16A. Compound to be kept clean.
rajasthan-factories-rules-1951-sec-16A.json
•
Section 16A
{
"act_title": "Rajasthan Factories Rules, 1951",
"act_slug": "rajasthan-factories-rules-1951",
"section_label": "Section",
"section": {
"number": "16A",
"title": "16A. Compound to be kept clean.",
"chapter": null,
"content": "Rule prescribed under sub-section (2) of section 12\nRule prescribed under sub-section (2) of section 12\n[17. Disposal of Trade Wastes and Effluents.\n[17A. Limits of temperature and air movement.\nSchedule\nDry bulb temperature\nWet bulb temperature\n°C\n°C\n30\n29.0\n31\n28.9\n32\n28.8\n33\n28.7\n34\n28.6\n35\n28.5\n36\n28.4\n37\n28.3\n38\n28.2\n39\n28.1\n40\n28.0\n41\n27.9\n42\n27.8\n43\n27.7\n44\n27.6\n45\n27.5\n46\n27.4\n47\n27.3\nProvision of thermometers.\n(ii) If the Inspector has reason to believe that a substantial amount of heat is added inside the environment of a work room by radiation from walls, roofs or other solid surroundings, he may serve on the manager of the factory an order requiring him to provide one or more globe thermometers referred to in the first proviso, in sub-rule (1) and further requiring him to place the globe thermometers at places specified by him and keep a record of the temperatures in a suitable register.\nVentilation.\n(i) covered by section 15; or\n(ii) in which temperature and humidity are controlled by refrigeration;\n(iii) where in any factory owing to special circumstances such as situation with respect to adjacent buildings and height of the building with respect to floor space, the requirement of ventilation openings under sub-clause (1) cannot be complied with or in the opinion of the Inspector the temperature of air in a work room is sufficiently high and is likely to exceed the limits prescribed in sub-rule, he may serve on manager of the factory an order requiring him to provide additional ventilation either by means of roof ventilators or by mechanical means;\n(iv) amount of fresh air supplied by mechanical means of ventilation in an hour shall be equivalent to at least six times the cubic capacity of the work room and shall be distributed evenly throughout the work room without dead air pockets or undue draughts caused by high inlet velocities;\n(v) in regions where in summer (15th March to 15th July) dry bulb temperatures of outside air in the shade during most part of the day exceed 35°C and simultaneous wet bulb temperatures are 25°C or below and in the opinion of the Inspector the manufacturing process carried on in the work room of a factory permits thermal environments with relative humidity of 50% or more, the Inspector may serve on the manager of the factory an order to have sufficient supply of outside air for ventilation cooled by passing it through water sprays either by means of unit type of evaporative air coolers (desert cooler) or, where supply of outside air is provided by mechanical means through ducts in a plenum system, by means of Central air washing plants.]\nRules 18 to 28 prescribed under sub-section (1) of section 15\nRules 18 to 28 prescribed under sub-section (1) of section 15",
"footnote": "",
"is_definition": false,
"sort_order": 26
},
"prev_section": "16",
"next_section": "18"
}