(a) by the use of steam during any period when the dry bulb temperature of that room exceeds 85 degrees:
(b) at any time when the wet bulb reading of the hygrometer is higher than that specified in the following Schedule in relation to the dry bulb reading of the hygrometer at that time; or as regards a dry bulb reading intermediate between any two dry bulb readings indicated consecutively in the Schedule when the dry bulb reading does not exceed the wet bulb reading to the extent indicated in relation to the lower or of these two dry bulb readings:-
Dry bulb
Dry bulb
Wet bulb
Wet bulb
Dry bulb
Dry bulb
Wet bulb
Wet bulb
Dry bulb
Dry bulb
Wet bulb
Wet bulb
60.0
58.0
77.0
75.0
94.0
86.0
61.0
59.0
78.0
76.0
95.0
87.0
62.0
60.0
79.0
77.0
96.0
87.5
63.0
61.0
80.0
78.0
97.0
88.0
64.0
62.0
81.0
79.0
98.0
88.5
65.0
63.0
82.0
80.0
99.0
89.0
66.0
64.0
83.0
80.5
100.0
89.5
67.0
65.0
84.0
81.0
101.0
90.0
68.0
66.0
85.0
82.0
102.0
90.0
69.0
67.0
86.2
82.5
103.0
90.5
70.0
68.0
87.0
83.0
104.0
90.5
71.0
69.0
88.0
83.5
105.0
91.0
72.0
70.0
89.0
84.0
106.0
91.0
73.0
71.0
90.0
84.5
107.0
91.5
74.0
72.0
91.0
85.0
108.0
91.5
75.0
73.0
92.0
85.5
109.0
92.0
76.0
74.0
93.0
86.0
110.0
92.0
Section 23 • Maharashtra Factories Rules, 1963
23. When artificial humidification not allowed.
maharashtra-factories-rules-1963-sec-23.json
•
Section 23
{
"act_title": "Maharashtra Factories Rules, 1963",
"act_slug": "maharashtra-factories-rules-1963",
"section_label": "Section",
"section": {
"number": "23",
"title": "23. When artificial humidification not allowed.",
"chapter": null,
"content": "(a) by the use of steam during any period when the dry bulb temperature of that room exceeds 85 degrees:\n(b) at any time when the wet bulb reading of the hygrometer is higher than that specified in the following Schedule in relation to the dry bulb reading of the hygrometer at that time; or as regards a dry bulb reading intermediate between any two dry bulb readings indicated consecutively in the Schedule when the dry bulb reading does not exceed the wet bulb reading to the extent indicated in relation to the lower or of these two dry bulb readings:-\nDry bulb\nDry bulb\nWet bulb\nWet bulb\nDry bulb\nDry bulb\nWet bulb\nWet bulb\nDry bulb\nDry bulb\nWet bulb\nWet bulb\n60.0\n58.0\n77.0\n75.0\n94.0\n86.0\n61.0\n59.0\n78.0\n76.0\n95.0\n87.0\n62.0\n60.0\n79.0\n77.0\n96.0\n87.5\n63.0\n61.0\n80.0\n78.0\n97.0\n88.0\n64.0\n62.0\n81.0\n79.0\n98.0\n88.5\n65.0\n63.0\n82.0\n80.0\n99.0\n89.0\n66.0\n64.0\n83.0\n80.5\n100.0\n89.5\n67.0\n65.0\n84.0\n81.0\n101.0\n90.0\n68.0\n66.0\n85.0\n82.0\n102.0\n90.0\n69.0\n67.0\n86.2\n82.5\n103.0\n90.5\n70.0\n68.0\n87.0\n83.0\n104.0\n90.5\n71.0\n69.0\n88.0\n83.5\n105.0\n91.0\n72.0\n70.0\n89.0\n84.0\n106.0\n91.0\n73.0\n71.0\n90.0\n84.5\n107.0\n91.5\n74.0\n72.0\n91.0\n85.0\n108.0\n91.5\n75.0\n73.0\n92.0\n85.5\n109.0\n92.0\n76.0\n74.0\n93.0\n86.0\n110.0\n92.0",
"footnote": "",
"is_definition": false,
"sort_order": 20
},
"prev_section": "22",
"next_section": "24"
}