79. Fire.

[(a) All process, storages, equipments, plants etc. involving serious explosion and flash fire hazard shall be located in segregated buildings where the equipment shall be so arranged that only a minimum number of employees are exposed to such hazards at any time.]
(b) All industrial processes involving serious fire hazard shall be located in buildings or work places separated from one another by walls of fire-resistant construction.
(c) Equipment and plant involving serious fire or flash fire hazard shall, wherever possible, be so constructed and installed that in case of fire, they can be easily isolated.
[(d) Ventilation ducts, pneumatic conveyors and similar equipment involving various fire risk should be provided with flame-arresting or automatic fire extinguishing appliances or fire resisting dampers electrically inter located with heat sensitive smoke detectors and air conditioning plant system.]
[(e) In all work places having serious fire or flash fire hazards, passages between machines installations or piles of material should be at least 90cm.wide. For storage piles, the clearance between the ceiling and the top of the pile should not be less than 2 metres]
[(b) doors and window openings shall be located in suitable positions on all external walls of the building to provide easy access to the entire area within the building for firefighting] .
(i) buildings in which explosive or highly flammable substances are manufactured, used, handled or stored;
(ii) storage tanks containing oils, paints or other flammable liquids;
(iii) grain elevators; and
(iv) buildings, tall chimneys or stacks where flammable gases, fumes, dust or lint are likely to be present.
[(v) sub-station buildings and out-door transformers and switch yard.]
(a) all electrical apparatus shall either be excluded from the area of risk or they shall be of such construction and so installed and maintained as to prevent the danger of their being a source of ignition;
(b) effective measures shall be adopted for prevention of accumulation of static charges to a dangerous extent;
(c) workers shall wear shoes without iron or steel nails or any other exposed ferrous materials which is likely to cause sparks by friction;
(d) smoking, lighting or carrying matches ,lighters or smoking materials shall be prohibited.
(e) transmission belts with iron fasteners shall not be used; and
(f) all other precautions, as are reasonably-practicable, shall be taken to prevent initiation of ignition from all other possible sources such as open flames, frictional sparks overheated surfaces of machinery or plant, chemical or physical-chemical reaction and radiant heat.
(b) Flammable liquids shall be stored in closed containers and in limited quantities in well ventilated rooms of fire resisting construction which are isolated from the remainder of the building by fire walls and self closing fire doors.
(c) Large quantities of such liquids shall be stored in isolated and adequately ventilated building of fire resisting construction or in storage tanks, preferably underground and at distance from any building as required in the Petroleum Rules, 1976.
(d) Effective steps shall be taken to prevent leakage of such liquids into basements, sumps or drains and to confine any escaping liquid within safe limits.
(a) Effective steps shall be taken for removal or prevention of the accumulation in the air of flammable dust, gas, fume or vapor to an extent which is likely to be dangerous.
(b) No waste materials of a flammable nature shall be permitted to accumulate on the floors and shall be removed at least once in a day or shift, and more often, when possible. Such materials shall be placed in suitable metal containers with covers wherever possible.
(i) "horizontal exit" means an arrangement which allows alternative egress from a floor area to another floor at or near the same level in an adjoining building or an adjoining part of the same building with adequate separation ; and
(ii) "travel distance" means the distance an occupant has to travel to reach an exit.
(b) An exit may be a doorway, corridor, passageway to an internal or external stairway or to a verandah. An exit may also include a horizontal exit leading to an adjoining building at the same level.
[(c) The number and types of first-aid firefighting equipment to be provided for light hazard occupancy shall be as given in Schedule I. For the ordinary hazard or extra hazard occupancies, equipment as given in sub-rule 12 shall be provided in addition to that given in Schedule I.]
(d) In every room of a factory exits sufficient to permit safe escape of the occupants in case of fire or other emergency shall be provided which shall be free of any obstruction.
(e) The exits shall be clearly visible and suitably illuminated with suitable arrangement, whatever artificial lighting is to be adopted for this purpose, to maintain the required illumination in case of failure of the normal source of electric supply.
(f) The exits shall be marked in a language understood by the majority of the workers.
(g) Fire resisting doors or roller shutters shall be provided at appropriate places along the escape routes to prevent spread of fire and smoke, particularly at the entrance of lifts or stairs where funnel or flue effect may be created inducing an upward spread of fire.
(h) All exits shall provide continuous means of egress to the exterior of a building or to an exterior open space leading to a street.
(i) Exits shall be so located that the travel distance on the floor shall not exceed 30 metres.
(j) In case of those factories where high hazard materials are stored or used, the travel distance to the exit shall not exceed 22.5 metres and there shall be at least two ways of escape from every room, however small, except toilet rooms, so located that the points of access thereto are out of or suitably shielded from areas of high hazard.
(k) Wherever more than one exit is required for any room space or floor, exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in separate directions from any point in the area served.
(l) The unit of exit width used to measure capacity of any exit shall be 50cm. A clear width of 25cm. shall be counted as an additional half unit. Clear width of less than 25cm. shall not be counted for exit width.
(m) Occupants per unit width shall be 50 for stairs and 75 for doors.
(n) For determining the exits required, the occupant load shall be reckoned on the basis of actual number of occupants within any floor area or 10 square metres per person, whichever is more.
(o) There shall not be less than two exits serving every floor area above and below the ground floor and at least one of them shall be an internal enclosed stairway.
(p) For every building or structure used for storage only, and every section thereof considered separately, shall have access to at least one exit so arranged and located as to provide a suitably means of escape for any person employed therein, and in any such room wherein more than 10 persons may be normally present, at least two separate means of exit shall be available, as remote from each other as practicable.
(q) Every storage area shall have access to at least one means of exit which can be readily opened.
(r) Every exit doorway shall open into an enclosed stairway, a horizontal exit on a corridor or passageway providing continuous and protected means of egress.
(s) No exit doorway shall be less than 100cm. in width. Doorways shall be not less than 200cm. in height.
(t) Exit doorways shall open outwards, that is, away from the room, but shall not obstruct the travel along any exit. No doors when opened shall reduce the required width of stairway or landing to less than 90cm. Over head or sliding doors shall not be installed for this purpose.
(u) An exit door shall not open immediately upon a flight of stairs. A landing equal to at least the width of the doorway shall be provided in the stairway at each doorway. The level of landing shall be the same as that of the floor which it serves.
(v) The Exit doorways shall be open able from the side which they serve without the use of a key.
(w) Exit for corridors and passageways shall be of width not less than the aggregate required width of exit doorways leading from there in the direction of travel to the exterior.
(x) Where stairways discharge though corridors and passageways, the height of the corridors and pass age ways shall not be less than 2.4 metres.
(y) Internal stairs shall be constructed of non-combustible materials throughout.
(z) Internal stairs shall be constructed as a self-contained unit width at least one side adjacent to an external wall and shall be completely enclosed.
(aa) A staircase shall not be arranged round a lift shaft unless the latter is totally enclosed by a material having a fire-resistance rating not lower than that of the type of construction of the former.
(bb) Hollow combustible construction shall not be permitted.
(cc) The minimum width of an internal staircase shall be 100cm.
(dd) The minimum width of treads without nosing shall be 25cm. For an internal staircase. The threads shall be constructed and maintained in a manner to prevent slipping.
(ee) The maximum height of a riser shall be 19cm. and the number of risers shall be limited to 12 per flight.
(ff) Hand rails shall be provided with a minimum height of 100cm. and shall be firmly supported.
(gg) The use of spiral staircase shall be limited to low occupant load and to a building of height of 9 metres, unless they are connected to platforms such as balconies and terraces to allow escapes to pause. A spiral staircase shall be not less than 300 cm. in diameter and have adequate head room.
(hh) The width of a horizontal exit shall be same as for the exit doorways.
(ii) The horizontal exit shall be equipped with at least one fire door or self closing type.
(jj) The floor area on the opposite or refuge side of a horizontal exit shall be sufficient to accommodate occupants of the floor areas served, allowing not less than 0.3 square metre per person. The refuge area shall be provided with exits adequate to meet the requirements of this sub-rule. At least one of the exits shall lead directly to the exterior or street.
(kk) Where there is difference in level between connected areas for horizontal exit, ramps not more than 1 in 8 slope shall be provided. For this purpose steps shall not be used.
(ll) Doors in horizontal exits shall be open able at all times.
(mm)Ramps with a slope of not more than 1 in 10 may be substituted for the requirements of staircase. For all slopes exceeding 1 in 10 and wherever the use is such as to involve danger of slipping, the ramp shall be surfaced with non-slipping materials.
(nn) In any building not provided with automatic fire alarm a manual fire alarm system shall be provided if the total capacity of the building is over 500 persons, or if more than 25 persons are employed above or below the ground floor, except that no manual fire alarm shall be required in one-storey buildings where the entire area is undivided and all parts thereof are clearly visible to all occupants.
(b) The types of first aid firefighting equipment to be provided shall be determined by considering the different types of fire risks which are classified as follows, namely:-
(1) "Class A fire" - Fire due to combustible materials such as wood, textiles, paper, rubbish and the like.
(i) "Light hazard" - Occupancies like offices, assembly halls, canteens, rest-rooms, ambulance rooms and the like;
(ii) "Ordinary hazard" - Occupancies like saw mills, carpentry shops, small timber yards, book binding shops, engineering workshop and the like.
(iii) "Extra hazards" - Occupancies like large timber yards, godowns storing fibrous materials flour mills, cotton mills, jute mills, large wood working factories and the like;
(2) "Class B Fire" - Fire in flammable liquids like oil, petroleum products, solvents, grease, paint, etc.,
(3) "Class C Fire" - Fire arising out of gaseous substances.
(4)"Class D Fire" - Fire from reactive chemicals, active metals and the like.
(5) "Class E Fire" - Fire involving electrical equipment and delicate machinery and the like.
(c) The number and types of first-aid fire fighting equipments to be provided shall be as per the following scale:
(1) Class A fire -
(i) Light hazard- One 9 litre water bucket for every 100 square metres of floor area or part thereof and one 9 litre watery type (soda-acid or gas pressure or bucket pump) extinguisher shall be provided for each 6 buckets or part thereof with a minimum of one extinguisher and two buckets per compartment of the building. These equipment shall be so distributed over the entire floor areas that a person shall have to travel not more than 25 meters for any point to reach the nearest equipment.
(ii) Ordinary hazard- One 9 litre water bucket for every 100 square metres of floor area or part thereof and one 9 litre water type (soda-acid or gas pressure or buckets pumps) extinguisher shall be provided for each six buckets or part thereof with a minimum of two extinguishers and four buckets per compartment of the building. These equipment shall be so distributed over the entire floor areas that a person shall have to travel not more than 15 meters from any point to reach the nearest equipments.
(iii)Extra hazard- The scale of equipment would be what is prescribed for ordinary hazard and, in addition such extra equipment as, in the opinion of the Inspector, are necessary, having regard to the special nature of occupancy:
(2) Class B Fire- There shall be at least one fire extinguisher either, foam type or carbon dioxide or dry powder type per 50 square meters of floor area and shall be so distributed that no person is required to travel more than 15 metres from any point to reach the nearest equipment. In addition to the requirements extinguishers specified here, requirements as laid down in clause (1) shall also be provided.
(3) Class C Fire- Carbon dioxide or dry chemical powder extinguishers shall be provided near each plant or groups of plants.
(4) Class D Fire- Special dry powder (chloride based) type of extinguishers or sand buckets shall be provided on a scale as laid down for class B fire. The Inspector may require a higher scale of portable equipment to be provided depending upon the risk involved.
(5) Class E Fire- Carbon dioxide or dry powder type extinguishers shall be provided near each plants or group of plants depending upon the risk involved.
(d) The first-aid fire fighting equipments shall confirm to the relevant Indian Standards.
(e) As far as possible the first-aid firefighting equipment shall all be similar in shape and appearance and shall have the same methods of operation.
(f) All first-aid firefighting equipment shall be placed in a conspicuous position and shall be readily and easily accessible for immediate use. Generally, these equipments shall be placed as near as possible to the exits or stair landing or normal routs of escape.
(g) All water buckets and bucket pump type extinguishers shall be filled with clean water. All sand buckets shall be filled with clean, dry and fine sand.
(h) All other extinguishers shall be charged appropriately in accordance with the instructions of the manufacturer.
(i) Each first-aid firefighting equipment shall be allotted a serial number by which it shall be referred to in the records. The following details shall be painted with the white paint on the body of each equipment namely :
(1) serial number;
(2) date of last refilling; and
(3) date of last inspection.
(j) First-aid firefighting equipment shall be placed on platforms or in cabinets in such a way that their bottom is 750mm. above the floor level. Fire bucket shall be placed on hooks attached to a suitable stand or wall in such a way that their bottom 750mm. above the floor level. Such equipment if placed outside the building shall be under sheds or covers.
(k) All extinguishers shall be thoroughly cleaned and recharged immediately after discharge. Sufficient refill material shall be kept readily available for this purpose at all times.
(l) All first-aid fire fighting equipments shall be subject to routine maintenance, inspection and testing to be carried out by properly trained persons. Periodicity of the routine maintenance, inspection and the test shall confirm to the relevant Indian Standards.
Note. - In the above formula in this clause -
Note.
A = the total area in square metres of all floors including galleries in all buildings of the factory;
B = the total area in square metres of all floors and galleries including open spaces in which combustible materials are handled or stored;
C = the total area in square metres of all floors over 15 metres above ground level; and
D = the total area in square metres of all floors of all buildings other than those of fire resisting construction.
(b) Each trailer pump shall be provided with equipment as per Schedule appended to this rule. Such equipment, shall confirm to the relevant Indian Standard.
(c) Trailer pumps shall be housed in a separate shed or sheds which shall be sited closed to a principal source of water supplies in the vicinity of the main risk of the factory.
(d) In factories where the area is such as cannot be reached by man hauling of trailer pumps within reasonable time vehicle with towing attachment shall be provided at the scale of one for every four trailer pumps with a minimum one such vehicle kept available at all times.
(e) Water supply shall be provided to give flow of water as required under clause (a) for at least 100 minutes. At least 50 per cent of water supply of 450,000 litres whichever is less, shall in the form of static tanks of adequate capacities (not less than 450,000 litres each) distributed round the factory with due regard to the potential fire risks in the factory. Where piped supply is provided, the size of the main shall not be less than 15cm. diameter and it shall be capable of supplying a minimum of 4500 litres per minute at a pressure of not less than 7 kg. per square centimeter.
(f) All trailer pumps including the equipment provided with them and the vehicles for towing them shall be maintained in good conditions and subjected to periodical inspections and testing as required.
(b) Sufficient number of person shall be trained in a proper handling of firefighting equipment as referred to in clause (a) and their use against the types of fire for which they are intended to ensure adequate number of persons is available for firefighting both by means of first-aid firefighting equipment and others. Wherever vehicles with towing attachment are to be provided as required in clause (d) of sub-rule (12) sufficient number of persons shall be trained in driving those vehicles to ensure that trained persons are available for driving them whenever the need arises.
(c) Fire fighting drills shall be held at least once in every three months.
[Schedule I]
First Aid Fire Fighting Equipments
First Aid Fire Fighting Equipments
Class of Fire
Class of Fire
Suitable type of Appliances
Suitable type of Appliances
A. Fires in ordinary combustibles (wood,
vegetable fibres, paper & the like)
Chemical Extinguishers of soda, acid
Gas/expelled water and antifreeze types and water buckets.
B. Fires inflammable liquids, paints, grease,
solvents and the like
Chemical Extinguishers of foam, Carbon dioxide
and dry powder types and sand buckets.
C. Fires in gaseous substances under pressure
Chemical Extinguishers of carbon dioxide and dry
powder types
D. Fires in Reactive Chemicals active metals and
the like
Special type of dry powder extinguishers and
sand buckets.
E. Fires in electrical equipments and dry powder
type and sand buckets
Chemical extinguishers of carbon dioxide
Buckets of water
Water type Extinguishers For each 9 Ltrs (or 2
gallons extinguishers)
Acceptable Replacement
For one bucket
For three buckets
Dry sand
1 bucket
3 buckets
Carbon dioxide
3Kg
9Kg (In not less than 2 Extinguishers
extinguishers)
9Kg
Dry powder
2Kg
5Kg (In one or more Extinguishers)
5Kg
Foam extinguishers
9 litrs
9 litrs
9 litrs
(a) For rooms containing electrical transformers, switch gears motors and/ or other electrical apparatus only, not less than two Kg. Dry powder or Carbon Dioxide type extinguishers shall be provided within 15m. of the apparatus.
(b) Where motors and/or other electrical equipment are installed in rooms other than those containing such equipment only one 5 Kg. Dry powder or Carbon dioxide Extinguisher shall be installed within 15m. of such equipment in addition to the requirement mentioned at (3) and (4) above. For this purpose the same extinguisher may be deemed to afford protection to all apparatus within 15m. thereof.
(c) Where electrical motors are installed on platforms, one 2 kg. Dry powder or Carbon dioxide type extinguisher shall be provided on or below each platform. In case of a long platform with a number of metres one extinguisher shall be acceptable as adequate for every 3 metres on the common platform. The above requirements will be in addition to the requirements mentioned at item (3) and (4) above.
(a) While selecting sites for first aid fire fighting equipments, due consideration shall be given to the nature of the risk to be covered. The equipments shall be placed in conspicuous position and shall be readily accessible for immediate use in all parts of the occupancy. It should always be borne in mind while selecting sites that first aid fire fighting equipments are intended only for use on incipient fires and their value may be negligible if the fire is not extinguished or brought under control in the early stages.
(b) Buckets and extinguishers shall be placed at convenient and easily accessible locations either on hangers or on stands in such a way that their bottom is 750 mm above the floor level.
[Schedule II]
Equipments To Be Provided With Trailer Pump
Equipments To Be Provided With Trailer Pump
For light trailer pump of a capacity of 680 litres/minute
For light trailer pump of a capacity of 680 litres/minute
1 Armoured suction hose of 9 metres length, with wrenches.
1 Metal suction strainer.
1 Basket strainer.
1 Two-way suction collecting-head
1 Suction adaptor.
10 Unlined or rubber lined 70mm. delivery hose of 25 metres length complete with quick-release coupling.
1 Dividing breaching-piece
2 Branch -piece with 15 mm. nozzles.
1 Diffuser nozzle.
1 Stand pipe with blank cap.
1 Hydrant key.
4 Collapsible canvas buckets
1 Fire hook (preventor) with cutting edge.
1 25mm. manila rope of 30 metres length.
1 Extension ladder of 9 metres length (where necessary)
1 Heavy axe.
1 Spade.
1 Pick axe.
1 Crowbar.
1 saw.
1 Hurricane lamp.
1 Electric torch.
1 Pair rubber gloves
For large trailor pump of a capacity 1800 litres/minute
1 Armoured suction hose of 9 metres length, with wrenches.
1 Metal strainer.
1 Basket strainer.
1 Three-way suction collecting head.
1 Suction adopter.
14 Unlined or rubber lined 70mm. delivery hose of 25 metres length complete with quick release couplings.
1 Dividing breaching-piece
1 Collecting breaching-piece
4 Branch pipes with one 25mm. two 20mm and one diffuser nozzles.
2 Standpipe with blank caps.
2 Hydrant keys.
6 Collapsible canvas buckets.
1 Ceiling hook (preventor) with cutting edge.
1 50mm manila rope of 30 metres length.
1 Extension ladder of 9 metres length (where necessary)
1 Heavy axe.
1 Spade.
1 Pick axe
1 Crowbar
1 Saw.
1 Hurricane lamp.
1 Electric torch.
1 Pair rubber gloves.
Note. - If it appears to the Chief Inspector of Factories that in any factory the provision of breathing apparatus is necessary he may by order in writing require the occupier to provide suitable breathing apparatus in addition to the equipment for light trailer pump or large trailer pump as the case may be.
Note.