Table - IV
Table - IV
Height of building( in meters)
Height of building( in meters)
Minimum abutting road width required ( in
meters)
Minimum abutting road width required ( in
meters)
Minimum alround open space on remaining sides
(in meters) *
Minimum alround open space on remaining sides
(in meters) *
(1)
(1)
(2)
(2)
(3)
(3)
Up to 21
Above 21 & up to
24
Above 24 & up to
27
Above 27 & up to 30
12
12
18
18
7
8
9
10
(i) The abutting road has to be black-topped with minimum 2-lane carriageway. Service roads where required as per these Rules shall be minimum 7 meters wide with minimum 2-lane black topped carriageway.
(ii) For upper floors from 2nd floor onwards, the balcony projection of up to 2 meters may be allowed projecting onto the open spaces.
(iii) The open space to be left between two blocks shall be equivalent to the open space mentioned in Column (3) of above Table IV.
(iv) It is permitted to transfer upto two meters of setback from one side to the other side, which needs to be uniform at any given point, subject to maintaining of minimum setback of 7 meters on all sides.
(v) Where the lighting and ventilation of a building is through the means of a chowk or inner courtyard or interior open space/duct, such open space shall be open to sky and of area at least 25 sq. meters and no side shall be less than 3 meters.
(a) For podium, i.e., Ground plus first floor: all-round setbacks shall be 7 meters all-round
(b) For the Tower block: The coverage and alround setbacks shall be minimum 50 % of the Podium Block, and shall be at least 3metersfrom the Podium edge on all sides,
(c) the fire safety and fire escape measures for the Tower Block shall be independent of the Podium Block.
(a)
At ground level
:
minimum 9 meters all round open space for the
first five floors
(b)
At upper floors
:
increase of 3 meters all round open space or
more, for every 5 upper floors or 15 meters height or part
thereof, over and above the ground level open space of minimum 9
mt.
(a) In every high rise building site, an organised open space which shall be utilised as greenery, tot lot or soft landscaping, etc. shall be provided over and above the mandatory open spaces to be left in and around the building.
This space shall be at least 10% of total site area and shall be of regular shape with a minimum width of 2 Meters. This may be in one or more pockets and shall be open to sky.
(b) In addition to the above, a minimum 2 meter wide green planting strip in the periphery on all sides within the setbacks are required to be developed and maintained in all high rise building sites.
(c) Rain water harvesting structures shall be provided in the prescribed manner within the setbacks.
(i) The building requirements and standards other than heights and setbacks specified in the National Building Code, 2005 shall be complied with.
(ii) Such buildings shall be undertaken by owners by engaging registered architect, licenced builders/developers and licenced structural engineers. The designs and building plans shall be countersigned by the owner, licenced developer, registered architect, licenced engineer and a qualified & licenced structural Engineer who shall be responsible for the supervision, structural safety, fire & life safety and specifications compliance of such buildings. Buildings shall be designed for compliance with earth quake resistance and resisting other natural hazards.
(iii) The Completion Certificate issued by the registered architect and licenced engineer and structural engineer shall certify that the norms have been followed in the design and construction of buildings for making the buildings resistant to earthquake, compliance with structural safety, fire and life safety requirements, and that the building is constructed in accordance with the sanctioned drawings.
(iv) The work of the building services like sanitation, plumbing, fire & life safety requirements, lifts, electrical installations, and other utility services shall be executed under the planning, design and supervision of qualified and competent technical personnel.
(v) In addition to the required staircases and lifts, there shall be at least one fire escape staircase and lift. These lifts shall be got certified from the manufacturer's authorised Service technical personnel from time to time.
(vi) Provision for power generator shall be made in all high-rise buildings.
(vii) All high-rise buildings shall be planned, designed and constructed to ensure fire & life safety requirements are met and maintained and shall comply in accordance with the Fire Protection Requirements of National Building Code of India.
(viii) The facilities for providing fire protection and fire fighting facilities in such buildings should be in compliance with the stipulations laid down and clearance issued by the Fire Department from time to time. NOC from the Fire Department shall be obtained from time to time regarding the fire safety requirements , equipment and facilities installed. The designs and installations regarding fire protection and safety measures including exit requirements and smoke containment and smoke management measures shall be undertaken through a fire engineer/ fire consultant.
(ix) The parking requirements shall comply as given in these rules. The parking facilities and vehicles driveways etc. shall be maintained to the satisfaction of the sanctioning Authority.
(x) All high-rise buildings shall be provided with solar water heating system in the building and solar lighting in the site for outdoor lighting, etc. and give a bank guarantee to this effect to the sanctioning authority for compliance of the same.
(xi) All high-rise public and semi-public buildings/ Assembly buildings/ Commercial complexes and such other public congregation buildings shall be designed and constructed to provide facilities to the physically handicapped persons and elderly persons as prescribed in the National Building Code of India,2005.
(xii) In all high rise buildings, the requirements of parts of the building like size and area requirements of habitable rooms, kitchen, bathrooms and Water closets, corridor and staircase widths, service ducts, and other areas shall be designed and conform to the provisions of the National Building Code of India.
(xiii) All environmental aspects like provision of Rain water harvesting structures, greenery, solar heating and area lighting systems, Andhra Pradesh Water, Land and Tree Act provisions, etc., shall be complied with.
Section 9 • Andhra Pradesh Municipalities Development Control Rules, 2008
9. Requirements For High Rise Buildings.
andhra-pradesh-municipalities-development-control-rules-2008-sec-9.json
•
Section 9
{
"act_title": "Andhra Pradesh Municipalities Development Control Rules, 2008",
"act_slug": "andhra-pradesh-municipalities-development-control-rules-2008",
"section_label": "Section",
"section": {
"number": "9",
"title": "9. Requirements For High Rise Buildings.",
"chapter": null,
"content": "Table - IV\nTable - IV\nHeight of building( in meters)\nHeight of building( in meters)\nMinimum abutting road width required ( in\n\t\t\t\tmeters)\nMinimum abutting road width required ( in\n\t\t\t\tmeters)\nMinimum alround open space on remaining sides\n\t\t\t\t(in meters) *\nMinimum alround open space on remaining sides\n\t\t\t\t(in meters) *\n(1)\n(1)\n(2)\n(2)\n(3)\n(3)\nUp to 21\nAbove 21 & up to\n\t\t\t\t24\nAbove 24 & up to\n\t\t\t\t27\nAbove 27 & up to 30\n12\n12\n18\n18\n7\n8\n9\n10\n(i) The abutting road has to be black-topped with minimum 2-lane carriageway. Service roads where required as per these Rules shall be minimum 7 meters wide with minimum 2-lane black topped carriageway.\n(ii) For upper floors from 2nd floor onwards, the balcony projection of up to 2 meters may be allowed projecting onto the open spaces.\n(iii) The open space to be left between two blocks shall be equivalent to the open space mentioned in Column (3) of above Table IV.\n(iv) It is permitted to transfer upto two meters of setback from one side to the other side, which needs to be uniform at any given point, subject to maintaining of minimum setback of 7 meters on all sides.\n(v) Where the lighting and ventilation of a building is through the means of a chowk or inner courtyard or interior open space/duct, such open space shall be open to sky and of area at least 25 sq. meters and no side shall be less than 3 meters.\n(a) For podium, i.e., Ground plus first floor: all-round setbacks shall be 7 meters all-round\n(b) For the Tower block: The coverage and alround setbacks shall be minimum 50 % of the Podium Block, and shall be at least 3metersfrom the Podium edge on all sides,\n(c) the fire safety and fire escape measures for the Tower Block shall be independent of the Podium Block.\n(a)\nAt ground level\n:\nminimum 9 meters all round open space for the\n\t\t\t\tfirst five floors\n(b)\nAt upper floors\n:\nincrease of 3 meters all round open space or\n\t\t\t\tmore, for every 5 upper floors or 15 meters height or part\n\t\t\t\tthereof, over and above the ground level open space of minimum 9\n\t\t\t\tmt.\n(a) In every high rise building site, an organised open space which shall be utilised as greenery, tot lot or soft landscaping, etc. shall be provided over and above the mandatory open spaces to be left in and around the building.\nThis space shall be at least 10% of total site area and shall be of regular shape with a minimum width of 2 Meters. This may be in one or more pockets and shall be open to sky.\n(b) In addition to the above, a minimum 2 meter wide green planting strip in the periphery on all sides within the setbacks are required to be developed and maintained in all high rise building sites.\n(c) Rain water harvesting structures shall be provided in the prescribed manner within the setbacks.\n(i) The building requirements and standards other than heights and setbacks specified in the National Building Code, 2005 shall be complied with.\n(ii) Such buildings shall be undertaken by owners by engaging registered architect, licenced builders/developers and licenced structural engineers. The designs and building plans shall be countersigned by the owner, licenced developer, registered architect, licenced engineer and a qualified & licenced structural Engineer who shall be responsible for the supervision, structural safety, fire & life safety and specifications compliance of such buildings. Buildings shall be designed for compliance with earth quake resistance and resisting other natural hazards.\n(iii) The Completion Certificate issued by the registered architect and licenced engineer and structural engineer shall certify that the norms have been followed in the design and construction of buildings for making the buildings resistant to earthquake, compliance with structural safety, fire and life safety requirements, and that the building is constructed in accordance with the sanctioned drawings.\n(iv) The work of the building services like sanitation, plumbing, fire & life safety requirements, lifts, electrical installations, and other utility services shall be executed under the planning, design and supervision of qualified and competent technical personnel.\n(v) In addition to the required staircases and lifts, there shall be at least one fire escape staircase and lift. These lifts shall be got certified from the manufacturer's authorised Service technical personnel from time to time.\n(vi) Provision for power generator shall be made in all high-rise buildings.\n(vii) All high-rise buildings shall be planned, designed and constructed to ensure fire & life safety requirements are met and maintained and shall comply in accordance with the Fire Protection Requirements of National Building Code of India.\n(viii) The facilities for providing fire protection and fire fighting facilities in such buildings should be in compliance with the stipulations laid down and clearance issued by the Fire Department from time to time. NOC from the Fire Department shall be obtained from time to time regarding the fire safety requirements , equipment and facilities installed. The designs and installations regarding fire protection and safety measures including exit requirements and smoke containment and smoke management measures shall be undertaken through a fire engineer/ fire consultant.\n(ix) The parking requirements shall comply as given in these rules. The parking facilities and vehicles driveways etc. shall be maintained to the satisfaction of the sanctioning Authority.\n(x) All high-rise buildings shall be provided with solar water heating system in the building and solar lighting in the site for outdoor lighting, etc. and give a bank guarantee to this effect to the sanctioning authority for compliance of the same.\n(xi) All high-rise public and semi-public buildings/ Assembly buildings/ Commercial complexes and such other public congregation buildings shall be designed and constructed to provide facilities to the physically handicapped persons and elderly persons as prescribed in the National Building Code of India,2005.\n(xii) In all high rise buildings, the requirements of parts of the building like size and area requirements of habitable rooms, kitchen, bathrooms and Water closets, corridor and staircase widths, service ducts, and other areas shall be designed and conform to the provisions of the National Building Code of India.\n(xiii) All environmental aspects like provision of Rain water harvesting structures, greenery, solar heating and area lighting systems, Andhra Pradesh Water, Land and Tree Act provisions, etc., shall be complied with.",
"footnote": "",
"is_definition": false,
"sort_order": 7
},
"prev_section": "8",
"next_section": "10"
}