Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007
Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007
Sections
1. Short title and Commencement.
Section 12. Definitions.
Section 23. Objective.
Section 34. Standards of Performance.
Section 45. Phasing of Implementation.
Section 56. Reporting Requirement and Compliance.
Section 67. Miscellaneous.
Section 72. For compilation of monthly report at circle level base data of sub-stations shall be used.
Section 23. The consolidated report for whole State Transmission Utility/Transmission Licensee shall be based on circle-wise compilation.
Section 34. The circle-wise compilation and base data at sub-station level may be subject to Commission scrutiny as may be necessary.
Section 4
andhra-pradesh-electricity-regulatory-commission-transmission-standards-of-performance-regulation-2007.json
•
10 Sections
•
Andhra Pradesh
{
"id": 14463,
"slug": "andhra-pradesh-electricity-regulatory-commission-transmission-standards-of-performance-regulation-2007",
"title": "Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007",
"short_title": "Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007",
"act_number": "(Regulation No. 1 of 2006)",
"act_year": 2007,
"act_type": "STATE",
"location": "Andhra Pradesh",
"law_status": "unknown",
"enactment_date": null,
"description": "Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007",
"preamble": "",
"section_label": "Section",
"sections": [
{
"number": "1",
"title": "1. Short title and Commencement.",
"chapter": null,
"content": "",
"footnote": "",
"is_definition": false,
"sort_order": 0
},
{
"number": "2",
"title": "2. Definitions.",
"chapter": null,
"content": "(a) \"Act\" means the Electricity Act, 2003 (Central Act No. 36 of 2003);\n(b) \"APTRANSCO\" means Transmission Corporation of Andhra Pradesh Limited registered under the Companies Act, 1956;\n(c) \"CEA\" means the Central Electricity Authority;\n(d) \"Commission\" means Andhra Pradesh Electricity Regulatory Commission;\n(e) \"Consumer\" in the context of this Regulation means any person who is provided with the transmission services by the transmission licensee and includes any person whose premises are for the time being connected for the purpose of providing transmission services from the licensee, and persons who have applied for availing transmission services from a transmission licensee.\n(f) \"EHV/EHT\" means Extra High Voltage/Extra High Tension (voltage level above 33,000 volts);\n(g) \"Grid Code\" means the set of principles and guidelines prepared in accordance with the terms of Section 86(1 )(h) of the Electricity Act, 2003;\n(h) \"IEGC\" means the Indian Electricity Grid Code approved by Central Electricity Regulatory Commission (CERC) and shall include any Grid Code specified by Central Commission under clause (h) of sub-section (1) of Section 79 of the Act;\n(i) \"PGCIL\" means Power Grid Corporation of India Limited, a Central Transmission Utility notified under sub-section (1) of Section 38 of the Act;\n(j) \"Rules\" means the India Electricity Rules, 1956 and/or any otherrules made under Act;\n(k) \"State\" means the State of Andhra Pradesh\n(l) \"State Transmission System\" means the system of EHV electric lines and electrical equipment operated and/or maintained by State Transmission Utility and/or any Transmission Licensee for the purpose of the transmission of electricity among generating stations, ' external interconnections, distribution systems and any other user connected to it with in the state of Andhra Pradesh;\n(m) \"User\" means a person including Generating Stations within the State, Transmission Licensees or Distribution Licensees within the State and open access customer who use the State Transmission System and who must comply with the provisions of the Grid Code.",
"footnote": "",
"is_definition": true,
"sort_order": 1
},
{
"number": "3",
"title": "3. Objective.",
"chapter": null,
"content": "(a) To ensure that the grid performance meets minimum standards essential for the Users' system demand and proper functioning of equipment;\n(b) To enable the Users to design their systems and equipment to suit the electrical environment that they operate in; and\n(c) To enhance the quality standards of the State Transmission System in order to move towards standards stipulated in or established under the authority of National and State Acts and Rules in the short term and gradually towards the international standards in the long term.",
"footnote": "",
"is_definition": false,
"sort_order": 2
},
{
"number": "4",
"title": "4. Standards of Performance.",
"chapter": null,
"content": "(a) Mandatory Standards - Those performance standards, the failure to maintain which attracts the provisions of sub-section (2) of the Section 57.\n(b) Desirable Standards - Those performance standards, which are desirable for providing quality, continuity and reliability of services by the Licensees, and though also specified by the Commission do not, unless provided otherwise by the Commission from time to time, attract the provisions of subsection (2) of the Section 57.\n(a) Voltage Variation\n(b) Safety Standards\n(a) Feeder Availability\n(b) Sub-station Availability\n(c) Voltage Unbalance\n(d) Neutral Voltage Displacement (NVD)\n(e) Voltage Variation Index (WI)\n(f) System Adequacy\n(g) System Security",
"footnote": "",
"is_definition": false,
"sort_order": 3
},
{
"number": "5",
"title": "5. Phasing of Implementation.",
"chapter": null,
"content": "(a) Preliminary Stage (Level-1): The time period of two (2) years immediately after these standards come into force shall be considered as Preliminary State. During this preliminary stage, Standards marked as Level 1 shall be achieved, unless specified otherwise.\n(b) Transition State (Level-2): Time period spreading up to three (3) years after the Preliminary State shall be considered as Transition Stage. During this period, the licensee is expected to upgrade its systems. Standards marked as Level 2 shall be achieved during Transition State-, unless specified otherwise.\n(c) Final Stage (Level-3): Two years after expiry of the Transition State when substantial improvements should have been carried out and the system considered to be in satisfactory condition with necessary capability improvement. Standards marked as Level 3 shall be achieved during this Final State.\nStandards to be complied with:\n(a) Voltage Variation:\n(a) Voltage Variation:\n(i) Voltage Variation is defined as the deviation of the root-mean-square (RMS) value of the voltage from its nominal RMS value, expressed in terms of percentage. Voltage Variation may be either of short duration not exceeding one minute or of long duration for a time greater than one minute.\n(ii) For the purpose of these standards, the sustained variation in steady state voltage exceeding one minute duration shall be considered. The specified permissible limits of sustained voltage variation shall not apply in the cases where the circumstances are reasonably beyond the control of State Transmission Utility/Transmission Licensee e.g. major break-down, grid failures, accidents, system distress conditions, etc.\n(iii) State Transmission Utility/ Transmission Licensee shall make all possible efforts to ensure that the grid voltages remain within the following voltage levels at all points of its Transmission System:\nNominal Voltage (kV)\nMaximum Value (kV)\nMinimum Value (kV)\n400\n220\n132\n33\n11*\n420\n245\n145\n35\n11.67\n360\n200\n120\n30\n10\n* 11 kV voltages to be maintained by the transmission licensee only in those cases where 11 kV supply is extended from the EHT substation.\n(b) Safety Standards:\n(b) Safety Standards:\n(i) State Transmission Utility/ Transmission Licensee shall observe the general safety requirements as laid down in IE Rules, 1956, for construction, installation, protection, operation and maintenance of electric supply lines and apparatus.\n(ii) Relevant rules under IE Rules, 1956 pertaining to safety standards and practices shall be followed.\n(iii) State Transmission Utility/ Transmission Licensee shall develop its own Operation and Maintenance Manual (including Safety Regulations) taking into consideration the safety requirements for the construction, operation and maintenance of electrical plants and electric lines as many be specified by the Central Electricity Authority under Clause © of Section 73 read with Section 53 of the Act.\n(c) Feeder Availability:\n(c) Feeder Availability:\n(i) The feeder availability gives the percentage fo time during which the feeder remained available for transmission. Feeder Availability shall be calculated based on following formula:\n% Availability of feeders = (No of feeders X 8760 - Feeder Annual outages in feeder-hours) X 100 Total availability in feeder-hours\n(ii) The Transmission Licensee shall achieve 99% feeder availability from the preliminary stage itself.\n(d) Sub-station Availability:\n(d) Sub-station Availability:\n(i) The sub-station availability expressed in percentage is the measure of the extent the power transmission capacity remained available from a sub-section. Sub-station availability shall be calculated based on following formula:\n% Availability of SS = (Installed in MVA X 8760-Outages in MVA X Hours) X 100 Installed capacity in MVA X 8760\n(ii) The Transmission Licensee shall achieve 97% Substation availability from the preliminary stage itself.\n(e) Voltage Unbalance:\n(e) Voltage Unbalance:\n(i) The phase voltages of a 3-phase supply should be equal in magnitude and phase angle. The loads on each phase should be balanced. Deviations will result in decreased efficiency, negative torque, vibrations and overheating Severe unbalance could lead to malfunctioning of some equipment. The unbalance is computed as follows:\n% Voltage Unbalance = Max Deviation from Mean of {V RY , V YB , V BR }X 100 {V RY , V YB , V BR }\n(ii) Subject to Distribution Licensee(s) observing the Grid Code Connection Conditions in this regard, the voltage unbalance shall not exceed the values given below:\nImplementation Stage\nVoltage Level\nLimit of voltage Unbalance\nPreliminary\n\t\t\t\tState-Level 1\nTransition State-Level\n\t\t\t\t2\nTransition State-Level 2\n220kV and Above\n132kV\n33 kV and 11 kV buses in EHV Substation\n2%\n3%\n3%\n(f) Neutral Voltage Displacement (NVD):\n(f) Neutral Voltage Displacement (NVD):\n(i) Unbalance in loads on three phases cause shifting of neutral from earth potential. Neutral displacement is applicable for transformers with 'Star Point' solidly ground. Under \"solidly\" grounded conditions, the potential of neutral should be equal to earth i.e. zero. But in actual conditions, the earthing of the star point is imperfect and so the star to ground offers small resistance. This results in flow of negative sequence currents because Ir + Iy + lb is not equal to zero, where, Ir is the current in the R-Phase, ly is the current in the Y-Phase and lb is the current in the B-Phase) through neutral to ground. The neutral therefore shifts from earth potential. This performance standard shall be achieved for star point of all EHT transformers having 33kV or 1 lkV on the low voltage side.\n(ii) Unbalance voltages and displacement of neutral result in decreased efficiency, negative torque, leakage currents, vibrations and overheating. Severe unbalance and neutral displacement could lead to malfunctioning of some equipment.\n(iii) The State Transmission Utility/ Transmission Licensee shall ensure that the neutral point voltage of the transformers with respect to earth will not have potential greater than 2% of the no load phase to phase voltage of the transformer.\n(iv) This standard shall be implemented in the Preliminary State (Level 1) itself.\n(g) Voltage Variation Index (WI): Voltage Variation Index representing the degree of voltage variation from nominal value (in %) over a specified period of time shall be computed separately by the State Transmission Utility/Transmission Licensee for higher than nominal system voltage and lower than nominal system voltage as per the following formula:\n(g) Voltage Variation Index (WI):\nN\nVVI = Square Root of { ∑ (V t -V N )/N²) X (1000/Vs)%} I=1\nI=1\nPreliminary State-Level 1 = 10 To be achieved for more than 90% of buses Transition stage Level 2 = 6 To be achieved for more than 90% of buses Final Stage-Level 3 = 4 To be achieved for more than 90% of buses\nPreliminary State-Level 1\n= 10\nTo be achieved for more than 90% of buses\nTransition stage Level 2\n= 6\nTo be achieved for more than 90% of buses\nFinal Stage-Level 3\n= 4\nTo be achieved for more than 90% of buses\n(h) System Adequacy:\n(h) System Adequacy:\nImplementation Stage\nNos. of hours in year when system demand\nLoss of Load Expectation\ncan be fully met subject to generation availability (A)\ncan not fully met even with generation availability (B=8760-A)\n(LOLE) in % of hours (C=B XI00/8760)\nPreliminary\n\t\t\t\tState-Level 1\nTransition\n\t\t\t\tStage-Level 2\nFinal Stage-Level 3\n7446\n7884\n8672.4\n1314\n876\n87.60\n15%\n10%\n1%\n(i) System Security:\n(i) System Security:\nImplementation Stage\nSystem Security Level of \"n-1\" (Single\n\t\t\t\tContingency) plus spinning reserve margin of:\nPreliminary Stage-Level 1\nTransition Stage-Level 2\nFinal Stage-Level 3\nNo mandatory\n\t\t\t\trequirement\n0.5% of system peak\n\t\t\t\tload\n1% of system peak load",
"footnote": "",
"is_definition": false,
"sort_order": 4
},
{
"number": "6",
"title": "6. Reporting Requirement and Compliance.",
"chapter": null,
"content": "(a) lst Half year: Is1 April to 30,h September\n(b) 2nd Half year: 1st October to March 31M.\n(a) Consequent to failure of State Transmission Utility/ Transmission Licensee to meet performance standards specified herein, the affected utility/ Consumers shall be entitled to seek relief/compensation from State Transmission Utility/ Transmission Licensee, as may be determined by the Commission:\n(b) The Commission at its own discretion may require the State Transmission Utility/ Transmission Licensee to furnish a report on actual performance levels maintained against the standards specified by the Commission with its Petitions for Annual Revenue Requirement (ARR) and Tariff Determination, which shall be subject to public hearing for tariff setting by the Commission.",
"footnote": "",
"is_definition": false,
"sort_order": 5
},
{
"number": "7",
"title": "7. Miscellaneous.",
"chapter": null,
"content": "Use of the Information\nPower to Amend\nSavings\nExemption\nHalf Yearly Report on Transmission Performance Standards\nHalf Yearly Report on Transmission Performance Standards\nName of State Transmission Utility/transmission Licensee\nReport for Half\n\t\t\t\tYear Ending:.......\nDate Of Submission......\nSI. No.\nCategory of Standard\nImplementing Stage/level\nPerformance Standard(s)\nMeasurable Parameter\nValue of Measurable Parameter Specified by\n\t\t\t\tCommission\nActual Achievement for half year\nName of the Parameter\nValue specified\nNote. - 1. The State Transmission Utility shall maintain the base data like Log Sheet, Complaint Registers and Interruption Register etc. at sub-station level.",
"footnote": "",
"is_definition": false,
"sort_order": 6
},
{
"number": "2",
"title": "2. For compilation of monthly report at circle level base data of sub-stations shall be used.",
"chapter": null,
"content": "",
"footnote": "",
"is_definition": false,
"sort_order": 7
},
{
"number": "3",
"title": "3. The consolidated report for whole State Transmission Utility/Transmission Licensee shall be based on circle-wise compilation.",
"chapter": null,
"content": "",
"footnote": "",
"is_definition": false,
"sort_order": 8
},
{
"number": "4",
"title": "4. The circle-wise compilation and base data at sub-station level may be subject to Commission scrutiny as may be necessary.",
"chapter": null,
"content": "Name of Reporting Officer:\nDesignation",
"footnote": "",
"is_definition": false,
"sort_order": 9
}
],
"metadata": {
"Act ID": "Last Updated 25th September, 2019 [ap610]",
"Act Number": "(Regulation No. 1 of 2006)",
"Enactment Date": "",
"Act Year": "2007",
"Short Title": "Andhra Pradesh Electricity Regulatory Commission (Transmission Standards of Performance) Regulation, 2007",
"Type": "STATE",
"Location": "Andhra Pradesh"
},