    "id": 25397,
    "slug": "the-u-p-cinematograph-rules-1951",
    "title": "The U.P. Cinematograph Rules, 1951",
    "short_title": "The U.P. Cinematograph Rules, 1951",
    "act_number": "",
    "act_year": 1951,
    "act_type": "STATE",
    "location": "Uttar Pradesh",
    "law_status": "unknown",
    "enactment_date": null,
    "description": "The U.P. Cinematograph Rules, 1951",
    "preamble": "",
    "section_label": "Section",
    "sections": [
        {
            "number": "1",
            "title": "1. Title, commencement and extent.",
            "chapter": null,
            "content": "(ii) They shall come into force with effect from February 1, 1951\n(iii) They shall apply to all cinemas in Uttar Pradesh.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 0
        },
        {
            "number": "2",
            "title": "2. Definitions.",
            "chapter": null,
            "content": "(i) \"Act\" means the Cinematograph Act, 1918, as amended from time to time;\n(ii) \"Auditorium\" means that portion of the licensed premises where accommodation is provided for the public to view the exhibition of films;\n(iii) \"Cinemas\" means the entire place licensed for cinematograph exhibition and includes all appurtenances, plant and apparatus located therein;\n(iv) \"Government\" means the Government of Uttar Pradesh;\n(v) \"License\" means a written authorization by the Licensing Authority to give cinematograph exhibitions and granted in the form set out in Appendix I to these rules and shall be subject to necessary modifications or amplifications in accordance with any terms or conditions imposed under sub-section (3) of Section 5 of the Act;\n(vi) \"Licensee\" means a person who has been granted a license and includes his agent appointed for the purpose under a power of attorney and whose appointment has been intimated in writing to the Licensing Authority;\n(vii) \"Licensing Authority\" means an officer appointed such by the Government by notification in the official Gazette , for specified area;\n(viii) \"Permanent building\" means a building, which is constructed for permanent use with stone, mud, brick, mortar, cement or other non-inflammable material;\n(ix) \"Protection room\" means that portion of the cinema in which the cinematograph machine is erected;\n(x) \"Special Cinematograph exhibition\" means a cinematograph exhibition given on specified occasion or occasions at a place not ordinarily used for such purpose;\n(xi) \"Temporary building\" means a building which is not a \"permanent building\" and includes a both, tent or similar structure;\n(xii) \"Temporary enclosure\" means that portion of a place licensed for special cinematograph exhibition or of a traveling cinema, where cinematograph apparatus is kept or erected or where fills are stored and wound;\n(xiii) \"Winding rooms\" means that portion of the cinema in which cinematograph films are stored and wound.",
            "footnote": "",
            "is_definition": true,
            "sort_order": 1
        },
        {
            "number": "3",
            "title": "3. Application for construction a building.",
            "chapter": null,
            "content": "[4. Application for a licence.\n(a) The proof of ownership of the premises and cinematographic projector/digital projection system with the original plan of site and premises and the position of the premises in relation to adjacent premises and public through fares on which the building abuts, within a radius of 200 meters, approved by the competent authority under the relevant provisions.\n(b) The original order of construction with building plan, which shall contain the elevations and sections of the buildings, the proposed electrical installations, arrangements for ventilation, sanitation and parking of vehicles approved by the Competent Authority under the relevant provisions.\n(c) Plan of seating arrangements for each class, separately, approved by the competent authority under the relevant provisions.\n(d) Completion certificate/occupation certificate issued by the Competent Authority; with no objection certificate regarding structural safety and stability.\n(e) Certificate from Deputy Director or Assistant Director of Electrical Security Department of concerned area or the person authorised by him that the electrical installations conform to the required standards and the existing rules and bylaws.\n(f) The details of arrangements for sanitation conforming to the requirements of the Rule 13 of the Uttar Pradesh Cinematograph Rules, 1951 and the Building and Development bylaws;\n(g) Certificate from Chief Fire Officer/Officer in-charge (Fire) of concerned area or the person authorised by him having jurisdiction that the arrangements for fire-fighting appliances provided and the precautions taken against fire conform to the requirements of the existing rules and bylaws.\n(h)(i) If the application is complete in all respect and the applicant is eligible, the licence shall be granted through the web portal within thirty days and the same shall be sent through e-mail to the applicant. The applicant may also download the said licence from the departmental web portal.\n(ii) If the licensing authority fails to grant or refuses to grant licence under sub-clause (i) within the stipulated time then on the expiry of the said period the licence shall be deemed to have been granted:",
            "footnote": "",
            "is_definition": false,
            "sort_order": 2
        },
        {
            "number": "5",
            "title": "5. Inspection by Electric Inspector.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 3
        },
        {
            "number": "6",
            "title": "6. Inspection by Medical Officer of Health and Regional Fire Officer.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 4
        },
        {
            "number": "7",
            "title": "7. Conditions for granting and renewing a license.",
            "chapter": null,
            "content": "(a) if it is situated within a radius of 200 meter from the Raj Bhawan, the State Secretariat, the High Court, the State Public Service Commission or the Board of Revenue; or\n(b) if it is situated within a radius of 75 meter from-\n(i) any recognised educational institution (other than primary school) or any residential institution attached thereto; or\n(ii) a public hospital with 25 or more indoor patients; or\n(iii) any building housing an office of a head of the department of the Central or the State Government or the district civil of criminal courts: or\n(iv) any other institution which the Government may consider necessary in public interest to declare an institution to which this clause applies; or\n(c) if for any other sufficient reason to be recorded, the licensing authority is satisfied that the location of a cinema at the site of that building is not public interest:",
            "footnote": "",
            "is_definition": false,
            "sort_order": 5
        },
        {
            "number": "8",
            "title": "8. Requirements of permanent buildings.",
            "chapter": null,
            "content": "(i) it shall be provided with an efficient lightning conductor;\n(ii) if entirely detached the minimum distance between it and other buildings shall be not less than 20 feet with a free all-round space so as to enable the audience to disperse quickly in the event of a fire and to permit easy access to fire engines and fire fighting appliances:\n(iii) in not entirely detached, it shall about on two or more different ways or open spaces shall have sufficient width to enable the audience to disperse quickly in the event of fire and to permit easy access to fire engines or other fire fighting appliances:\n(iv) The frontage shall be of adequate length and the building shall have verandahs on two sides;\n(v) if accommodation is meant to be provided for more than 1000 persons, its distance from other buildings shall be such as THE Licensing Authority may by a special written order require;\n(vi) it shall not be constructed under or on the top of any other building without the special written sanction of the Licensing Authority;\n(vii) where it is in close proximity of another building, a wall or other structure of fire-resisting material in a manner approved by the Licensing Authority shall separate it there from, whose decision as to whether any building is in close proximity shall be final. No opening in the walls or in any part of the building as may be likely to communicate fire to a neighboring building shall be made:\n(viii) the distance between the floor of the auditorium and the ceiling or any covering immediately above shall not be less than 12 feet;\n(ix) the landings, doors, staircases, lobbies and corridors shall be not less than 4 feet 6 inches in width if accommodation is meant for 400 persons or less and not less than 6 feet in width when accommodation is provided for more than 400 persons:\n(x) all staircases shall be constructed of non- inflammable material with stapes not less than 10 inches wide and more than 7 inches high. Each flight shall have not more than 15 and not less than 3 steps;\n(xi) the floor of all landings, staircase, passages and gangways shall be of sufficient strength to carry 120 lb. live load per squire feet and shall be constructed of fireproof material;\n(xii) every staircase forming an exit from an upper story to the ground floor shall have on both sidewalls of bricks or other fire-resisting material in the stores through which it passes and no opening shall be made into the auditorium except when required for an exit from the upper story, which it serves. The staircase leading to the upper story may, however, on one side, instead of a wall, be provided with extra stout handrails or balusters. Enclosed staircases except on platforms and landings with a length exceeding the width of the stairs shall have on both sides strong handrails firmly secure to the walls by strong metal led brackets sunk into the walls to a depth of three inches. For all upper storeys intended for use by the public there shall be provided at least two staircases;\n(xiii) Stairs turning at angles shall have a proper landing at each turn and no wonders shall be introduced; all landings shall be provided with emergency lights;\n(xiv) Where possible gradients or inclined floors shall be used instead of steps, but no gradient or inclined floor shall be steeper than 1 in 10;\n(xv) all exit doors for the use of the public in cinemas already in existence shall be not less than 7 feet in height and 4 feet 6 inches in width, and not less than 7 feet 6 inches in height and 5 feet in width in cinemas licensed after the coming into force of these rules, the width being measured between levees of the doors in open position. The doors shall open outwards and when open shall not obstruct any gangway, passage, staircase landing or lobby, but rest flush against the walls;\n(xvi) cloak rooms where provided shall be so situated that their use causes no obstruction to the free use of any existing corridor or other passage for exit of the audience.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 6
        },
        {
            "number": "9",
            "title": "9. Licence for permanent building.",
            "chapter": null,
            "content": "10.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 7
        },
        {
            "number": "11",
            "title": "11. Electrical requirements.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 8
        },
        {
            "number": "12",
            "title": "12. Ventilation.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 9
        },
        {
            "number": "13",
            "title": "13. Sanitation.",
            "chapter": null,
            "content": "(ii) Latrine and urinals separately for men and women, at different places, and of a suitable type and design shall be provided.\n(iii) There shall be not less than one latrine seat for every 100 person or less and not less than one place for urinating for every 50 persons or less of total seating accommodation: Provided that at least one latrine seat and two places for urinating shall be provided for women.\n(iv) The latrine shall be cleaned and flushed immediately before and after each exhibition and shall be properly washed with a disinfectant at least twice a day. (v) in the case of a water-flushed latrine or urinal a separate water reservoir of adequate capacity shall be provided for flushing.\n(vi) the management may, subject to the direction issued in this behalf by the District Magistrate, refuse admission to or eject persons known to be suffering from a contagious, loathsome or infectious disease.\n(vii) the rooms, passages and staircase of all permanent buildings shall be time wished and all iron and wood-work of such a building shall be cleaned or varnished at least once every year and shall at all times be kept clean and free from dirt.\n(viii) the doors and windows of the halls of the building shall be left open for at least three hours every morning, and for half an hour between shows. During the half hour intervals between the two shows the auditorium shall be disinfected with an aerosal approved by the Medical Officer of Health. The auditorium shall be swept, cleaned and disinfected every morning.\n(ix) the Medical Officer of Health shall be responsible for periodical inspections of all cinemas licensed under the Cinematograph Act, 1918 (II of 1918), situated within the municipal limit to see that sanitary conveniences and arrangements for making the premises clean as provided under the rules are being compiled with and any instructions given in this regard as laid down in the rules shall be compiled with by the management within the time specified.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 10
        },
        {
            "number": "14",
            "title": "14. Seating accommodation.",
            "chapter": null,
            "content": "(ii) Except ground floor and first floor no other floor for seating shall be permitted in permanent cinema buildings.\n(iii) The seating shall be arranged as to leave free access to the exits.\n(iv) The seating space assigned to each person shall be not less than 18 inches. Seat shall have back supports and armrests for each person.\n(v) The rows of seats shall be so arranged as to leave a clear space of not less than 15 inches between the back of any seat and the foremost portion of the seat in the row behind measured between perpendiculars.\n(vi) All seats except in the boxes, shall be securely fixed to the floor or shall be firmly secured together in complete lengths; the complete line shall be firmly attached to the floor. Seating on the floor will not be allowed in permanent building.\n(vii) The distance between the front row of the seats and the screen shall not be less than 19 feet.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 11
        },
        {
            "number": "15",
            "title": "15. Exits.",
            "chapter": null,
            "content": "(i) The licensing Authority may, having regard to the large number of seats in an auditorium, require that a gangway or gangway of a specific width, shall be provided parallel to the rows of seats to secure direct access to exits.\n(ii) An adequate number of clearly indicated exit doors, as may be determined by the Licensing Authority, shall be provided to afford safe and speedy egress for the audience.\n(iii) All doors through which the public must pass in using stairway corridor or other passage for exit shall remain unbolted during the entire period of the exhibition.\n(iv) Passages, gangways, corridors, landings and lobbies shall be kept free from all obstruction at all times to enable quick egress.\n(v) Walls of passages, gangways or corridors shall not have any recess nor shall there be any projection there from within 6 feet of the ground Light shall not be hung to a height less than 7 feet above floor level. Fire appliances are not included within the purview of this sub-rule.\n(vi) Two separate exits not leading into the same thoroughfare shall be provided to every floor or gallery and no stairway shall discharge into a passage or corridor against or across the direction of the exit; provided than the Licensing Authority may accept any other arrangements which likely to ensure adequate safety.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 12
        },
        {
            "number": "16",
            "title": "16. Fire precaution.",
            "chapter": null,
            "content": "17.\n(ii) Once in every year discharge each portable fire-extinguisher provide in the licensed premises and recharge it and immediately record the date of such recharge in durable paint on the external surface of the container of the portable fire-extinguisher.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 13
        },
        {
            "number": "18",
            "title": "18. Prohibition of use of building for purposes other that of a cinema.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 14
        },
        {
            "number": "19",
            "title": "19. Entry into projection room or winding room.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 15
        },
        {
            "number": "20",
            "title": "20. Prohibition on naked light and smoking in projection and winding room.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 16
        },
        {
            "number": "21",
            "title": "21. Projection room.",
            "chapter": null,
            "content": "(ii) (Combustible material) - No combustible material shall be allowed within the enclosure, and all necessary combustible materials when not in use shall be kept in fireproof receptacles suitable for the purpose, and of a type approved by the Regional fire Officer. The box shall be kept closed at all times except when it is necessary to obtain or place a film.\n(iii)Only films which are being used during the exhibition shall be kept in the projection room.\n(iv)The projection room shall be substantially constructed of fire-resisting material and shall be so placed as to be outside the main building forming the auditorium. Provided that in case of cinemas existing the time of commencement of these rules, this requirement may be expressly waved by the Licensing Authority. Before waiving the above requirement the Licensing Authority shall personally satisfy it self that the alternative arrangement proposed is such as will provide sufficient precaution against the extension of fire from the projection room or the auditorium.\n(v) The openings in front of the projection room for each projection machine shall not be more than three in number of which the middle one shall not exceed 8 inches square and the other shall not be more than 5 inches square. Each such aperture shall be provided with a fire proof place glass screen not less than 5/ 16 inch thick fixed in position with some light joints.\n(vi)The entrance to the projection room shall be through a closely fitting self closing door of fire-resisting material suitable placed and opening outwards and all openings, bushes and joints shall be so constructed and maintained as to prevent, as far as possible, the escape of any smoke into the auditorium. This door shall be kept closed at all times when not used for ingress or agrees. Channels of ventilation shall not be allowed to communicate direct with the auditorium. The projection room shall be provided with an opening or vent flue in its roof or upper part of its side wall leading to the outside air. The vent flue shall have minimum sectional area of 50 square inches and shall be fire proof:\n(vii) The projection room shall be at least eight feet in height if one machine is to operated, the space shall not less than 489 square feet and an additional 24 square feet shall be provided for each additional machine to be operated. The width of the room shall be such as to provide sufficient space and easy passages for operators when passing behind the machine.\n(viii) The staircase for the projection room shall be altogether separate from one meant for the use of cinema-goers.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 17
        },
        {
            "number": "22",
            "title": "22. Cinematograph machine.",
            "chapter": null,
            "content": "(ii) The body of the cinematograph machine shall be constructed of metal or liquid with metal and asbestos; or in the latter case there shall be an air space between the metal and asbestos living. The bottom of the cinematograph machine must form a metal tray which shall be surrounded by a vertical edge at least one foot in depth.\n(iii) The cinematograph machine shall be provided with a metal shutter which can be readily inserted between the source of a light and the film gate.\n(iv) The shutter shall be immediately dropped in the event of any accident to the cinematograph machine or stoppage of the film and shall only be raised when the film is in motion for the purpose of projection.\n(v) The film gate shall be of massive construction and provided with ample heat radiating surface and the passage for the film shall be sufficiently; narrow to prevent film travelling upwards or downwards form the light opening.\n(vii) All cinematograph projectors shall be fitted with two metal film boxes of substantial construction, not more than 18 inches in diameter inside measurement, to and from which the films shall travel:",
            "footnote": "",
            "is_definition": false,
            "sort_order": 18
        },
        {
            "number": "23",
            "title": "23. Winding room.",
            "chapter": null,
            "content": "(ii) The winding room shall be closed by a closely fitting self-closing door or fire-resisting material which shall only be opened for egress and shall remain closed during the entire period that the entertainment is in progress. Suitable arrangements shall be made for ventilation in the winding room and one or more electric fans of suitable dimensions shall be provided by the licensee.\n(iii) Only electric light shall be used in the winding room and any lamps in proximity to the film shall be close in a stout fitting designed to prevent breakage of the bulb.\n(iv) Sports shall be chain or gear driven and films shall be so wound upon spools that the wound film shall not at any time reach or project beyond the edges of the flanges of the spool.\n(v) The winding of films shall not be carried out in the projection room while an exhibition is in progress.\n(vi) All films which are not in use shall be kept in prescribed containers specified in the Cinematograph Films Rules, 1948.\n(vii) Exception a films which is being wound or stored, no inflammable article shall unnecessarily be taken into or be allowed to remain in the winding room\n(viii) All cinemas in permanent building shall, without exception, be required to provided and use a winding room in accordance with the above requirements.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 19
        },
        {
            "number": "24",
            "title": "24. Film storage.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 20
        },
        {
            "number": "25",
            "title": "25. Electrification.",
            "chapter": null,
            "content": "(ii) The electric installation in general shall conform to the \"Regulations for Electric Equipment of Buildings\" issued by the institute of Electrical Engineers, England, and the Indian Electricity Rules, 1937, in so far as they are applicable.\n(iii) Where a clear writing a leading in wires of feeding fans or pendant lights run on wooden beams, or other inflammable material, they shall run in conduit so as to resist fire in the event of short circuit.\n(i) Cables for projectors shall be taken as separate circuits from the supply side of the main fuse in general lighting circuit;\n(ii) An efficient doubt pole iron clad switch shall be fitted within the projection room in the projectors circuit;\n(iii) Within the projection room the insulting material of all electric of all electric cables including the leads of the pendant lights and fans shall be covered with fire-resisting material;\n(iv) The writing in the projection room shall be in seamless screwed conduit with efficient bushes. Lead covered cables shall not be used unless enclosed in such conduits;\n(v) All switchgears, fuses, etc., shall be iron clad;\n(vi) The body of the projections switchgears, conduit, etc., shall be connected to the earth by means of not less than No. 8 Standard wore gauge copper wire;\n(vii) All resistances with the exception of resistance for regulating purposes, shall be placed outside the projection room and winding room and if reasonably practicable, also outside the auditorium.\n(viii) Where switchboards are installed in the projection room, the space between any switchboard and the wall shall be enclosed with fire proof material in such a manner that the fire proof material in such a manner that the fire cannot spread to the wiring at the back of the switchboard;\n(ix) No electric current, except with the written sanction of the Electrical Inspector, shall be at pressure higher than 250 volts within the projection room at any time;\n(x) Not more than one-third of the general lighting shall be controlled from the projection room.\n(a) an independent source of supply such as battries, or\n(b) separate main fuses where supply is generated in the premises and a separate line with a separate pole fuse where the installation is fed by the town supply and mannered separately.\n(ii) Emergency lights shall consist of -\n(a) not less than two lights of 200 watts each in the auditorium;\n(b) exit lights;\n(c) light in the doorways foyer, lobbies, verandahs, staircases, corridors and passages for all portions of the premises to which the public has access either generally or in emergency and on the extension of the building facing through-fares.\nNote. - (a), (b) and (c) may be controlled by independent switches or (i), (a) may have an independent switch while (ii) (b) may be controlled by the second switch. All or both switches shall be fixed side by side.\n(iii) All emergency lights shall be controlled from switchboard installed in the convenient and easily accessible place in front of the building. None of the circuits of the emergency light shall on any account enter or be carried through the projection room or winding room;\n(iv) Boxes bearing the words \"EXIT\" painted (red) in three inch letters on translucent glass with dark black background shall be either mounted over each emergency exit door and shall be either connected with the emergency light circuit or fed independently be means of a battery or lighted either with at least two oil lamps, or with at least one gas burner. Such exit signs shall be kept continuously alight during entire period of a performance.\n(v) An efficient portable electric battery or torch with a fully protected bulb shall be kept available in one particular space and in the enclosure and also in the place used for winding film throughout the performance and during all winding or re-winding operations.\n(ii) A shock restoration chart which may be obtained on payment from the Superintendent, Printing and Stationary, Uttar Pradesh Allahabad, shall be provided and hung in a conspicuous place.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 21
        },
        {
            "number": "26",
            "title": "26. Operators.",
            "chapter": null,
            "content": "(ii) An operator's permit shall be granted by the Licensing Authority in the form set out in Appendix II, and a fee of Rs. 20 shall be chargeable for each such permit. No fee shall, however, be charged in respect of permits issued to operators in Government employment.\n(iii) A permit shall not be granted to operator unless he -\n(a) possesses a working knowledge of cinematograph machine and in particulars a working knowledge of the type of machine which he is to operate;\n(b) is thoroughly conversant with the rules and conditions imposed regarding precautions against fire;\n(c) is conversant with the speedy and effective method of dealing with an outbreak of fire\n(d) is proficient in the handling, winding, repairing and cleaning of films.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 22
        },
        {
            "number": "27",
            "title": "27. Period and extent of licences to travelling cinemas.",
            "chapter": null,
            "content": "(a) during the period from April 1 to October 15 ceiling fans, in such numbers and of such size as may be approved by Licensing Authority are provided in the auditorium;\n(b) at least two power driven exhaust fans of not less than 24 inches size are provided in the auditorium;\n(c) on three sides of the auditorium a twelve feet high wall of a non-inflammable material like tinsheets, mud or mortar or bricks is provided; (d) all exit doors provided in the auditorium are according to the specification laid down in sub-rule (15) of Rule 8 and in proportion to its seating capacity that is one door for every 150 persons;\n(e) if the roof of the auditorium is covered by a tent or any other cloth, such cloth shall not touch the ground on any side except towards the screen. The tent shall, however, be fixed securely to pegs on the ground;\n(f) chairs or benches shall be provided for all the classes and a space of 15 inches shall be kept between the rows;\n(g) the screen and cinematograph apparatus shall be so maintained as to ensure satisfactory visibility and audibility;",
            "footnote": "",
            "is_definition": false,
            "sort_order": 23
        },
        {
            "number": "28",
            "title": "28. Grant of licence for travelling cinemas.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 24
        },
        {
            "number": "29",
            "title": "29. Enclosure for travelling cinemas or special cinematograph exhibition.",
            "chapter": null,
            "content": "(i) Construction - It shall consists of a smoke-proof box constructed of sheet iron or steel on a substantial framework and securely fastened together. The internal height from the floor to roof shall be at least ten feet. The floor shall be 48 square feet if one machine is operated and 24 square feet for every additional machine shall be necessary. The room shall be of such width as may allow sufficient space behind the machine for operators to pass easily. The building shall in every other respect conform to the requirements of a projection room in a permanent building: Provided that, if the temporary enclosure is kept in situ or stored on the premises and does not travel with a portable apparatus thereby avoiding risk of breakage, such enclosure may be of asbestos sheeting or other type of fire-resisting material on a substantial fire-resisting framework, the type of fire-resisting material used shall be approved by the Regional fire Officer.\n(ii) Electrical and other necessary apparatus - All apparatus within a temporary enclosure shall likewise satisfy the requirements prescribed for similar apparatus in a permanent building except that such apparatus may be of a portable type.\n(iii) General working - The rules regarding fire-fighting appliances, prohibition of inflammable material, smoking, lights, matches, film re-winding and non-admittance of persons other than operators, the licensee or technician, prescribed for projection rooms in permanent building shall apply to temporary enclosure.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 25
        },
        {
            "number": "30",
            "title": "30. For precautions for auditorium cinemas and special cinematograph exhibition.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 26
        },
        {
            "number": "31",
            "title": "31. Inspection of travelling cinemas by Electric Inspector.",
            "chapter": null,
            "content": "(ii) All travelling cinemas whose stay in the district is likely to extend beyond one month, shall have their installations inspected by the Electric Inspector to Government.\n(iii) The fees, as may be prescribed through notification by the State Government from time to time, shall be levied and credited to the State Government for every initial inspection by the Electric Inspector to Government and also for every subsequent inspection rendered necessary by the detection of defects at a previous inspection which in the opinion of the Electric Inspector make the installation unsafe.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 27
        },
        {
            "number": "32",
            "title": "32. Refusal of licence to travelling cinemas, if in dangerous proximity to other building.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 28
        },
        {
            "number": "33",
            "title": "33. Pandal used during special cinematograph exhibition or by travelling cinemas.",
            "chapter": null,
            "content": "(ii) doors and openings not ordinarily in use may be covered or closed by mats, screen or similar material so as to prevent removal by light pressure from inside the building or structure.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 29
        },
        {
            "number": "34",
            "title": "34. Fencing in vicinity of temporary building.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 30
        },
        {
            "number": "35",
            "title": "35. Notice for special cinematograph exhibition.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 31
        },
        {
            "number": "36",
            "title": "36. Exemption of special cinematograph exhibition from the provisions of the rules.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 32
        },
        {
            "number": "37",
            "title": "37. Inspection of cinemas.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 33
        },
        {
            "number": "38",
            "title": "38. Removal of defects.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 34
        },
        {
            "number": "39",
            "title": "39. Fees for Cinematograph licence.",
            "chapter": null,
            "content": "(i) For the grant or renewal of a permanent licence for permanent cinema in a local area having population -\n(a) Upto one lac -\nRs. 1000/ (One thousand) per month or part there\n\t\t\t\tof.\n(b) More than One lac -\nRs. 1500/ (One thousand Five Hundred) per month\n\t\t\t\tor part thereof.\n(ii) For the grant or renewal of a temporary licence for travelling cinema for a period - Rs. (a) not exceeding one month 150.00 (b) exceeding one month but not Exceeding three\n\t\t\t\tmonths. 450.00 (c) exceeding three moths but not Exceeding six\n\t\t\t\tmonths. 900.00\nRs.\n(a) not exceeding one month\n150.00\n(b) exceeding one month but not Exceeding three\n\t\t\t\tmonths.\n450.00\n(c) exceeding three moths but not Exceeding six\n\t\t\t\tmonths.\n900.00\n(iii) Fee for the issue of a duplicate copy of permanent of temporary licence to the licensee shall be 75 percent of the respective fee for the original licence as prescribed above.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 35
        },
        {
            "number": "39A",
            "title": "39A. Fee for inspection of places proposed for construction of permanent building.",
            "chapter": null,
            "content": "40.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 36
        },
        {
            "number": "41",
            "title": "41. Control of sound from cinemas.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 37
        },
        {
            "number": "42",
            "title": "42. Booking office.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 38
        },
        {
            "number": "43",
            "title": "43. Revocation or suspension of licence.",
            "chapter": null,
            "content": "(a) that the licensee is responsible for a breach of one or more provisions of the Act, or these rules, or any condition of the licence,\n(b) that any unauthorised alteration is make in the building or the seating arrangement or enclosure, or\n(c) that the building and installations are not maintained in proper order, or\n(d) that the licensee has failed without sufficient cause to comply with any direction given under the Act, or under these rules by an authority competent to issue such direction, or\n(e) that the cinema is used or conducted in a manner prejudicial to the public interest.\n(ii) A licensee aggrieved by an order passed under the preceding clause may appeal to the State Government within a period of thirty days from the date of Service of such order.\n(iii) The order shall be deemed to be duly served if it is tendered to the licensee, or, where in the opinion of the Licensing Authority personal service cannot be effected, if a copy of the order is affixed at a prominent place or the premises owned or controlled by the licensee.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 39
        },
        {
            "number": "10",
            "title": "44. Imposition of composition charge while granting exemption under Section 10 of the Act.",
            "chapter": null,
            "content": "Sl No.\nSl No.\nExemption from rules\nExemption from rules\nComposition charge Rs.\nComposition charge Rs.\n1.\nRule 3(3)\nRs. 50,000\n2.\nRule 8(2)\nRs. 35,000\n3.\nRule 8(3)\nRs. 40,000\n4.\nRule 14(2)\nRs. 45,000\n5.\nRule 18\nRs. 15,000\nNotifications\nNotifications\nNotification No.20 - M (47)(1)-76,dated May 19, 1977.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 40
        }
    ],
    "metadata": {
        "Act ID": "Last Updated 13th February, 2021 [up869]",
        "Act Number": "",
        "Enactment Date": "",
        "Act Year": "1951",
        "Short Title": "The U.P. Cinematograph Rules, 1951",
        "Type": "STATE",
        "Location": "Uttar Pradesh"
    },
    "updated_at": "2026-09-29 21:55:22"
}