    "act_title": "The Static and Mobile Pressure Vessels (Unfired) Rules, 2016",
    "act_slug": "the-static-and-mobile-pressure-vessels-unfired-rules-2016",
    "section_label": "Section",
    "section": {
        "number": "22",
        "title": "22. Location of pressure vessels.",
        "chapter": null,
        "content": "Table-1\nTable-1\nMinimum Safety Distances for Corrosive, Toxic or Permanent Flammable Gases\nMinimum Safety Distances for Corrosive, Toxic or Permanent Flammable Gases\nSl. No.\nWater capacity of vessel (in litres)\nMinimum distance from building or group of\n\t\t\t\tbuildings or line of adjoining property\nMinimum distance between pressure vessels\n(1)\n(2)\n(3)\n(4)\n(i)\nNot above 2000\n5 metres\n1 metre\n(ii)\nAbove 2000 but not above 10,000\n10 metres\n1 metre\n(iii)\nAbove 10,000 but not above 20,000\n15 metres\n1.5 metres\n(iv)\nAbove 20,000 but not above 40,000\n20 metres\n2 metres\n(v)\nAbove 40,000\n30 metres\n2 metres\nTable-2\nTable-2\nMinimum Safety Distances for Non-Corrosive, Non-Flammable or Non-Toxic Gases\nMinimum Safety Distances for Non-Corrosive, Non-Flammable or Non-Toxic Gases\nSl. No.\nWater capacity of vessel (in litres)\nMinimum distance from building or group of\n\t\t\t\tbuildings or line of adjoining property\nMinimum distance between vessels\n(1)\n(2)\n(3)\n(4)\n(i)\nNot above 2000\n3 metres\n1 metre\n(ii)\nAbove 2000 but not above 10,000\n5 metres\n1 metre\n(iii)\nAbove 10,000 but not above 20,000\n7.5 metres\n1.5 metres\n(iv)\nAbove 20,000 but not above 40,000\n10 metres\n2 metres\n(v)\nAbove 40,000\n15 metres\n2 metres\nTable-3\nTable-3\nMinimum Safety Distances for Liquefied Flammable Gases\nMinimum Safety Distances for Liquefied Flammable Gases\nSl. No.\nWater capacity of vessel(in litres)\nMinimum distance from building or group of\n\t\t\t\tbuildings or line of adjoining property\nMinimum distance between vessels\nAbove ground\nUnderground or aboveground vessels covered with\n\t\t\t\tearth (mound)\nAbove ground\nUnderground or aboveground vessels covered with\n\t\t\t\tearth (mound)\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\n(i)\nNot above 2000\n5 metres\n3 metres\n1 metre\n1 metre\n(ii)\nAbove 2000 but not above 7,500\n10 metres\n3 metres\n1 metre\n1 metre\n(iii)\nAbove 7,500 but not above 10,000\n10 metres\n5 metres\n1.5 metres\n1 metre\n(iv)\nAbove 10,000 but not above 20,000\n15 metres\n7.5 metres\n2 metres\n1 metre\n(v)\nAbove 20,000 but not above 40,000\n20 metres\n10 metres\n2 metres\n1 metre\n(vi)\nAbove 40,000 but not above 3,50,000\n30 metres\n15 metres\n2 metres or 1/4 th of the\n1 metre\n(vii)\nAbove 3,50,000 but not above 4,50,000\n40 metres\n15 metres\nsum of diameter of adjacent vessel or ½\n\t\t\t\tthe diameter of the two adjacent vessels, whichever is greater\n1 metre\n(viii)\nAbove 4,50,000 but not above 7,50,000\n60 metres\n15 metres\n1 metre\n(ix)\nAbove 7,50,000 but not above 38,00,000\n90 metres\n15 metres\n1 metre\n(x)\nAbove 38,00,000\n120 metres\n15 metres\n1 metre\nTable-4\nTable-4\nMinimum Safety Distances (in meters) between facilities associated with storage of liquefied flammable gas in petroleum refinery, gas processing plants, storage terminals and bottling plants\n(A) For Total Storage above 100 Tonnes\nFrom/ To\nStorage Vessel\nProperty line/ buildings not associated with\n\t\t\t\tstorage and operation\nSheds for filling, storage and evacuation of\n\t\t\t\tcylinders\nTank Truck loading/ unloading gantry\nTank Wagon gantry\nPump/ compress or Shed\nFire Water Pump room\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\n(7)\n(8)\nStorage Vessel\nTable 3\nTable 3\n30\n30\n50\n15\n60\nProperty line/ buildings not associated with\n\t\t\t\tstorage and operation\nTable 3\n-----\n30\n30\n50\n30\n--\nSheds for filling, storage and evacuation of\n\t\t\t\tcylinders\n30\n30\n15\n30\n50\n15\n60\nTank Truck loading/ unloading gantry\n30\n30\n30\n30\n50\n30\n60\nTank Wagon gantry\n50\n50\n50\n50\n50\n30\n60\nPump/ compressor Shed\n15\n30\n15\n30\n30\n---\n60\nFire Water Pump room\n60\n---\n60\n60\n60\n60\n---\n(B) For Total Storage not above 100 Tonnes\nFrom/ To\nStorage Vessel\nProperty line/ buildings not associated with\n\t\t\t\tstorage and operation\nSheds for filling, storage and evacuation of\n\t\t\t\tcylinders\nTank truck unloading/ loading gantry\nFire Water Pump room\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\nStorage Vessel\nTable 3\nTable 3\nTable 3\n15\n30\nProperty line/ buildings not associated with storage &\n\t\t\t\toperation\nTable 3\n-----\n15\n15\n--\nSheds for filling, storage and evacuation of cylinders\nTable 3\n15\n15\n15\n30\nTank truck unloading/ loading gantry\n15\n15\n15\n15\n30\nFire Water Pump room\n30\n--\n30\n30\n--\nTable-5\nTable-5\nMinimum Safety Distances (in metres) between facilities associated with storage and dispensing of liquefied petroleum gas in liquefied petroleum gas dispensing station as automotive fuel to motor vehicles\nMinimum Safety Distances (in metres) between facilities associated with storage and dispensing of liquefied petroleum gas in liquefied petroleum gas dispensing station as automotive fuel to motor vehicles\nTo/ From\nLPG Storage Vessels\nFill point of LPG Storage vessel and Centre of LPG Tank-Truck\n\t\t\t\tunloading hard stand\nLPG Dispenser\nProperty line\nPetroleum Class A or B service Station licensed in Form XIV\n\t\t\t\tof Petroleum Rules 2002\nFill point of petroleum class A/B tanks\nVent pipe of petroleum class A/B tanks\nPetroleum Class A/B dispensing pump\n(1)\n(2)\n(3)\n(4)\n(5)\n(6)\n(7)\n(8)\nLPG Storage Vessels\nTable 3\n9 (aboveground/  mounded vessels exceeding 7,500\n\t\t\t\tlitres capacity) 6 (aboveground/ mounded vessels not exceeding\n\t\t\t\t7,500 litres capacity) 3 (underground vessel)\n9 (above-ground vessels not exceeding 20,000\n\t\t\t\tlitres capacity or underground/ mounded vessels) 15 (above-\n\t\t\t\tground vessels exceeding 20,000 litres capacity)\nTable 3\n9\n9\n9\nFill point of LPG Storage vessel and Centre of\n\t\t\t\tLPG Tank-Truck unloading hard stand\n9 (aboveground/ mounded vessels exceeding 7,500\n\t\t\t\tlitres capacity) 6 (aboveground/ mounded vessels not exceeding\n\t\t\t\t7,500 litres capacity) 3 (underground vessel)\n--\n6\n9\n6\n6\n6\nLPG Dispenser\n9 (aboveground vessels not exceeding 20,000\n\t\t\t\tlitres capacity or underground/ mounded vessels) 15\n\t\t\t\t(aboveground vessels exceeding 20,000 litres capacity)\n6\n--\n6\n6\n6\n6\nProperty line\nTable 3\n9\n6\n--\n3\n4\n6\nTable-6\nTable-6\nMinimum Safety Distance for Non-Flammable, Non-Toxic, Cryogenic Liquids And Liquefied Nitrous Oxide\nMinimum Safety Distance for Non-Flammable, Non-Toxic, Cryogenic Liquids And Liquefied Nitrous Oxide\nWater capacity of vessel (litres)\nBetween two vessels (meter)\nBetween vessel and any building or adjoining property line or\n\t\t\t\tpedestrian passage (meter)\nBetween vessel and flammable structure, naked flame, pipeline\n\t\t\t\tcontaining flammable fluids, electric installation or places of\n\t\t\t\tpublic assembly or drain (meter)\n(1)\n(2)\n(3)\n(4)\nUp to 1,000\n0.5\n2\n3\nAbove 1,000 but not above 10,000\n1\n3\n5\nAbove 10,000\n1\n3\n7.5\nTable-7\nTable-7\nMinimum Safety Distances for Liquid Carbon Dioxide\nMinimum Safety Distances for Liquid Carbon Dioxide\nWater capacity of vessel in litres\nBetween two vessels\nBetween vessel and any building or adjoining property line or\n\t\t\t\tplaces of public assembly or drain\n(1)\n(2)\n(3)\nNot exceeding 50,000\n1 metre\n2 metres\nExceeding 50,000\n2 metres\n4 metres\n(a) thirty metres for corrosive, toxic or flammable gases for above ground vessel and fifteen meters for underground and mounded vessel;\n(b) fifteen metres for non-corrosive, non-toxic or non-flammable gases.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 21
    },
    "prev_section": "21",
    "next_section": "23"
}