    "act_title": "The Oil Mines Regulations, 2017",
    "act_slug": "the-oil-mines-regulations-2017",
    "section_label": "Section",
    "section": {
        "number": "144",
        "title": "144. Appeal to Committee.",
        "chapter": null,
        "content": "Schedule\n[ See regulation 106]\n[ See regulation 106]\nClassification of Hazardous Area in Oil Mine\nClassification of Hazardous Area in Oil Mine\nA. Drilling and Work-Over Operations:\n(i) When the derrick is not enclosed and the sub-structure is open to ventilation, the area in all directions from the base of rotary table extending up to 3.0 metre shall be zone \"2\" hazardous area. Any cellars, trenches and pits below the ground level shall be zone \"1\" hazardous area; the area lying up to 3.0 metre in horizontal direction from the edge of any cellars, trenches on pit and 0.5 metre vertically above the cellars, trenches on pit shall be zone \"2\" hazardous area.\n(ii) When the derrick floor and substructure are enclosed, the enclosed substructure below the derrick floor, including collars, pits or sumps below the ground level, shall be zone \"1\" hazardous area; the enclosed area above the derrick floor shall be zone \"2\" hazardous area.\nThe free space above the level of mud in tank and channel shall be zone \"1\" hazardous area; the area in a radius of 3.0 metre in all direction from the edge of mud tank and channel shall be zone \"2\" hazardous area.\n(i) The area within a radius of 1.5 metre in all directions from the shale shaker in open air shall be zone \"1\" hazardous area. The area beyond 1.5 metre and up to 3.0 metre in all directions from the shale shaker shall be zone \"2\" hazardous area.\n(ii) When the shale shaker is located in an enclosure, the enclosed area shall be zone \"1\" hazardous area to the extent of the enclosure. The area outside the shale shaker and up to 1.5 metre in all directions from the shale shaker shall be zone \"2\" hazardous area.\nThe area within a radius of 1.5 metre from the open end of the vent extending in all directions shall be zone \"1\"; the area beyond 1.5 metre and up to 3 metre in all directions from the open end of vent shall be zone \"2\" hazardous area.\nThe area within a radius of 1.5 metre in all direction from the Desander and Desilter location in open air shall be zone \"2\" hazardous area.\nThe free space above the level of flammable liquid within the effluent pit on sump shall be zone \"1\" hazardous area; the free space lying up to 3.0 metre in hazardous direction form the edge of any effluent pit or sump and 5.0 metre vertically above the effluent pit or open sump shall be zone \"2\" hazardous area.\nB. Oil Wells.\nA well area below the ground level shall be zone \"1\" hazardous area; the area lying up to 3.0 metre in horizontal direction from the edge of any cellars, trenches or pit and 0.5metre vertically above the callers trenches on sump shall be zone \"2\" hazardous area.\n(i) The area in wells equipped with sucker-rod pump to 3.0 metre above the ground level up to 3.0 metre horizontal in all directions from the well head shall be zone - \"2\" hazardous area. In case of cellar, an area below the ground level shall be zone \"1\" hazardous area; the area lying up to 3.0 metre in horizontal direction from the edge of any cellars and 0.5 metre vertically above the cellars shall be zone \"2\" hazardous area.\n(ii) The area in wells equipped with submersible electric motor driven pump or hydraulic subsurface pump or gas lift wells shall be same as specified in clause B(1) when the well is provided with cellar or sump.\nThe area within a radius of 8.0 metre from an open discharge of petroleum bearing fluid from a well under production test shall be zone \"1\" hazardous area. The area beyond zone 1 hazardous area for a future distance of 8 metre in all directions shall be zone \"2\" hazardous area.\nThe area within a radius of 10.0 metre in all direction from a well-pulling and other such well servicing shall be zone \"2\" hazardous area:\nProvided that where cellar or sump is present, the area within the cellar or sump shall be zone \"1\" hazardous area and the area up to 3.0 metre in horizontal direction from the edge of any cellars or sump and 0.5 metre vertically above the cellar or sump shall be zone \"2\" hazardous area.\nThe area within a radius of 1.5 metre from open end of the vent extending in all direction shall be zone \"1\" hazardous area and area lying within a radius beyond zone \"1\" hazardous area up to 3.0 metre of the vent shall be zone \"2\" hazardous area.\nC. Oil and Gas Processing and Storage Equipment.\n(i) the area within a radius of 3.0 metre from any oil-gas separation vessel, fired vessel, dehydrator, stabiliser and hydrocarbon recovery unit shall be zone \"2\" hazardous area;\n(ii) any trench or pit below the ground level shall be zone \"1\" hazardous area and the area lying up to 3.0 metre in horizontal direction from the edge of any trench or pit and 0.5 metre vertically above the trench or pit shall be zone \"2\" hazardous area.\nThe area within a radius of 1.5 metre from open end of the vent extending in all direction shall be zone \"1\" hazardous area and area lying within a radius beyond zone \"1\" hazardous area up to 3.0 metre of the vent shall be zone \"2\" hazardous area.\nThe area within a radius of not less than 3.0 metre from discharge of a relief valve, extending in all direction shall be zone \"2\" hazardous area subject to the conditions that there shall be no electrical equipment in direct path of discharge from relief valve.\nThe area within a radius of 1.5 metre of pig launching or receiving trap extending in all direction shall be zone \"1\" hazardous area. The area lying beyond zone \"1\" hazardous area and up to a radius of 3.0 metre in all directions pig launching/ receiving trap shall be zone \"2\" hazardous area.\n(i) Where a pump handling flammable liquid or a gas compressor located in open air or under well ventilated shed without wells, the area lying up to 3.0 metre in all directions from the pump or compressor shall be zone \"2\" hazardous area.\n(ii) Where a pump or a compressor is located in an adequately ventilated building, the entire interior of such building including an area within 1.5 metre of the vent shall be zone \"2\" hazardous area.\n(iii) Pits, sumps, trenches below the ground level shall be zone \"1\" hazardous area and the area lying up to 3.0 metre in horizontal direction from the edge of any trench or pit and 0.5 metre vertically above the pits, sumps or trenches shall be zone \"2\" hazardous area.\n(i) In case of floating roof tank, the space above the floating roof and inside the enclosures up to top level of the enclosure wall shall be zone \"1\" hazardous area; the area beyond zone \"1\" hazardous area and up to a radius of 4.5 metre in all directions from tank shall and shell top shall be zone \"2\" hazardous area. In case of a dyke, zone \"2\" hazardous area shall extend vertically up to the height of the dyke and horizontally up to the physical boundary of the dyke.\n(ii) In case of fixed roof tank, the area inside the tank and within a radius of 1.5 metre from all opening including breather valve, dip hatch, thief hatch and safety valve shall be zone \"1\" hazardous area; the area zone \"1\" beyond hazardous area and up to a radius of 3.0 metre in all directions from tank shall and rood of the tank be zone \"2\" hazardous area. In case of a dyke, the sump in the dyke shall be zone \"1\" hazardous area and an area extending vertically up to a height of the dyke horizontally to the physical boundary of the dyke shall be zone \"2\" hazardous area.\nD. General.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 143
    },
    "prev_section": "143",
    "next_section": null
}