    "section": {
        "number": "12",
        "title": "12. Ventilation.",
        "chapter": null,
        "content": "(b) The sectional area of every part of the inlet and exhaust system (other than a par serving a drying room or locker) shall be at least [38.71 square centimetre] for each person for whose use at any one time the space is appropriated and shall not be less than [122.58 square centimetres] in all at any point in the system. The effective area of the inlet and exhaust system serving each space shall be capable of being adjusted from fully open down to a minimum of the [19.35 square centimetres] for each person likely to use the space at any time.\n(a) maintain the air at a satisfactory temperature and relative humidity as compared to outside air conditions;\n(b)ensure a sufficiency of air charges in all air conditioned spaces;and\n(c) take into account particular characteristics of operations at sea so as to avoid producing objectionable noises or vibrations.]",