    "id": 12323,
    "slug": "the-madras-port-petroleum-rules-1963",
    "title": "The Madras Port Petroleum Rules, 1963",
    "short_title": "The Madras Port Petroleum Rules, 1963",
    "act_number": "Published vide Notification Gazette of India, 1963",
    "act_year": 1963,
    "act_type": "CENTRAL",
    "location": "India (Central)",
    "law_status": "unknown",
    "enactment_date": null,
    "description": "The Madras Port Petroleum Rules, 1963",
    "preamble": "",
    "section_label": "Section",
    "sections": [
        {
            "number": "1",
            "title": "1. Short title, extent and commencement.",
            "chapter": null,
            "content": "(ii) They extend to the whole of the Madras Port area.\n(iii) They shall come into force from the date of publication.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 0
        },
        {
            "number": "2",
            "title": "2. Application of Petroleum Rules, 1937, not barred.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 1
        },
        {
            "number": "3",
            "title": "3. Definitions.",
            "chapter": null,
            "content": "(a) \"Bulk Oil vessel\" means a vessel licensed to carry petroleum in bulk as  cargo.\n(b) \"Cased Petroleum\" means petroleum packed in cases, casks, drums or  other receptacles.\n(c) \"Dangerous Petroleum\" means any petroleum having flash point below  76°F.\n(d) \"Heavy Petroleum\" means petroleum which has its flash point not  below 150°F.\n(e) \"Non-dangerous Petroleum\" means petroleum having its flash point  below 150°F, but not below 76° F.\n(f) \"Petroleum\" means any liquid hydro-carbon or mixture of hydrocarbons  and any inflammable mixture (liquid, viscous or solid) containing any  liquid hydro-carbon or any other commodity given in the Schedule.\n(g) \"Petroleum in bulk\" means petroleum contained in receptacles  exceeding 200 gallons in capacity.\n(h) \"Ton\" when used to indicate the weight of petroleum is taken as  equivalent to 300 gallons.",
            "footnote": "",
            "is_definition": true,
            "sort_order": 2
        },
        {
            "number": "4",
            "title": "4. Notice of arrival of 'Petroleum'.",
            "chapter": null,
            "content": "(a) The name /names of the petroleum product/products.\n(b) The flash point of such product/products.\n(c) Whether such product/ products is/ are mixable with water or not.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 3
        },
        {
            "number": "5",
            "title": "5. Vessels carrying Petroleum in bulk.",
            "chapter": null,
            "content": "(a) from sunrise to sunset a red flag not less than three feet square with a  white circular centre six inches in diameter, if dangerous petroleum is  carried and a red flag not less than three feet square, if non-dangerous  petroleum is carried; and\n(b) from sunset to sunrise, a red light.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 4
        },
        {
            "number": "6",
            "title": "6. Landing of Petroleum in bulk.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 5
        },
        {
            "number": "7",
            "title": "7. Vessels discharging Petroleum in bulk.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 6
        },
        {
            "number": "8",
            "title": "8. Conditions of landing of Petroleum in bulk.",
            "chapter": null,
            "content": "(b) In the case of interruption to pumping after sunset due to any reasons, other  than those stated in Cl. (a) above, the Deputy Port Conservator may, at his discretion,  grant special permission to re-commence pumping even during the night time.  Discharge of dangerous petroleum interrupted or suspended after sunset, shall on  no account, be re-commenced until after sunrise, without the permission of the Deputy  Port Conservator.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 7
        },
        {
            "number": "9",
            "title": "9. Accident Fire prevention.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 8
        },
        {
            "number": "10",
            "title": "10. Cased Petroleum, i.e., Petroleum not in bulk.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 9
        },
        {
            "number": "11",
            "title": "11. Landing of Non-dangerous cased Petroleum.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 10
        },
        {
            "number": "12",
            "title": "12. Sailing vessels.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 11
        },
        {
            "number": "13",
            "title": "13. Landing of cased dangerous Petroleum.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 12
        },
        {
            "number": "14",
            "title": "14. Cased Dangerous Petroleum in excess of 20 tons or 6,000 gallons.",
            "chapter": null,
            "content": "(a) Such consignment shall be unloaded into harbour craft at the Petrol Berth.\n(b) The harbour craft containing such consignment shall lie in the Royapuram Bay.\n(c) Not more than four loaded harbour crafts shall be allowed to lie at anchor outside the harbour entrance at any time.\n(d) If it is proposed to leave harbour craft loaded with such consignment afloat in Royapuram Bay during night, the Deputy Port Conservator shall be notified before 4 P.M. of the preceding day.\n(e) Each harbour craft loaded with such consignment shall be provided  with a full crew whose duty it shall be to attend to the moorings of the  harbour craft under their charge and to see that she does not drag. No  harbour craft shall be moored East of the oil intake at the Oil Berth.\n(f) Each harbour craft loaded with such consignment shall be provided  with an efficient anchor and 30 fathoms of good chain and in addition  with not less than 30 fathoms of good 4 inch manila or 6 inch coir rope;  each harbour craft shall also carry at least two oars.\n(g) No harbour craft loaded with such consignment shall be anchored in  Royapuram Bay at a distance less than 150 feet from any other harbour  craft or any vessel.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 13
        },
        {
            "number": "15",
            "title": "15. Bunkering.",
            "chapter": null,
            "content": "(a) During all such time, as any vessel is receiving heavy petroleum into  her bunkers, the Master or First Mate of such vessel shall be present on  board. It shall be his duty to see that the conditions specified in these  rules are complied with and that all reasonable precautions for safety  are observed.\n(b) A ship's officer shall be on watch and an attendant shall be stationed  alongside the flexible connection pipe while bunkering is in progress.\n(c) Suppliers of heavy petroleum shall be responsible for seeing that all flexible pipes used for bunkering are tested to a pressure of 30 lbs. per  square inch before operations commence, and that all joints are oil  tight, that when flexible pipes are dismantled, any unavoidable spillage  on the quay shall be properly cleansed up with sand. No bunkering  shall be commenced until their supplier has delivered to the Trustees a  certificate to the effect that all flexible pipes to be sued in the operation  have been tested as required by this rule. Officers-in-charge of vessels  which receive heavy petroleum for bunkering shall be responsible for  seeing that all valves in the vessel's tanks connections are properly  regulated to receive the petroleum and due warning shall always be  given to suppliers by ship's officers before any valves are closed, to  prevent the possibility of a sudden increase in pressure which may  cause a burst in the flexible pipe or elsewhere and a consequent leakage  of oil. Owners of vessels which receive heavy petroleum for bunkering  and suppliers, shall be severally responsible for seeing that bunkering  operations are conducted with cleanliness and in an orderly manner  and any damage resulting from neglect of all proper precautions shall  render them liable under clause (d).\n(d) Suppliers of heavy petroleum for bunkering shall be liable for any  damage whatsoever caused to cargo or property belonging to or in  charge of the Trustees by any leakage of such petroleum due to or arising  from negligence or any defect in or failure of, apparatus or appliances  belonging to the suppliers. The Master and owners or the agents of the vessels receiving heavy  petroleum shall also be liable for any such damage if caused by  negligence or defect or failure of apparatus or appliances belonging to  the vessel.\n(e) No cargo other than steel plates, iron rails and similar goods unaffected  by oil, shall be allowed on the wharf within 50 feet of the oil stand  pipes, and shed doors immediately behind them shall be kept closed  while bunkering is in progress.\n(f) Before bunkering commences, the vessel's attendant shall see that the  telephone connection to the Oil Company's depots is in working order.\n(g) An attendant shall be on duty at the .pump throughout the time of  bunkering.\n(h) At least two hour's notice in writing shall be given to the Deputy Port  Conservator before bunkering is commenced.\n(i) No bunkering shall be commenced unless a sand cart containing 15  c.f.t. of sand is on the spot at the supply pipe. This would be the  responsibility of the Oil Company supplying the oil for bunkering.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 14
        },
        {
            "number": "16",
            "title": "16. Enforcement and Penalties.",
            "chapter": null,
            "content": "(b) The occupiers or custodians of premises within the Port limits and/or owners  of petroleum handled or stored anywhere within the Port limits, shall, if so required  by any of the officers mentioned in sub-rule (1), afford all reasonable facility to such  officers to ascertain whether these rules are duly observed.\nAppendix I\nAppendix I\n[See rule 9 (7)]\nFire Protection of the Oil Pipelines and Booster Pumphouse-Precautions to be taken or procedure to be observed by the Oil Companies landing petroleum in bulk.\nFire Protection of the Oil Pipelines and Booster Pumphouse-Precautions to be taken or procedure to be observed by the Oil Companies landing petroleum in bulk.\n(a) General. - 1. Advice to the Trust's Mechanical Engineer - Oil Companies  intending to land petroleum in bulk shall advise the trust's Mechanical Engineer of  the intended landing of such petroleum at least 24 hours before such landing  commences, so as to enable him to post necessary staff to man the Booster Pumphouse  and to petrol the oil pipelines.\n(b) Action to be taken in the event of a leak and/or fire.-In the event of a leak in  the flexible pipelines, (i.e.pipelines connecting the tanker to the shore pipelines) and/  or a fire on or around the North Groyne, the Oil Company's Supervisor/Assistant-in-charge of tanker discharge shall take action as follows :",
            "footnote": "",
            "is_definition": false,
            "sort_order": 15
        },
        {
            "number": "1",
            "title": "1. Arrange for the tanker to stop pumping and to shut down all tanker  discharge valves.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 16
        },
        {
            "number": "2",
            "title": "2. Notify the Port Fire Service-Telephone No. 30161, Extension 268.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 17
        },
        {
            "number": "3",
            "title": "3. Notify the Booster Pumphouse.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 18
        },
        {
            "number": "4",
            "title": "4. Notify the Terminal receiving petroleum, if necessary.",
            "chapter": null,
            "content": "Note.\n(b) It is to be clearly understood that all 'leaks' involving 'Petroleum' other  than'Heavy Petroleum' shall be notified to the Port Fire Service.\nAppendix II\nAppendix II\n[See rule 9 (8)]\nFire Petroleum of the Oil Pipelines and the Booster Pumphouse-Instructions to Port Trust Staff\nFire Petroleum of the Oil Pipelines and the Booster Pumphouse-Instructions to Port Trust Staff\nI. Instructions To The Drivers Of Booster Pumphouse :\nI. Instructions To The Drivers Of Booster Pumphouse :\n(a) General. - The drivers of the booster pump shall, at normal times, be responsible for carrying out the following instructions:",
            "footnote": "",
            "is_definition": false,
            "sort_order": 19
        },
        {
            "number": "1",
            "title": "1. Speaking-tube communicating between the pump room and the engine room shall, at all times, be left closed with the metal cap provided.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 20
        },
        {
            "number": "2",
            "title": "2. The doors and windows of the pumphouse shall always be left closed.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 21
        },
        {
            "number": "3",
            "title": "3. Breakages to the door and window-panes and damage to ventilator  shutters shall promptly be reported to the Workshop Foreman for urgent  repairs.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 22
        },
        {
            "number": "4",
            "title": "4. The refuse-bin provided in the pit shall always be kept reasonably  clean of oil waste and other waste matter.",
            "chapter": null,
            "content": "(b) In case of a leak and/or fire in pipelines or in or about the pumphouse. - In  the event of a leak coming to his notice or being reported to him,.the pump driver shall  expeditiously carry out the following instructions in the order of precedence as given  below:",
            "footnote": "",
            "is_definition": false,
            "sort_order": 23
        },
        {
            "number": "1",
            "title": "1. Stop or arrange to stop pumping.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 24
        },
        {
            "number": "2",
            "title": "2. Actuate the warning device to warn the supervisor on North Groyne and to Engineer at tanker pump.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 25
        },
        {
            "number": "3",
            "title": "3. Notify West Fire Station by telephone.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 26
        },
        {
            "number": "4",
            "title": "4. Hoist warning signal (Red burgee during day and red light during  night) on the flag staff on top of the pumphouse.",
            "chapter": null,
            "content": "II. Instructions To The Section Officers And Staff Of The Traffic Department\nII. Instructions To The Section Officers And Staff Of The Traffic Department",
            "footnote": "",
            "is_definition": false,
            "sort_order": 27
        },
        {
            "number": "1",
            "title": "1. Vans of the pumphouse driven by the quickest means.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 28
        },
        {
            "number": "2",
            "title": "2. Inform West Fire Station of the occurrence (In case of leak, information  may be given over telephone, in case of fire, actuate the nearest fire  alarm box and follow up with a telephonic message.)",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 29
        },
        {
            "number": "3",
            "title": "3. Report the occurrence to 'M' Division Police Station.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 30
        },
        {
            "number": "4",
            "title": "4. Cordon off the area as best as possible pending arrival of police party  and see that no naked lights are brought or caused to be within 300 feet  of the point of occurrence. (For the purpose of this order, locos internal  combustion engines, hurricanes and pressurised lanterns, railways  signal lamps, all types of cycle lamps, ordinary electric hand torches,  etc., are to be considered as 'naked lights'.)",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 31
        },
        {
            "number": "5",
            "title": "5. Pending arrival of Fire Service, take such other measures as may be  considered expedient to prevent outbreak of fire or to keep in check or  extinguish the fire if one has already started.",
            "chapter": null,
            "content": "III. Instructions To The Staff Of Railway Section Of The Traffic Department\nIII. Instructions To The Staff Of Railway Section Of The Traffic Department\nIV. Instructions To The Mazdoors, Posted To Patrol The Oil Pipelines\nIV. Instructions To The Mazdoors, Posted To Patrol The Oil Pipelines",
            "footnote": "",
            "is_definition": false,
            "sort_order": 32
        },
        {
            "number": "1",
            "title": "1. The, mazdoor who notices the leak/fire, shall rush either to the  Pumphouse near No. 1 Gate or to the Oil Companies' bunk on the  North Groyne (whichever of the two places is nearer or more readily  reached from the location of the leak/fire) and shall notify the occurrence  to the Pumphouse driver or the Oil.Company's staff present at the North  Groyne. On his way to the pumphouse or North Groye, he shall alert  the other mazdoors, by shouting out the information to them.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 33
        },
        {
            "number": "2",
            "title": "2. A second mazdoor, i.e., the one nearest to the location of the leak/ fire  shall rush to contact any responsible member of the Port Trust Section  or Railway staff who may be available nearest to location of the leak/  fire, and shall notify him of the occurrence.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 34
        },
        {
            "number": "3",
            "title": "3. The remaining two Mazdoors shall rush to the location of the leak/fire  and shall take such action as they can, to prevent a fire or to keep the  fire under control. In the case of a leak, such Mazdoors shall endeavour  to cordon off the area, as best as they can and shall ward-off locos and  other sources of naked light, from the vicinity of the leak. In the event of a fire, they shall endeavour to keep the fire under check; by using  earth and sand or the foamengine stationed near the Pumph",
            "chapter": null,
            "content": "Note.\nV. Instructions To The Port Fire Service\nV. Instructions To The Port Fire Service",
            "footnote": "",
            "is_definition": false,
            "sort_order": 35
        },
        {
            "number": "1",
            "title": "1. Turn out one unit, under the charge of the seniormost rank of the Fire Service then present at the station.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 36
        },
        {
            "number": "2",
            "title": "2. Notify the Fire Officer and Assistant Satefy Officer, and also notify the Harbour Master of the leak/fire.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 37
        },
        {
            "number": "3",
            "title": "3. Instruct the Hydraulic Powerhouse Driver to start the Fire Service pump and to maintain a working pressure of about 100 lbs.p.s.i. at the pump gauge.",
            "chapter": null,
            "content": "N.B.\nSchedule\n[See rule 3 (1)]\n[See rule 3 (1)]\nInflammable liquids-Their characteristics properties and precautions necessary in the handling of such liquids\nInflammable liquids-Their characteristics properties and precautions necessary in the handling of such liquids\nNote.\nInflammable\n\t\t\t\tliquids(not exhaustive)\nHazards\n\t\t\t\tgenerally associated with inflammable liquids\nPrecautions\n\t\t\t\tnecessary\nAmylalcohol\n\t\t\t\tBisulphide \nof corbon Collodion Ether",
            "footnote": "",
            "is_definition": false,
            "sort_order": 38
        },
        {
            "number": "1",
            "title": "1.\n\t\t\t\tHighly inflammable, even a spark may be \nsufficient to cause \n\t\t\t\tignition.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 39
        },
        {
            "number": "1",
            "title": "1.\n\t\t\t\tNaked or non-safety lights should not be \nallowed within a radius\n\t\t\t\t of atleast 100 ft. of any \nplace where such liquids \nare\n\t\t\t\thandled/st.",
            "chapter": null,
            "content": "Ether\n\t\t\t\tButyric (Ethyl Butyrate \nEther Formic (Ethyl \nFormate), [Ether\n\t\t\t\t(Sulphuric) \nEthyl Acetate (Accetic Ether) \nFuel Oil",
            "footnote": "",
            "is_definition": false,
            "sort_order": 40
        },
        {
            "number": "2",
            "title": "2.\n\t\t\t\tVapour forms \nexplosive mixture with air \nignition of such\n\t\t\t\tmixture \nby a spark or flame may \ncause a shattering \nexplosion.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 41
        },
        {
            "number": "2",
            "title": "2.\n\t\t\t\tThe electrical \nfittings (switches for light \nand fans, lamp\n\t\t\t\tholders, \netc.) within the premises \nused for storage of such \n\t\t\t\tliquids should be of the \ngasproof safety pattern \nand the wiring\n\t\t\t\tshould be \nrun in properly earthed \nmetal conduits.",
            "chapter": null,
            "content": "Petroleum\n\t\t\t\tEther\nPyroxyine\n\t\t\t\t(for photo-graphic and similar purposes)\nVinesthene\n\t\t\t\t(Di-Vinyl Ether)\nEthyl\n\t\t\t\tChloride",
            "footnote": "",
            "is_definition": false,
            "sort_order": 42
        },
        {
            "number": "3",
            "title": "3.\n\t\t\t\tThe vapour, which \nis generally heavier than \nair, may travel \n\t\t\t\tconsiderable distances \n(as and when blown by a \ndraught of air)\n\t\t\t\tand may \nthen ignite by contact with \nflame or spark.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 43
        },
        {
            "number": "3",
            "title": "3.\n\t\t\t\tEvery source of \nsparking should be \navoided within a. radius \nof\n\t\t\t\t100 ft. of any place \nwhere vapour of such \nliquids may be\n\t\t\t\tpresent.",
            "chapter": null,
            "content": "Absolute\n\t\t\t\tAlcohol\nAcetone\nButyl\n\t\t\t\tAlcohol\nC.P.\n\t\t\t\tMethanol\nFrench\n\t\t\t\tPolish\nHydraulic\n\t\t\t\tBrake Fluid\nIndustrial\n\t\t\t\tAlcohol \ndenatured, as under:-",
            "footnote": "",
            "is_definition": false,
            "sort_order": 44
        },
        {
            "number": "4",
            "title": "4.\n\t\t\t\tVapours of most \nsuch liquids are injurious \nif inhaled for any\n\t\t\t\tlength \nof time.",
            "chapter": null,
            "content": "",
            "footnote": "",
            "is_definition": false,
            "sort_order": 45
        },
        {
            "number": "4",
            "title": "4.\n\t\t\t\tThe drums/ \ncontainers of such liquids \nshould not be dropped, \n\t\t\t\tbumped, rolled or roughly \nhandled.",
            "chapter": null,
            "content": "Denatured\n\t\t\t\tMhews\nSpirit\nDenatured\n\t\t\t\tSpirit\nOrdinary\nDenatured\n\t\t\t\tSpirit",
            "footnote": "",
            "is_definition": false,
            "sort_order": 46
        },
        {
            "number": "5",
            "title": "5.\n\t\t\t\tEvery possible \nprecaution should be \ntaken to prevent leaks in \n\t\t\t\tcontainers/drums of \nsuch liquids.",
            "chapter": null,
            "content": "Special\nMethylated\n\t\t\t\tSpirit",
            "footnote": "",
            "is_definition": false,
            "sort_order": 47
        },
        {
            "number": "6",
            "title": "6.\n\t\t\t\tLeaks in such \ndrums/containers \nshould be notified to the \nFire\n\t\t\t\tService, immediately \non being noticed.",
            "chapter": null,
            "content": "Isopropyl\n Alcohol\nMethyl\n Acetone\nMethyl\n Alcohol\nNaptha\n Mineral\nPower\n Alcohol\nPower\n Alcohol Mixture\nSolvent\n Naptha\nSpirit\n Varnish\nRectified\n Spirit (50°F. over\nproof\n and above)\nAs\n under:-\nArrack\nLiquor\nMhowa\n Spirit\nToddy\nToluol\nWood\n Naptha or wood\nspirit\n XvloI,\nInsecticides\n (Fluid)\nInflammable.\nNecol\n household cement\nNeco\n ustre\nPaint\n thinners\nEnamels,\n nitro-cellulose\nLacquers\n nitro-cellulose\nPaints,\n nitro-cellulose\nPolishes,\n nitro-cellulose\nStains,\n nitro-cellulose\nVarnishes,\n nitro-cellulose\nCellulose\n Acetate Dope\nNitro,\n cellulose Dope\nPaint\n and Varnish\nRemover\nPlastic\n Wood\nRawplug\n Durofix\nRubber\n solution \ncomposed of\nRubber\n and naptha\nNote.",
            "footnote": "",
            "is_definition": false,
            "sort_order": 48
        }
    ],
    "metadata": {
        "Act ID": "2015",
        "Act Number": "Published vide Notification Gazette of India, 1963, Part 2, Section 3(i), page 1110.",
        "Enactment Date": "",
        "Act Year": "1963",
        "Short Title": "The Madras Port Petroleum Rules, 1963",
        "Type": "CENTRAL",
        "Location": "India (Central)"
    },
    "updated_at": "2026-09-29 21:55:18"
}