        "title": "87. Lines crossing or approaching each other",
        "chapter": null,
        "content": "SI. No. Nominal System voltage 11-66 KV 110-132 KV 220 KV 400 KV 800 KV 1. Low & Medium 2.44 3.05 4.58 5.49 7.94 2. 11-66KV 2.44 3.05 4.58 5.49 7.94 3. 110-132KV 3.05 3.05 4.58 5.49 7.94 4. 220KV 4.58 4.58 4.58 5.49 7.94 5. 400KV 5.49 5.49 5.49 5.49 7.94 6. 800KV 7.94 7.94 7.94 7.94 7.94 ]",