    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "80",
        "title": "80. Clearances from buildings of high and extra-high voltage lines",
        "chapter": null,
        "content": "(a) for high voltage lines upto and including 33,000 volts 3.7 metres (b) for extra-high voltage lines 3.7 metres plus 0.30 metres for every metres for every additional 33,0000 volts or part thereof.\n(a) for high voltage lines upto and including 11,000 volts 1.2 metres (b) for high voltage lines above 11,000 volts upto and including 33,000 volts 2.0 metres (c) for extra-high voltage lines 2.0 metres plus 0.3 metres plus 0.3 metre for every additional 33,000 volts for part thereof.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 79
    },
    "prev_section": "79",
    "next_section": "81"
}