        "title": "77. Clearance above ground of the lowest conductor",
        "chapter": null,
        "content": "(a) for low and medium voltage lines 5.8 metres (b) for high voltage lines 6.1 metres\n(a) for low and medium voltage lines 5.5 metres (b) for high voltage lines 5.8 metres\n(a) for low, medium and high voltage lines upto and including 11,00 volts, if bare 4.6 metres (b) For low, medium and high voltage lines upto and including 11,000 volts, if insulated 4.0 metres (c) for low voltage lines above 11,000 volts 5.2 metres",
        "footnote": "",
        "is_definition": false,
        "sort_order": 76
    },
    "prev_section": "75",
    "next_section": "78"
}