    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "72",
        "title": "72. Additional provisions for supply to high voltage electrode boilers",
        "chapter": null,
        "content": "(a) The metal work of the electrode boiler shall be efficiently connected to the metal sheathing and metallic armouring (if any) of the high voltage electric supply line whereby energy is supplied to the electrode boiler.\n(b) The supply of energy at high or extra-high voltage to the electrode boiler shall be controlled by a suitable circuit-breaker so set as to operate in the event of the phase currents becoming unbalanced to the extent of 10 per cent of the rated current consumption of the electrode boiler under normal conditions of operation:\n(c) An inverse time element device may be used in conjunction with the aforesaid circuit-breaker to prevent the operation thereof unnecessarily on the occurrence of unbalanced phase currents of momentary or short duration.\n(d) The supplier shall serve a notice in writing on the telegraph authority at least seven days prior to the date on which such supply of energy is to be afforded specifying the location of every point (including the earth connection of the electrode boiler) at which the system is connected with earth.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 71
    },
    "prev_section": "71",
    "next_section": "73"
}