    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "67",
        "title": "67. Connection with earth",
        "chapter": null,
        "content": "(a) limit the touch and step potential to tolerable values;\n(b) limit the ground potential rise to tolerable values so as to prevent danger due to transfer of potential through ground, earth wires, cable sheath, fences, pipe lines, etc.;\n(c) maintain the resistance of the earth connection to such a value as to make operation of the protective device effective.\n(a) the neutral point of every generator and transformer shall be earthed by connecting it to the earthing system as defined in rule 61(4) and hereinabove by not less than two separate and distinct connections:\n(b) in the event of an appreciable harmonic current flowing in the neutral connection so as to cause interference, with communication circuits, the generator or transformer neutral, shall be earthed through a suitable impedance;\n(c) in case of the delta-connected system the neutral point shall be obtained by the insertion of a grounding transformer and current limiting resistance or impedance; wherever considered necessary at the commencement of such a system.]\n[(b) Every earthing system belonging to either the supplier or the consumer shall be tested for its resistance to earth on a dry day during dry season not less than once a year. Records of such tests shall be maintained and shall be produced, if required, before the Inspector or any officer appointed to assist him and authorised under sub-rule (2) of rule 4-A.]",
        "footnote": "",
        "is_definition": false,
        "sort_order": 66
    },