    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "54",
        "title": "54. Declared voltage of supply to consumer",
        "chapter": null,
        "content": "[(i) in the case of low or medium voltage, by more than 6 per cent, or;\n(ii) in the case of high voltage, by more than 6 per cent on the higher side or by more than 9 per cent on the lower side, or;\n[(iii) in the case of extra-high voltage, by more than 10 per cent on the higher side or by more than 12.5 per cent on the lower side:]",
        "footnote": "",
        "is_definition": false,
        "sort_order": 54
    },
    "prev_section": "53",
    "next_section": "55"
}