    "act_title": "The Indian Electricity Rules, 1956",
    "act_slug": "the-indian-electricity-rules-1956",
    "section_label": "Section",
    "section": {
        "number": "49",
        "title": "49. Leakage on consumer's premises",
        "chapter": null,
        "content": "(a) the consumer does not give all reasonable facilities for inspection and testing of his installation, or\n[(b) when an insulation resistance at the consumer's installation is so low as to prevent safe use of energy,]\n[50. Supply and use of energy\n(a) The following controls of requisite capacity to carry and break the current [are placed]\n(i) a linked switch with fuse(s) or a circuit breaker by low and medium voltage consumers;\n(ii) a linked switch with fuse(s) or a circuit breaker by HV consumers having aggregate installed transformer/apparatus capacity up to 1000 KVA to be supplied at voltage upto 11 KV and 2500 KVA at higher voltages (above 11 KV and not exceeding 33 KV);\n(iii) a circuit breaker by HV consumers having an aggregate installed transformer/apparatus capacity above 1000 KVA and supplied at 11 KV and above 2500 KVA supplied at higher voltages (above 11 KV and not exceeding 33 KV);\n(iv) a circuit breaker by EHV consumer:\nProvided that where the point of commencement of supply and the consumer apparatus are near each other, one linked switch with fuse(s) or circuit breaker near the point of commencement of supply as required by this clause shall be considered sufficient for the purpose of this rule.\n(b) In case of every transformer the following shall be provided:-\n(i) On primary side for transformers a linked switch with fuse(s) or circuit breaker of adequate capacity:\nProvided that the linked switch on the primary side of the transformer may be of such capacity as to carry the full load current and to break only the magnetising current of the transformer:\n[Provided further that for all transformers:-\n(A) having a capacity of 5000 KVA and above and installed before the commencement of the Indian Electricity (Amendment-1) Rules, 2000; and\n(B) having a capacity of 1000 KVA and above and installed on or after the commencement of the Indian Electricity (Amendment-1) Rules, 2000 a circuit breaker shall be provided:]\n[Provided further that the provision of linked switch on the primary side of the transformer shall not apply to the unit auxiliary transformer of the generator.\n[(ii) In respect of all transformers installed on or after the commencement of the Indian Electricity (Amendment-1) Rules, 2000, on the secondary side of all transformers transforming HV to EHV, MV or LV a circuit breaker of adequate rating shall be installed:\nProvided that for suppliers' transformers of capacity upto 630 KVA, a linked switch with fuse or circuit breaker of adequate rating shall be installed on secondary side;]\n[(c) except in the case of composite control gear designed as a unit every distinct circuit is protected against excess energy by means of suitable cut-out or a circuit breaker of adequate breaking capacity suitably located and so constructed as to prevent danger from overheating, arcing or scattering of hot metal when it comes into operation and to permit for ready renewal of the fusible metal of the cut-out without danger;\n(d) the supply of energy to each motor or a group of motors or other apparatus meant for operating one particular machine is controlled by a suitable linked switch or a circuit breaker or an emergency tripping device with manual reset of requisite capacity placed in such a position as to be adjacent to the motor or a group of motors or other apparatus readily accessible to and easily operated by the person incharge and so connected in the circuit that by its means all supply of energy can be cut off from the motor or group of motors or apparatus from any regulating switch, resistance of other device associated therewith;\n(e) all insulating materials are chosen with special regard to the circumstances of its proposed use and their mechanical strength is sufficient for its purpose and so far as is practicable of such a character or so protected as to maintain adequately its insulating property under all working conditions in respect of temperature and moisture; and\n(f)\tadequate precautions shall be taken to ensure that no live parts are so exposed as to cause danger.\n[50-A. Additional provisions for supply and use of energy in multi-storeyed buildings (more than 15 metres in height)",
        "footnote": "",
        "is_definition": false,
        "sort_order": 50
    },
    "prev_section": "48",
    "next_section": "51"
}