    "act_title": "The Cold Storage Order, 1980",
    "act_slug": "the-cold-storage-order-1980",
    "section_label": "Section",
    "section": {
        "number": "3",
        "title": "3. Installation Requirements",
        "chapter": null,
        "content": "Table 1\nTable 1\nMinimum Air Duct Area and Openings\nMinimum Air Duct Area and Openings\n(Clause 3.1.3)\nWeight of the refrigerant in the system\nMechanical discharge of air\nDuct area\nOpen window of door area\nKg\nm 3 /min\nm 2\nm 2\n(1)\n(2)\n(3)\n(4)\n10\n3.9\n0.03\n0.44\n25\n7.1\n0.05\n0.7.0\n50\n11.3\n0.05\n1.0\n75\n14.8\n0.07\n1.2\n100\n18.0\n0.07\n1.4\n125\n20.8\n0.10\n1.6\n150\n235\n0.10\n1.7\n200\n28.5\n0.12\n2.0\n250\n33\n0.12\n2.2\n300\n37\n0.14\n2.4\n350\n41\n0.18\n2.6\n400\n45\n0.18\n2.8\n450\n49\n0.18\n3.0\n500\n53\n0.20\n3.1\n600\n59\n0.20\n3.4\n700\n66\n0.20\n3.7\n800\n72\n0.20\n4.0\n900\n78\n0.20\n4.2\n1000\n83\n0.20\n4.4\n1250\n97\n0.28\n5.0\n1500\n109\n0.35\n5.4\n2000\n132\n0.40\n6.3\n2500\n154\n0.45\n7.0\n3000\n173\n0.50\n7.7\n3500\n192\n0.54\n8.3\n4000\n210\n0.58\n8.8\n4500\n227\n0.60\n9.4\n5000\n244\n0.65\n9.9\n6000\n275\n0.70\n10.8\n7000\n305\n0.72\n11.7\n8000\n333\n0.75\n12.5\n9000\n361\n0.78\n13.3\n10000\n387\n0.81\n14.0\n12000\n437\n0.83\n15.3\n14000\n484\n0.84\n16.6\n16000\n529\n0.86\n17.7\n18000\n572\n0.88\n18.8\n20000\n614\n0.90\n20.0\nNote 1. - Mechanical discharge of air and open area have been derived from the following formula taken from DIN 8975 Refrigeration Plants, Safety Principles for their Construction, Equipment and Erection :\nNote 1.\nNote 2. - Intermediate values may be obtained by calculation.\nNote 2.\nTable 2\nTable 2\nMaximum Permissible Quantities of Inflammable Refrigerants\nMaximum Permissible Quantities of Inflammable Refrigerants\n(Clause 3.8)\nName\nChemical formula\nMaximum quantity g/m 3\nButane\nC 4 H 10\n40\nEthane\nC 2 H 6\n40\nEthyl Chloride\nC 2 H5C\n100\nEthylene\nC 2 H 4\n32\nIsobutane\n(CH 3 ) 3 CH\n40\nMethyl\nCH 3 C1\n160\nMethyl Format\nCHOOCH 3\n110\nPropane\nC 2 H 8\n40\n(a) name and make of the condensing unit;\n(b) model of condensing unit;\n(c) name and full charge of refrigerant;\n(d) full charge of oil;\n(e) quantity of refrigerant and oil charged in the system with date of charging ;\n(f) pressure at which the system is tested after installation; and\n(g) change of refrigerant, if any, with date.",
        "footnote": "",
        "is_definition": false,
        "sort_order": 28
    },
    "prev_section": "2",
    "next_section": "4"
}